Carrier 30XA080-500 specifications Make Electrical Connections

Page 62

Step 5 — Make Electrical Connections

WARNING

Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon- nect locations to alert others not to restore power until work is completed.

POWER SUPPLY — The electrical characteristics of the available power supply must agree with the unit nameplate rating. Supply voltage must be within the limits shown. See Tables 5-11 for electrical and configuration data.

FIELD POWER CONNECTIONS (See Fig. 37) — All power wiring must comply with applicable local and national codes. Install field-supplied, branch circuit fused disconnect(s) of a type that can be locked off or open. Disconnect(s) must be locat- ed within sight and readily accessible from the unit in compli- ance with NEC Article 440-14 (U.S.A.). See Tables 5-11 for unit electrical data.

IMPORTANT: The 30XA units have a factory-installed option available for a non-fused disconnect for unit power supply. If the unit is equipped with this option, all field power wiring should be made to the non-fused disconnect since no terminal blocks are supplied.

Maximum wire size that the unit terminal block or non- fused disconnect will accept is 500 kcmil.

POWER WIRING — All power wiring must comply with ap- plicable local and national codes. Install field-supplied branch circuit fused disconnect per NEC of a type that can be locked OFF or OPEN. Disconnect must be within sight and readily ac- cessible from the unit in compliance with NEC Article 440-14. In the power box, 7/8 in. holes are provided for power entry. The holes will need to bee enlarged to accept the appropriate conduit. NEC also requires all conduits from a conditioned space to the power box(es) be sealed to prevent airflow and moisture into the control box.

The 30XA units require 1 or 2 power supplies, depending on the unit and circuit voltage. See Tables 5-8 for chiller elec- trical data. Cooler and pump heaters, if factory-installed, are wired in the control circuit. Heaters on chillers with the option- al control transformer will be capable of operation only when the main power supply to the chiller is on. On chillers with sep- arate control power, the heaters are capable of operation when- ever the control power is supplied.

FIELD CONTROL POWER CONNECTIONS (See Fig. 37) — All units require 115-1-60 control circuit power, unless the control transformer option is installed.

Terminals TB5-1 and TB5-2 are provided for field installa- tion of a chilled water (fluid) pump interlock (CWPI). The chilled water (fluid) flow sensor (CWFS) is factory installed. These devices are to be installed in series. Contacts must be rated for dry-circuit applications capable of handling a 24-vac at 50 mA load.

An accessory remote on-off switch can be wired into TB5-9 and TB5-10. Contacts must be rated for dry-circuit applications capable of handling a 24-vac at 50 mA load.

CAUTION

Do not use interlocks or other safety device contacts connected between TB5-9 and TB5-10 as remote on-off. Connection of safeties or other interlocks between these 2 terminals will result in an electrical bypass if the ENABLE-OFF-REMOTE contact switch is in the ENABLE position. If remote on-off unit control is required, a field-supplied relay must be installed in the unit control box and wired as shown in Fig. 37. Failure to wire the remote on-off as recommended may result in tube freeze damage.

Terminals 11 and 13 of TB5 are for control of the chilled water pump 1 (PMP1) starter. Terminals 13 and 15 of TB5 are for control of the chilled water pump 2 (PMP2) starter.

CARRIER COMFORT NETWORK® COMMUNICATION BUS WIRING (See Fig. 38) — The communication bus wiring is a shielded, 3-conductor cable with drain wire and is field supplied and installed in the field.

The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN (Carrier Comfort Network) should be made at TB (terminal block) 3. Consult the CCN Contractor’s Manual for further information. See Fig. 38.

NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating tempera- ture range of –4 F (–20 C) to 140 F (60 C) is required. See Table 12 for a list of manufacturers that produce CCN bus wiring that meet these requirements.

It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain- ing different colored wires. At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the result- ing continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only).

To connect the unit to the network:

1.Turn off power to the control box.

2.Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. Substitute appropri- ate colors for different colored cables.

3.Connect the red wire to (+) terminal on TB3 of the plug, the white wire to COM terminal, and the black wire to the

(–) terminal.

