Carrier 42BHC, 42BVC manual Carrier Corporation Syracuse, New York 05A

Page 40

Guide specifications (cont)

2)One-in. pleated, (2) 1-in. throwaway or 2-in pleated MERV 11 filters with 2-in. pre-filter shall be installed as indicated on the equipment schedule.

c.Insulation:

1)Units shall be equipped with 1-in. thick Tuf-Skin™ II insulation (standard).

2)Units are available with ¾-in. closed cell, 1-in. Tuf-Skin Rx™ edge sealed, or 1-in. foil-faced insulation.

d.Controls:

1)Unit shall be equipped with 24-v trans- former, motor contactor and terminal strip for connection to field or factory provided controller.

2)Unit shall be equipped with interlock- ing door-disconnect switch, touch-type fusing, 24-v transformer, motor con- tactor and terminal strip for connec- tion to field provided controller.

3)Unit shall be equipped with interlock- ing door-disconnect switch, separate motor and electric heater touch-type fusing, 24-v transformer, motor con- tactor and terminal strip for connec- tion to field-provided or factory- provided controller.

e.Motor(s):

Single-phase motors are capacitor start and shall include automatic reset thermal over- load protection and shall be available in 115, 208, 230, or 277 volts (60 Hz). Three-phase motors shall be available in 208, 230, or 460 volts (60 Hz).

f.Electric Heat:

1)Electric heaters shall be constructed of high-grade resistance wire supported by ceramic insulators on plated steel brackets. The heat elements shall be suspended in front of the outlet, after the blower and coil. High-limit thermal cutouts shall protect the heat elements in the event of an air failure.

2)Single-phase heaters shall be available in 115, 208, 230, or 277 volts (60 Hz). Three-phase electric heat shall be available in 208, 230, or 460 volts (60 Hz).

2.Field-Installed Accessories:

a.Mixing Boxes:

2)Mixing boxes shall include

a linkage kit, which consists of two crank arms, 2 swivels and a rod, 25 in. long (for unit sizes 06-16) or 84 in. long (for unit sizes 20-40), for the field installation of the actuator.

b.Thermostats:

Three thermostats shall be available for field installation:

1)The single stage heat thermostat shall feature manual changeover, off-cool- heat system switch, on-auto fan mode switch, single-stage electric heat, and outside air signal.

2)The 2-stage heat thermostat shall fea- ture automatic/manual changeover, digital display of temperatures and all functions, off-cool-heat-auto system mode buttons, single speed fan opera- tion, on-auto fan mode button, single or two stage electric heat signal, out- side air signal and optional remote temperature sensor.

3)The single-stage heat, 2-pipe heat/ cool thermostat shall feature digital display of ambient temperature and operating mode, single fan speed oper- ation, power and operating mode but- tons, continuous fan operation, cycling water control valve, 4-pipe automatic changeover/manual changeover with “on-auto” fan mode button, optional one or 2-stage electric heat signal, and purge cycle, temperature sensor for 2-pipe cold water/hot water systems, and programmable operating range, dead band, digital display, tempera- ture set-back.

c.Valve Packages:

1)Valve packages shall be factory- assembled for field installation.

2)Basic valve packages shall include 2-way or 3-way valves with balancing valves and 2 ball valves.

3)Deluxe valve packages shall include a circuit setting and a strainer in addition to the features included in the basic valve package.

1)Mixing boxes shall be preassembled at the factory and shipped separately with base rails.

 

 

 

Carrier Corporation • Syracuse, New York 13221

9-05A

9-05

 

 

 

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

3

 

New Book

4

Pg 40

Catalog No. 524-236

Printed in U.S.A.

Form 42B-1PD

Tab

7a

 

 

Tab

4FC4

 

 

 

 

Replaces: 42BHC-1PD

 

 

 

 

 

 

 

 

 

 

 

Image 40
Contents Features/Benefits Variety of coil options reduces first cost42BHC Unit 42BVC UnitTable of contents Physical data Model number nomenclatureSize Nominal Cfm Coil Rows Options and accessories Factory-installed optionsField-installed accessories 42BHC, BVC Options and AccessoriesThermostat Functions AuxBase unit dimensions 42BHC FAN Coil Base Unit no ControlsUnit 42BHC42BHC FAN Coil with Motor Control Option 42BHC FAN Coil with Electric Heat Option Dimensions Supply Duct Return Duct 42BVC FAN Coil Base Unit no Controls42BVC Fan Size42BVC FAN Coil with Motor Control Option Dimensions 42BVC FAN Coil with Electric Heat Option42BHC Unit Corner Weights lb 42BHC Weight42BVC Unit Corner Weights lb Total Weight Unit Correction Factor lbAccessory dimensions Mixing BOX42BHC,BVC Unit SizeMixing BOX Rails Piping Size Close Valve PackagesOFF Head Stub OUT Sizes Row Coil SO Piping Connection Location DiagramNominal Heat Options 42BHC,BVC Coil Rows Basic definitions Application dataUnit Hand Piping Components Piping Components WAY Motorized Valve Electric Selection procedure FormulasPerformance data 42BHC,BVC Airflow Correction FactorsDirect Expansion DX Correction Factors Altitude Cooling Correction Factors42BHC, BVC Nominal Cooling Capacities 42BHC,BVC Nominal Heating Capacities42BHC,BVC 4-ROW Cooling Capacity by Gpm 42BHC,BVC 6-ROW Cooling Capacity by Gpm42BHC,BVC 8-ROW Cooling Capacity by Gpm 42BHC,BVC 4-ROW Cooling Capacity by ∆T42BHC, BVC 6-ROW Cooling Capacity by ∆T 42BHC, BVC 8-ROW Cooling Capacity by ∆TCFM Suction 42BHC,BVC Temp F Size Blower CFM 42BHC,BVC Unit Horsepower Data TableRpm Bhp Unit Horsepower Data Table 42BHC,BVC Component Static Resistance in. wg Cv Factor by Coil and Unit SizeRow FilterSound Power Data 42BHC,BVC Unit Size Nominal CFMCenter Frequency Hz 125 250 1000 2000 4000Typical wiring schematics Page Typical wiring schematics Service Switches Electrical data42BHC,BVC Electric Heater Data Availability Motor Performance Data AmpsStandard control features ControlsMotor control options Motor and electric heat control optionsGuide specifications System Fan Coil UnitCarrier Corporation Syracuse, New York 05A