Page 4

Options and accessories

42BHC, BVC OPTIONS AND ACCESSORIES

ITEM

OPTION*

ACCESSORY†

Automatic Air Vents

X

 

Controls

X

 

Electric Heat

X

 

Filters

X

 

Heating/Cooling Coils

X

 

Insulation

X

 

Mixing Boxes

 

X

Motors

X

 

Thermostats

 

X

Valve Packages

 

X

*Factory-installed option.

 

 

†Field-installed accessory.

 

 

The 42BHC and 42BVC fan coil units are designed to offer maximum flexibility in an application, accessibility for service, quiet operation and durability.

Factory-installed options

Automatic air vents — Automatic air vents have fiber- washers, which allow air in the pipes to pass through, automatically bleeding the system. The fiber washers elimi- nate the need to manually remove air from the system. When wet, washers swell and seal the system.

Coils — Coils are available in a choice of two-pipe system with 4-row cooling/heating or four-pipe system with 4, 6 or 8-row cooling and 1 or 2 row heating.

Reheat operation is standard. Preheat is available as an option.

Controls

Interlocking disconnect switch

Heater power fusing

24 v Class 2 transformer (40 va)

8-pole control terminal strip

Auto reset temperature limit switch

Airflow safety switch

Motor power fusing

Motor control contactor

24 v condensate overflow switch

Electric heat — Total electric heat eliminates the require- ment for a boiler. Heating and/or cooling may be available on an individual basis throughout the year. Resistance electric heat is available from 1.0 kW to 40.0 kW (refer to

electric heater data table for availability per unit) with single-stage or multiple-stage, single power source.

Voltages:

115 v, 208 v, 230 v and 277 v single-phase 60 Hz

208 v, 230 v and 480 v three-phase 60 Hz

Electric heat is available with the following staging options (3-phase staging is balanced).

1 to 12 kW 1 stage only — single phase

3 to 12 kW 1 or 2 stage only — single phase

1 to 40 kW 1 stage only — 3 phase

4 to 40 kW 1 or 2 stage only — 3 phase

12 to 40 kW 1, 2, or 3 stage — 3 phase

Heater coils are constructed of high-grade resistance wire that is supported by ceramic insulators on plated steel brackets. These heat elements are suspended directly in front of the outlet after the blower and the coil. High limit thermal cutouts protect the heater in the event of air failure.

Filters — Two in. pleated filters are standard. One-in. pleated, two 1-in. throwaway, or 2-in. MERV (minimum efficiency reporting value) 11 filters with 2-in. pleated pre-filter are available. The 2-in. MERV 11 filters with 2-in. pleated pre-filter include a filter rack.

Insulation — Tuf-Skin™ II (1-in. thick) insulation is standard. Units are available with ¾-in. closed cell, 1-in. Tuf-Skin Rx™ edge sealed, or 1-in. foil-faced insulation.

Motors — A wide selection of standard motors provides efficient operation in ducted applications with excellent performance with up to 2 inches of total static pressure.

Available motor options:

115 v, 208 v, 230 v and 277 v single-phase 60 Hz

208 v, 230 v and 460 v three-phase 60 Hz

Open drip-proof motors

External junction box

Field-installed accessories

Mixing boxes — Mixing boxes can be used when outside air is required for ventilation. Preassembled at the factory and shipped separately with base rails for field installation, mixing boxes include a linkage kit consisting of two crank arms, 2 swivels and either a 25 in. long (for sizes 06-16) or a 84 in. long (for sizes 20-40) rod for field installation of an actuator.

4

Image 4
Contents Features/Benefits Variety of coil options reduces first cost42BHC Unit 42BVC UnitTable of contents Physical data Model number nomenclatureSize Nominal Cfm Coil Rows Options and accessories Factory-installed optionsField-installed accessories 42BHC, BVC Options and AccessoriesThermostat Functions AuxBase unit dimensions 42BHC FAN Coil Base Unit no ControlsUnit 42BHC42BHC FAN Coil with Motor Control Option 42BHC FAN Coil with Electric Heat Option Dimensions Supply Duct Return Duct 42BVC FAN Coil Base Unit no Controls42BVC Fan Size42BVC FAN Coil with Motor Control Option Dimensions 42BVC FAN Coil with Electric Heat Option42BHC Unit Corner Weights lb 42BHC Weight42BVC Unit Corner Weights lb Total Weight Unit Correction Factor lbAccessory dimensions Mixing BOX42BHC,BVC Unit SizeMixing BOX Rails Piping Size Close Valve PackagesOFF Head Stub OUT Sizes Row Coil SO Piping Connection Location DiagramNominal Heat Options 42BHC,BVC Coil Rows Basic definitions Application dataUnit Hand Piping Components Piping Components WAY Motorized Valve Electric Selection procedure FormulasPerformance data 42BHC,BVC Airflow Correction FactorsDirect Expansion DX Correction Factors Altitude Cooling Correction Factors42BHC, BVC Nominal Cooling Capacities 42BHC,BVC Nominal Heating Capacities42BHC,BVC 4-ROW Cooling Capacity by Gpm 42BHC,BVC 6-ROW Cooling Capacity by Gpm42BHC,BVC 8-ROW Cooling Capacity by Gpm 42BHC,BVC 4-ROW Cooling Capacity by ∆T42BHC, BVC 6-ROW Cooling Capacity by ∆T 42BHC, BVC 8-ROW Cooling Capacity by ∆TCFM Suction 42BHC,BVC Temp F Size Blower CFM 42BHC,BVC Unit Horsepower Data TableRpm Bhp Unit Horsepower Data Table 42BHC,BVC Component Static Resistance in. wg Cv Factor by Coil and Unit SizeRow FilterSound Power Data 42BHC,BVC Unit Size Nominal CFMCenter Frequency Hz 125 250 1000 2000 4000Typical wiring schematics Page Typical wiring schematics Service Switches Electrical data42BHC,BVC Electric Heater Data Availability Motor Performance Data AmpsStandard control features ControlsMotor control options Motor and electric heat control optionsGuide specifications System Fan Coil UnitCarrier Corporation Syracuse, New York 05A