62

Image 62
Contents Installation Instructions Place, Mount, and Rig the Unit AquaForce Chiller Model Number Designation A30-440130XA080 Air-Cooled Liquid Chiller Dimensions Right END View A30-4403100 4404090 110A30-4405 30XA090-120 Air-Cooled Liquid Chiller with Pump Dimensions Front View 160 140115.88 115.64Back View A30-440730XA140,160 Air-Cooled Liquid Chiller with Pump Dimensions 2300 30XA180,200 Air-Cooled Liquid Chiller Dimensions A30-4174 220 46.17 171.42 240 46.23 170.83 A30-4409614 532 208 132 1500 4260 4798 4799 5221 8363 300 260280 A30-4177614 532 208 132 1900 5011 5747 5760 6184 9555 A30-4178325 350614 532 208 132 1900 6205 6941 6954 7378 10750 A30-4181 4182 A30Left END View Front View A30 A30-4183 450500 A30-418 A30-41 Back View Unit Mounting Weights Units with Mchx Condenser Coils 30XA140,160 30XA080 30XA220-30030XA090-120 30XA325-350 30XA400-50030XA090-120 30XA140,160 A30-4421Dual Pump Units English Unit Mounting Weights Units with Al/Cu Condenser Coils Cooler Side ED CBA K L M N O P Compressor Side FG HIJ 1273 2898 1160 972 2089 1271 662 1273 3106 1248 972 2089 1271 959 Unit Mounting Weights Units with Cu/CU Condenser Coils 30XA080 30XA090-1201394 3139 1280 1093 2330 1392 10,627 Do not use a forklift truck to move the units A30-4420 A30-4421Physical Data, 30XA080-500 English Unit 30XAPhysical Data, 30XA080-500 SI Refrigerant Charge kg Ckt A/Ckt B/Ckt C MchxUnit Rigging Label Detail 30XA080-200 A30-4427A30-4428 Unit Rigging Label Detail 30XA400-500 30XA Typical Piping and Wiring Units with Hydronic Package Cooler Option Dimensions A30-4413A30-4417 A30-4418A30-4138 A30-4414A30-4415 PT Hydronic Pump PackageA30-4002 Thermal Flow Sensor A30-343230XA Minimum and Maximum Cooler Flow Rates Minimum Maximum NominalDetail a 30XA080-12030XA140-500 A30-3997A30-4411 A30-441230XA Pump Impeller Sizes090-160 FTV-5 Rpm Impeller Dia30XA120 30XA090,10030XA110 30XA140A30-4439 A30-4436A30-4437 A30-44403450 RPM Page Make Electrical Connections NON-FUSED Disconnect Unit Voltage Number No Hydronic Package Unit Voltage Number Unit Voltage Number No Hydronic Package 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 Unit Voltage Number Unit Voltage Number No Hydronic Package 230-60 207 253 592.4 800 869.3 700 607.0 883.9 115 30XA140-500 Electrical Data, Dual Point High Ambient Option 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 230-60 207 253 383.8/256.9 600/350 660.8/436.2 450/300 115 Power and Control Connections Compressor and Fan Electrical Data Unit Cond Size FansA30-4001 CCN Communication Bus WiringPump Electrical Data A30-3999 A30-4000Refrigerant Charge Page Copyright 2009 Carrier Corporation
Related manuals
Manual 8 pages 25.4 Kb

30XA080-500 specifications

The Carrier 30XA080-500 is a sophisticated air-cooled chiller designed for large commercial and industrial applications, renowned for its energy efficiency and reliability. This model is part of Carrier's extensive range of chillers, providing an optimal solution for space cooling needs while supporting sustainability goals.

One of the main features of the 30XA080-500 is its advanced scroll compressor technology. This design not only enhances the chiller's efficiency but also ensures quieter operation. The compressors operate with a high efficiency at partial loads, making the 30XA080-500 ideal for buildings with varying cooling demands. The unit also incorporates multiple compressors, allowing for enhanced reliability through redundancy; if one compressor fails, others can maintain performance.

The 30XA080-500 is equipped with high-performance evaporators and condensers which facilitate superior heat exchange. The unit features a fin-and-tube heat exchanger design, optimized for maximum surface area and minimal air resistance, thus enhancing overall performance. Moreover, the chiller is built with microchannel technology, which significantly reduces the refrigerant charge while improving efficiency through better heat transfer.

In terms of controls, the Carrier 30XA080-500 utilizes advanced VFD (Variable Frequency Drive) technology. This allows the system to adjust motor speed to match building loads, further increasing efficiency and reducing energy consumption. The intuitive control options enable users to monitor performance and make adjustments easily, helping optimize system operations in real time.

Another highlight of the 30XA080-500 is its environmentally conscious refrigerant, R-410A, which is known for its low Global Warming Potential (GWP). This makes the unit compliant with current and future environmental regulations, ensuring that users can operate within legal limits while reducing their carbon footprint.

The durability of the 30XA080-500 is enhanced by a rugged construction designed to withstand various weather conditions, making it suitable for outdoor installation. Insulated panels and protective coatings guard against corrosion, extending the lifespan of components and reducing maintenance costs.

In conclusion, the Carrier 30XA080-500 is a high-efficiency chiller that offers advanced technology, reliable performance, and environmental consciousness, making it an excellent choice for modern commercial buildings seeking to balance cooling needs with sustainability and energy savings. Its combination of innovative features positions it as a leader in the chiller market.