3.3.4.4 Horizontal wall vent termination
The position of the horizontal vent termination must be positioned in such a way as to meet all local building codes. Attach the correct length of vertical section pipe and an elbow fitting to the stove. Mark the center line of the pipe facing the wall (allowing for a 1/4” rise per foot of horizontal, example 10 ft of horizontal would require a rise of 2.5”).
NOTE: ALLOWING THE VENT PIPE TO SLOPE DOWN TOWARDS THE VENT TERMINATION COULD CAUSE POOR COMBUSTION AND/OR HIGH TEMPERTURES THAT MAY PRESENT A FIRE HAZARD.
Mark a 10” x 10” square around the center mark (inside dimensions).Cut and frame the exterior wall to except the wall thimble. Install the wall thimble shield using wood screws. If the wall being penetrated is constructed of
Siding
Siding standoff
Wall Thimble
10” Duravent
Part #942
Screws
Apply sealant
On four sides
Caution: When installing the terminal on to vinyl siding, a vinyl siding kit or furring strips must be used to prevent the terminal from being recessed into the siding.
When the termination is to be attached to vinyl siding, apply a bead of
Before sliding the pipe into the termination, ensure that you have slid the decorative wall thimble cover and penetration heat shield over the pipe.
Slide the pipe into the vent, making sure that at least 11/4” overlap between the pipe and the terminal. Attach the pipe by attaching two sheet metal screws through the terminal straps and into the pipe. Bend back the straps towards the terminal making sure they are hidden by the decorative thimble. Finally attach the wall penetration heat shield and secure with wood screws
16