DUAL PUMP UNITS — ENGLISH
30XA |
| MOUNTING WEIGHT (lb) — Cu/Cu* |
| ||||
UNIT SIZE | A | B | C | D | E | F | Total |
090 | 1394 | 3347 | 1369 | 1093 | 2330 | 1392 | 10,924 |
100 | 1420 | 3409 | 1406 | 1117 | 2382 | 1418 | 11,151 |
110 | 1433 | 3452 | 1428 | 1139 | 2416 | 1424 | 11,291 |
1201467 3491 1430 1142 2449 1458 11,436
30XA |
|
| MOUNTING WEIGHT (lb) — Cu/Cu* |
|
| ||||
UNIT SIZE | A | B | C | D | E | F | G | H | Total |
140 | 2188 | 1735 | 2012 | 1889 | 1273 | 1004 | 1876 | 1990 | 13,966 |
160 | 2242 | 1762 | 2029 | 1919 | 1299 | 1019 | 1896 | 2043 | 14,209 |
DUAL PUMP UNITS — SI
30XA |
| MOUNTING WEIGHT (kg) — Cu/Cu* |
|
|
| ||||
UNIT SIZE | A | B | C | D | E | F | Total |
|
|
090 | 632 | 1518 | 621 | 496 | 1057 | 631 | 4955 |
|
|
100 | 644 | 1546 | 638 | 507 | 1080 | 643 | 5058 |
|
|
110 | 650 | 1566 | 648 | 517 | 1096 | 646 | 5122 |
|
|
120 | 665 | 1583 | 649 | 518 | 1111 | 661 | 5187 |
|
|
30XA |
|
| MOUNTING WEIGHT (kg) — Cu/Cu* |
|
| ||||
UNIT SIZE | A | B | C | D | E | F | G | H | Total |
140 | 992 | 787 | 913 | 857 | 577 | 455 | 851 | 903 | 6335 |
160 | 1017 | 799 | 921 | 871 | 589 | 462 | 860 | 927 | 6445 |
*Condenser Coil: Copper Fins/Copper Tubing. |
|
|
|
|
|
|
|
|
| 30XA140,160 |
| |
| COOLER SIDE |
|
| COOLER SIDE |
| |
|
|
|
|
| ||
C | B | A | D | C | B | A |
|
|
|
a30-4420
a30-4421
DEFEFGH
COMPRESSOR SIDE | COMPRESSOR SIDE |
Fig. 15C — Unit Mounting Weights (Units with Cu/Cu Condenser Coils) (cont)
RIGGING UNIT (See Fig.
Do not use a forklift truck to move the units.
Use spreader bars to keep cables or chains clear of unit sides. As further protection plywood sheets may be placed against sides of unit, behind cables or chains. Run cables or chains to a central suspension point so that angle from horizontal is not less than 45 degrees. Raise and set unit down carefully.
See Fig.
For shipping, some domestic units and all export units are mounted on a wooden skid under entire base of unit. Skid can be removed before unit is moved to installation site. Lift the unit from above to remove skid. See Fig.
If overhead rigging is not available, the unit can be moved on rollers or dragged. When unit is moved on rollers, the unit
skid, if equipped, must be removed. To lift the unit, use jacks at the rigging points. Use a minimum number of rollers to distrib- ute the load such that the rollers are no more than 6 ft (1.8 m) apart. If the unit is to be dragged, lift the unit as described above, and place unit on a pad. Apply moving force to the pad, and not the unit. When in its final location, raise the unit and remove the pad. If the unit was shipped with coil protection, it must be removed before
Step 3 — Cooler Fluid and Drain Piping Con- nections — See Fig.
CAUTION
Remove the chilled water flow switch, entering and leaving water thermistors before welding connecting piping. Rein- stall flow switch and thermistors after welding is complete. Failure to remove these devices may cause unit damage.
GENERAL — The