Carrier 42BVC manual Performance data, 42BHC,BVC Airflow Correction Factors

Page 23

Performance data

42BHC,BVC AIRFLOW CORRECTION FACTORS

CFM RATIO

TOTAL (Ct)

SENSIBLE (Cs)

(Actual/Base)

 

 

1.40

1.25

1.26

1.35

1.22

1.23

1.30

1.19

1.20

1.25

1.16

1.17

1.20

1.13

1.14

1.15

1.10

1.11

1.10

1.07

1.08

1.05

1.04

1.04

1.00

1.00

1.00

0.95

0.97

0.97

0.90

0.94

0.93

0.85

0.90

0.89

0.80

0.86

0.85

0.75

0.82

0.81

0.70

0.78

0.77

0.65

0.74

0.72

0.60

0.70

0.67

0.55

0.66

0.62

0.50

0.62

0.57

0.45

0.58

0.52

0.40

0.53

0.47

0.35

0.48

0.42

0.30

0.43

0.38

0.25

0.38

0.33

NOTE: Use Sensible Heat correction factors when calculating heating capacity.

DIRECT EXPANSION (DX) CORRECTION FACTORS

% OF

CORRECTION FACTOR

NOMINAL CFM

Total

Sensible

80

0.95

0.93

90

0.97

0.96

100

1.00

1.00

110

1.02

1.04

120

1.05

1.08

Consult factory for values outside of table.

DX Total Capacity (MBtuh) = Base Et x Total Correction Factor

DX Sensible Capacity (MBtuh) = Base Es x Sensible Correction Factor

%of Nominal Cfm = Actual Cfm (from Fan Performance table) ÷ Nominal Cfm

ALTITUDE COOLING CORRECTION FACTORS

ELEVATION (ft)

TOTAL HEAT (Et)

SENSIBLE HEAT (Es)

1000

0.99

0.96

2000

0.98

0.93

3000

0.97

0.89

4000

0.96

0.86

5000

0.94

0.83

6000

0.93

0.80

7000

0.92

0.77

8000

0.91

0.75

9000

0.90

0.73

42BHC,BVC HOT WATER CAPACITY CORRECTION FACTORS

ENTERING AIR

 

 

 

ENTERING WATER TEMPERATURE (F)

 

 

 

TEMPERATURE (F)

100

110

120

130

140

150

160

170

180

190

200

50

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

1.182

1.273

1.364

55

0.409

0.500

0.591

0.682

0.773

0.864

0.955

1.045

1.136

1.227

1.318

60

0.363

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

1.182

1.273

65

0.318

0.409

0.500

0.591

0.682

0.773

0.864

0.955

1.045

1.136

1.227

70

0.272

0.363

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

1.182

75

0.227

0.318

0.409

0.500

0.591

0.682

0.773

0.864

0.955

1.045

1.136

80

0.182

0.272

0.363

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

NOTES:

1.Leaving air temperature not to exceed 104 F with standard motor.

2.Base capacity ratings based on 180 F entering water temperature and 70 F entering air temperature.

3.Hot Water Heating Capacity (MBtuh) = Rated Heating Capacity x Hot Water Capacity Correction Factor x Sensible Airflow Correc- tion Factor.

23

Image 23
Contents 42BVC Unit Features/BenefitsVariety of coil options reduces first cost 42BHC UnitTable of contents Size Nominal Cfm Coil Rows Model number nomenclaturePhysical data 42BHC, BVC Options and Accessories Options and accessoriesFactory-installed options Field-installed accessoriesAux Thermostat Functions42BHC Base unit dimensions42BHC FAN Coil Base Unit no Controls Unit42BHC FAN Coil with Motor Control Option 42BHC FAN Coil with Electric Heat Option Fan Size Dimensions Supply Duct Return Duct42BVC FAN Coil Base Unit no Controls 42BVC42BVC FAN Coil with Motor Control Option 42BVC FAN Coil with Electric Heat Option Dimensions42BHC Weight 42BHC Unit Corner Weights lbTotal Weight Unit Correction Factor lb 42BVC Unit Corner Weights lbUnit Size Accessory dimensionsMixing BOX 42BHC,BVCMixing BOX Rails OFF Valve PackagesPiping Size Close Nominal Piping Connection Location DiagramHead Stub OUT Sizes Row Coil SO Heat Options 42BHC,BVC Coil Rows Unit Hand Piping Components Application dataBasic definitions Piping Components WAY Motorized Valve Electric Formulas Selection procedureAltitude Cooling Correction Factors Performance data42BHC,BVC Airflow Correction Factors Direct Expansion DX Correction Factors42BHC,BVC Nominal Heating Capacities 42BHC, BVC Nominal Cooling Capacities42BHC,BVC 6-ROW Cooling Capacity by Gpm 42BHC,BVC 4-ROW Cooling Capacity by Gpm42BHC,BVC 4-ROW Cooling Capacity by ∆T 42BHC,BVC 8-ROW Cooling Capacity by Gpm42BHC, BVC 8-ROW Cooling Capacity by ∆T 42BHC, BVC 6-ROW Cooling Capacity by ∆TCFM Suction 42BHC,BVC Temp F Rpm Bhp Unit Horsepower Data TableSize Blower CFM 42BHC,BVC Unit Horsepower Data Table Filter 42BHC,BVC Component Static Resistance in. wgCv Factor by Coil and Unit Size Row1000 2000 4000 Sound Power Data42BHC,BVC Unit Size Nominal CFM Center Frequency Hz 125 250Typical wiring schematics Page Typical wiring schematics Motor Performance Data Amps Service SwitchesElectrical data 42BHC,BVC Electric Heater Data AvailabilityMotor and electric heat control options Standard control featuresControls Motor control optionsSystem Fan Coil Unit Guide specificationsCarrier Corporation Syracuse, New York 05A