Options and accessories
42BHC, BVC OPTIONS AND ACCESSORIES
ITEM | OPTION* | ACCESSORY† |
Automatic Air Vents | X |
|
Controls | X |
|
Electric Heat | X |
|
Filters | X |
|
Heating/Cooling Coils | X |
|
Insulation | X |
|
Mixing Boxes |
| X |
Motors | X |
|
Thermostats |
| X |
Valve Packages |
| X |
|
| |
|
|
The 42BHC and 42BVC fan coil units are designed to offer maximum flexibility in an application, accessibility for service, quiet operation and durability.
Factory-installed options
Automatic air vents — Automatic air vents have fiber- washers, which allow air in the pipes to pass through, automatically bleeding the system. The fiber washers elimi- nate the need to manually remove air from the system. When wet, washers swell and seal the system.
Coils — Coils are available in a choice of
Reheat operation is standard. Preheat is available as an option.
Controls
•Interlocking disconnect switch
•Heater power fusing
•24 v Class 2 transformer (40 va)
•
•Auto reset temperature limit switch
•Airflow safety switch
•Motor power fusing
•Motor control contactor
•24 v condensate overflow switch
Electric heat — Total electric heat eliminates the require- ment for a boiler. Heating and/or cooling may be available on an individual basis throughout the year. Resistance electric heat is available from 1.0 kW to 40.0 kW (refer to
electric heater data table for availability per unit) with
Voltages:
•115 v, 208 v, 230 v and 277 v
•208 v, 230 v and 480 v
Electric heat is available with the following staging options
•1 to 12 kW 1 stage only — single phase
•3 to 12 kW 1 or 2 stage only — single phase
•1 to 40 kW 1 stage only — 3 phase
•4 to 40 kW 1 or 2 stage only — 3 phase
•12 to 40 kW 1, 2, or 3 stage — 3 phase
Heater coils are constructed of
Filters — Two in. pleated filters are standard.
Insulation —
Motors — A wide selection of standard motors provides efficient operation in ducted applications with excellent performance with up to 2 inches of total static pressure.
Available motor options:
•115 v, 208 v, 230 v and 277 v
•208 v, 230 v and 460 v
•Open
•External junction box
Field-installed accessories
Mixing boxes — Mixing boxes can be used when outside air is required for ventilation. Preassembled at the factory and shipped separately with base rails for field installation, mixing boxes include a linkage kit consisting of two crank arms, 2 swivels and either a 25 in. long (for sizes
4