Avalon Stoves Cedar EF Installation Addenda, Addendum #2 Interior Masonry Chimney Conversions

Page 41

Installation Addenda

39

ADDENDUM #2 Interior Masonry Chimney Conversions

Interior Masonry Chimney

• Follow the requirements and

use the equipment listed in

the illustration to the right to

install this appliance into an

interior masonry chimney.

• Maximum vertical rise is 40'

• Minimum vertical rise is 10'

• See the chart on page 14 for

determining the correct

The entire chimney system must be air-tight. Make sure to seal the flashing, clean-out, and thimble connection, and to inspect the chimney.

Make sure the coaxial pipe maintains a 1” clearance to any combustible. The vent must be sealed air-tight.

#991 High Wind

Termination

Flashing (included in

#934 Masonry

Conversion Kit

High-Temp

Silicone .

restrictor position.

NOTE: these restrictor

positions are based upon lab

tests. The ideal restrictor

position may vary slightly

#990 90° Elbow

#711 Flex Liner (4” dia.)

(or other UL 1777 Gas

 

Liner)

Co-Axial Straight

Lengths

Connector with Cover

(included in #934 Masonry

Conversion Kit)

Standard Masonry Fireplace

The entire chimney system must be air-tight. Seal the connector cover and inspect the chimney.

. -Temp HighSilicone

Make sure the coaxial pipe maintains a 1” clearance to any combustible. The vent must be sealed air-tight.

#991 High Wind

Termination

Flashing (included in

#934 Masonry

Conversion Kit)

#711 Flex Liner (4” dia.)

(or other UL 1777 Gas Liner)

Connector (included in #934 Masonry Conversion Kit) secured and sealed to block-off plate.

Travis Industries

4 1 2 2 1 0 4

9 3 5 0 8 1 1 7

Image 41 Contents
Cedar Manual Page Travis Industries 2 2 1 0 5 0 8 1 1 Introduction1Introduction Important Information Safety Precautions This Manual Table of Contents Specifications5 Installation Preparation Installation WarningsPacking List Stove ClearancesGas Line Installation Heater Placement RequirementsFloor Protection Requirements Gas Inlet PressureManuafacturer R i e s Vent RequirementsRestrictor Position Approved Vent ConfigurationsMeasuring Vent Lengths T EOffset Length Hor. Offset Vert. Rise Vertical Terminations with 0, 2, or 4 45 OffsetsRestrictor Position #Horizontal Terminations with One 90 Elbow Restrictor Restrictor Position # 5feet 10feet 15feet 20feet Restrictor Position # Vertical Terminations with Two 90 ElbowsRise every 12 of travel PositionTermination Requirements see the illustration below Finalizing the Installation Correct Opening the Door Log Set and Coal Installation Operation21 Safety NoticeLocation Gas Control ValveStarting The Pilot Flame 22OperationOperation23 Adjusting the Flame HeightStarting the Heater for the First Time Turning the Heater On and Off24Operation Optional Blower Adjusting the SpeedNormal Operating Sounds Normal Operating OdorsYearly Service Procedure Maintenance25Cleaning Your Heater Troubleshooting Steps 26MaintenanceHow this Heater Works Maintenance27What Turns the Main Burners On and Off What Prevents Gas BuildupReplacement Parts 28MaintenanceWiring Diagram Minimum Clearances to Combustibles Safety Label2000 2001 2002 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec.0398Years 1 & 2 Coverage Parts & Labor Limited 7 Year WarrantyYears 3 Through 5 Coverage Parts & Labor Years 6 & 7 Coverage Parts onlyLP Conversion Instructions Optional EquipmentPlace Nutdriver 32Optional EquipmentFrom the air shutter by Sliding it to the leftOff the pilot Fireback 34Optional EquipmentBack Stove Blower36Optional Equipment Gold Door Before installing the ventGold Grill Gold TrivetAddendum #1 Class a Chimney Conversion Kit 38Installation AddendaAddendum #2 Interior Masonry Chimney Conversions Installation AddendaInterior Masonry Chimney Standard Masonry Fireplace40Index