Carrier 42BVC Electrical data, Service Switches, 42BHC,BVC Electric Heater Data Availability

Page 37

Electrical data

42BHC,BVC ELECTRIC HEATER DATA AVAILABILITY

 

 

 

42BHC,BVC ELECTRIC HEATER DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

 

 

 

42BHC UNIT SIZE

 

 

 

 

 

 

 

 

FULL LOAD AMPS

 

 

06

08

10

 

12

16

 

20

30

40

 

kW

 

Single-Phase

 

Three-Phase

 

 

 

 

 

 

1

 

 

 

 

 

120 V

208 V

240 V

277 V

208 V

240 V

480 V

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

8.3

4.8

4.2

3.6

2.8

2.4

1.2

2

 

 

 

 

 

1.5

 

12.5

7.2

6.3

5.4

4.2

2.4

1.2

2.5

 

 

 

 

 

2

 

16.7

9.6

8.3

7.2

5.6

4.8

2.4

3

 

 

 

 

 

2.5

 

20.8

12.0

10.4

9.0

6.9

6.0

3.0

3.5

 

 

 

 

 

3

 

25.0

14.4

12.5

10.8

8.3

7.2

3.6

4

 

 

 

 

 

3.5

 

29.2

16.8

14.6

12.6

9.7

8.4

4.2

4.5

 

 

 

 

 

4

 

33.3

19.2

16.7

14.4

11.1

9.6

4.8

5

 

 

 

 

 

4.5

 

37.5

21.6

18.8

16.2

12.5

10.8

5.4

6

 

 

 

 

 

5

 

41.7

24.0

20.8

18.1

13.9

12.0

6.0

7

 

 

 

 

 

6

 

28.8

25.0

21.7

16.7

14.4

7.2

8

 

 

 

 

 

7

 

23.7

29.2

25.3

19.4

16.8

8.4

10

 

 

 

 

 

8

 

38.5

33.3

28.9

22.2

19.2

9.6

12

 

 

 

 

 

10

 

47.6

41.3

35.7

27.5

23.8

11.9

15

 

 

 

 

 

12

 

43.3

33.3

28.9

14.4

16

 

 

 

 

 

15

 

41.6

36.1

18.0

20

 

 

 

 

 

16

 

44.4

38.5

19.2

25

 

 

 

 

 

20

 

47.9

23.9

30

 

 

 

 

 

25

 

30.1

35

 

 

 

 

 

30

 

36.1

40

 

 

 

 

 

35

 

42.1

 

 

 

 

 

 

 

 

 

 

 

 

40

 

48.0

LEGEND

Standard Offering

NOTES:

1.Stages available:

Single phase: 1-12 kW, 1 stage only 3-12 kW, 1 stage or 2 stage

Three phase: 1-40 kW, 1 stage only 4-40 kW, 1 or 2 stage

12-40 kW, 1, 2 or 3 stage

2.Electric Heating Capacities (Btuh) = Heater kW x 3413

3.Electric Heater Amperage for Single-phase Power

=(Heater kW x 1000)/Applied Voltage Electric Heater Amp. for 3-phase Power

=(Heater kW x 1000)/(Applied Voltage x 1.73).

MOTOR PERFORMANCE DATA (AMPS)

VOLTAGE

 

 

 

Nominal HP

 

 

 

V-Ph-Hz

1/4

1/3

1/2

3/4

1

11/2

2

3

5

115-1-60

5.2

6.0

8.6

13.3

14.4

208-1-60

3.0

3.6

4.8

6.5

7.4

9.4

11.0

230-1-60

2.5

3.0

4.2

6.6

6.0

9.0

10.9

277-1-60

2.1

2.5

3.6

5.1

5.4

8.5

8.0

208-3-60

2.4

3.6

3.8

6.0

6.5

8.2

230-3-60

2.2

3.0

3.2

4.8

6.2

8.0

14.0

460-3-60

1.1

1.5

1.9

2.8

3.1

4.0

7.0

NOTES:

1.Motor Full Load Amps refer to National Electric Code (NEC) Amps; actual motor nameplate amps may vary.

2.NEC data extrapolated for 277 v.

3.Motors are open drip proof, ball bearing, single speed, 1750 rpm rated at continuous duty, 140 F ambient with reversible rotation.

Service Switches:

The service switch is an On/Off switch on incoming power supply to unit. Proper amperage load must be determined before switch can be selected. The range of the fused or non-fused service switch is 0 to 40 amps.

Amp Load = [Motor amps + Heater amps (if required)]* 1.20.

The UL listing signifies that Carrier’s fan coil units have been examined by UL and comply with the organization’s applicable standards of U.S. and Canadian national product safety standard, UL 1995/CSA C22.2 No. 236.

37

Image 37
Contents Variety of coil options reduces first cost Features/Benefits42BHC Unit 42BVC UnitTable of contents Physical data Model number nomenclatureSize Nominal Cfm Coil Rows Factory-installed options Options and accessoriesField-installed accessories 42BHC, BVC Options and AccessoriesAux Thermostat Functions42BHC FAN Coil Base Unit no Controls Base unit dimensionsUnit 42BHC42BHC FAN Coil with Motor Control Option 42BHC FAN Coil with Electric Heat Option 42BVC FAN Coil Base Unit no Controls Dimensions Supply Duct Return Duct42BVC Fan Size42BVC FAN Coil with Motor Control Option 42BVC FAN Coil with Electric Heat Option Dimensions42BHC Weight 42BHC Unit Corner Weights lbTotal Weight Unit Correction Factor lb 42BVC Unit Corner Weights lbMixing BOX Accessory dimensions42BHC,BVC Unit SizeMixing BOX Rails Piping Size Close Valve PackagesOFF Head Stub OUT Sizes Row Coil SO Piping Connection Location DiagramNominal Heat Options 42BHC,BVC Coil Rows Basic definitions Application dataUnit Hand Piping Components Piping Components WAY Motorized Valve Electric Formulas Selection procedure42BHC,BVC Airflow Correction Factors Performance dataDirect Expansion DX Correction Factors Altitude Cooling Correction Factors42BHC,BVC Nominal Heating Capacities 42BHC, BVC Nominal Cooling Capacities42BHC,BVC 6-ROW Cooling Capacity by Gpm 42BHC,BVC 4-ROW Cooling Capacity by Gpm42BHC,BVC 4-ROW Cooling Capacity by ∆T 42BHC,BVC 8-ROW Cooling Capacity by Gpm42BHC, BVC 8-ROW Cooling Capacity by ∆T 42BHC, BVC 6-ROW Cooling Capacity by ∆TCFM Suction 42BHC,BVC Temp F Size Blower CFM 42BHC,BVC Unit Horsepower Data TableRpm Bhp Unit Horsepower Data Table Cv Factor by Coil and Unit Size 42BHC,BVC Component Static Resistance in. wgRow Filter42BHC,BVC Unit Size Nominal CFM Sound Power DataCenter Frequency Hz 125 250 1000 2000 4000Typical wiring schematics Page Typical wiring schematics Electrical data Service Switches42BHC,BVC Electric Heater Data Availability Motor Performance Data AmpsControls Standard control featuresMotor control options Motor and electric heat control optionsSystem Fan Coil Unit Guide specificationsCarrier Corporation Syracuse, New York 05A