Application data (cont)
PIPING COMPONENTS (cont)
SYMBOL/SKETCH | DESCRIPTION | CV FACTOR | RATING* | |||
1/2 | 3/4 | PSI | F | |||
|
| |||||
| BALANCE VALVE: Variable water flow manual bal- |
|
|
|
| |
| ancing valve with screwdriver slot adjustment |
|
|
|
| |
| screw. |
|
|
|
| |
| Application — Often used in conjunction with test | 3.0 | 8.9 | 150 | 200 | |
| port fittings for water flow balancing. Balance by | |||||
| temperature differential or coil pressure drop |
|
|
|
| |
| (check specifications for service fittings required if |
|
|
|
| |
| balancing by pressure drop). May be used in |
|
|
|
| |
| valve bypass line to permit equal flow balancing. |
|
|
|
| |
| STRAINER: |
|
|
|
| |
| steel screen. |
|
|
|
| |
| Application — Used for removal of small particles |
|
|
|
| |
| from system water during normal system operation. | 9.0 | 19.0 |
|
| |
| Should not be used in lieu of main system strain- | 400 | 250 | |||
| ers. Strainer screen may have to be removed dur- | Clean | Clean | |||
|
|
| ||||
| ing initial high pressure system flushing during |
|
|
|
| |
|
|
|
|
| ||
| per normal maintenance schedule (provisions for |
|
|
|
| |
| strainer |
|
|
|
| |
| BALL VALVE: Manual balance and |
|
|
|
| |
| Application — Used for unit isolation and water flow |
|
|
|
| |
| balancing. Without memory stop feature water bal- | 4.0 | 7.5 | 400 | 200 | |
| ance point must be marked by installer (if neces- | |||||
|
|
|
|
| ||
| sary). Check specifications for service fittings |
|
|
|
| |
| required when used for water balancing. |
|
|
|
|
LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
*Check all system component pressure ratings (coils, values, pumps, etc.) with manufacturer and any applicable local or national piping codes prior to specifying system pressure rating.
20