Carrier 42BVC, 42BHC manual Guide specifications, System Fan Coil Unit

Page 39

Guide specifications

System Fan Coil Unit

HVAC Guide Specifications — 42B

Size Range: 600 to 4000 Nominal Cfm

Carrier Model Number:

42BHC (Horizontal Fan Coil Unit) 42BVC (Vertical Fan Coil Unit)

Part 1 — General

1.01SYSTEM DESCRIPTION

Horizontal and vertical, 2-pipe or 4-pipe, belt- driven, galvanized casing model fan coil unit for ducted installation above the ceiling or within floor mounted cabinet, with full access to internal components.

1.02QUALITY ASSURANCE

A.Unit performance shall be rated in accordance with ARI Standard 440-2005.

B.Unit construction shall comply with ASHRAE (latest edition) Safety Code and NEC.

C.Unit shall be constructed in accordance with ETL and ETL, Canada standards. Factory-installed motors and electric heaters shall be UL approved.

D. Each coil

shall be

factory tested

for leakage

at

350-psig air pressure

with coil

submerged

in

water.

Insulation

and

adhesive

shall meet

NFPA-90A requirements for flame spread and smoke generation.

E. Each coil shall be factory tested for leakage at 350 psig air pressure with coil submerged in water. Insulation and adhesive shall meet NFPA-90A requirements for flame spread and smoke genera- tion. Factory-installed motors shall be UL approved.

1.03DELIVERY, STORAGE AND HANDLING

Unit shall be handled and stored in accordance with the manufacturer’s instructions.

Part 2 — Products

2.01EQUIPMENT

A.General:

Factory-assembled, horizontal and vertical, draw- thru type fan coil unit for ducted installation above the ceiling or floor mounting. Unit shall be complete with water coils, fan(s), motor, belt drive, drain pan, and filter.

B.Casing:

Construction shall be heavy-gage galvanized steel, lined with one-in. thick fiberglass Tuf-Skin™ II thermal/acoustical insulation. Knockouts shall be provided for hanging the horizontal unit, that will accept 3/8-in. threaded rod at the top, and bottom of all unit corners. Supply and return duct connec- tion shall be 1 in. long. Removable side panels shall be provided for access to the fan/motor assembly. A double-sloped drain pan shall be constructed of stainless steel, extending under the full length and

width of the coil(s) with a 3/4-in. male nominal pipe thread stainless steel drain connection and 1/2-in.

male MPT stainless secondary drain connection (capped when not required). The outside surface of the drain pan shall be insulated with 1/8-in. closed cell insulation.

C.Fans:

Belt-driven, double-width fan wheels shall have forward-curved blades and be statically and dynami- cally balanced. Fan drive shall consist of variable- pitch motor pulley, fixed-pitch fan pulley and V-belt. Fans and scrolls shall be of galvanized steel.

D.Coils:

Standard unit shall be equipped with a 4-row coil for installation in a 2-pipe system and additional rows of coil shall be provided for installation in a 4-pipe sys- tem as described in the Options and Accessories section. Coils shall have 1/2-in. copper tubes, alumi- num fins bonded to the tubes by mechanical expan- sion and have a working pressure of 250 psig at 200 F. Each coil shall have a manual air vent and sweat connections for copper tubes.

E.Operating Characteristics:

A single-circuit coil unit installed in a 2-pipe system shall be capable of providing heating or cooling as determined by the operating mode of the central water supply system. A double-circuit coil unit installed in a 4-pipe system shall be capable of pro- viding sequenced heating and cooling.

F.Motor(s):

Fan motors shall be open, drip-proof, single-speed, 60 Hz, 1750 rpm 1 or 3 phase, suitable for contin- uous duty at 104 F (40 C). Single phase motors are capacitor start, include automatic reset thermal overload protection and are available in 115, 208, 230, or 277 volts (60 Hz). Three-phase motors are available in 208, 230, or 460 volts (60 Hz). Motors are resilient base mounted (except 3 and 5 hp motors, which are rigid base mounted).

G.Options and Accessories:

1.Factory-Installed Options:

a.Coils:

1)Unit coil(s) shall be equipped with auto- matic air vent(s).

2)Unit shall be equipped with a high- capacity 6-row or 8-row coil for installa- tion in a 2-pipe system.

3)For installation in a 4-pipe system, unit shall be equipped with either a 4-row cooling/1-row hot water heating split- circuit coil, or a 4/2, 6/1, or 6/2 split- circuit coil as required.

4)Unit shall be equipped with either a 4- row DX (direct expansion) cooling coil or a 6-row DX cooling coil as required.

5)Unit coil(s) shall be copper fin, copper tube with stainless steel tube and sheets.

b.Filters:

1)A two-in. pleated filter shall be installed in the unit (standard).

39

Image 39
Contents 42BVC Unit Features/BenefitsVariety of coil options reduces first cost 42BHC UnitTable of contents Model number nomenclature Physical dataSize Nominal Cfm Coil Rows 42BHC, BVC Options and Accessories Options and accessoriesFactory-installed options Field-installed accessoriesAux Thermostat Functions42BHC Base unit dimensions42BHC FAN Coil Base Unit no Controls Unit42BHC FAN Coil with Motor Control Option 42BHC FAN Coil with Electric Heat Option Fan Size Dimensions Supply Duct Return Duct42BVC FAN Coil Base Unit no Controls 42BVC42BVC FAN Coil with Motor Control Option 42BVC FAN Coil with Electric Heat Option Dimensions42BHC Weight 42BHC Unit Corner Weights lbTotal Weight Unit Correction Factor lb 42BVC Unit Corner Weights lbUnit Size Accessory dimensionsMixing BOX 42BHC,BVCMixing BOX Rails Valve Packages Piping Size CloseOFF Piping Connection Location Diagram Head Stub OUT Sizes Row Coil SONominal Heat Options 42BHC,BVC Coil Rows Application data Basic definitionsUnit Hand Piping Components Piping Components WAY Motorized Valve Electric Formulas Selection procedureAltitude Cooling Correction Factors Performance data42BHC,BVC Airflow Correction Factors Direct Expansion DX Correction Factors42BHC,BVC Nominal Heating Capacities 42BHC, BVC Nominal Cooling Capacities42BHC,BVC 6-ROW Cooling Capacity by Gpm 42BHC,BVC 4-ROW Cooling Capacity by Gpm42BHC,BVC 4-ROW Cooling Capacity by ∆T 42BHC,BVC 8-ROW Cooling Capacity by Gpm42BHC, BVC 8-ROW Cooling Capacity by ∆T 42BHC, BVC 6-ROW Cooling Capacity by ∆TCFM Suction 42BHC,BVC Temp F Unit Horsepower Data Table Size Blower CFM 42BHC,BVCRpm Bhp Unit Horsepower Data Table Filter 42BHC,BVC Component Static Resistance in. wgCv Factor by Coil and Unit Size Row1000 2000 4000 Sound Power Data42BHC,BVC Unit Size Nominal CFM Center Frequency Hz 125 250Typical wiring schematics Page Typical wiring schematics Motor Performance Data Amps Service SwitchesElectrical data 42BHC,BVC Electric Heater Data AvailabilityMotor and electric heat control options Standard control featuresControls Motor control optionsSystem Fan Coil Unit Guide specificationsCarrier Corporation Syracuse, New York 05A