Carrier 30XA080-500 specifications

Page 61

PUMP MODIFICATION/TRIMMING — Since the pumps are constant speed, the only way to obtain greater flow with a given pump/impeller is to decrease system head. This will allow the pump to “ride” its curve to the right, resulting in increased flow. If greater flow is necessary, consider opening the combination valve. Also, verify that the strainer is clean, and that no unnecessary system resistance is present, such as partially closed isolation valves.

Once the combination valve is set, note the stem position. If later service work requires the valve to be closed, it will be easier to re-balance the system, if the original balance point is known.

Increasing system resistance by closing the balancing valve will force the pump to “ride” its curve to the left, resulting in less flow. Although this does reduce power consumption slightly, it may not be the desirable method of reducing the flow, especially if a large reduction is needed.

The other method for reducing flow on a constant speed pump is impeller trimming. The impellers in the pumps provid- ed in the 30XA hydronic kit can be easily removed for this purpose. Refer to the vendor literature packet supplied with the hydronic package information on Seal Replacement in the Service section, and follow instructions for impeller removal and trimming. See Fig. 33 and 34 for pump envelope curve in- formation. Trimming should only be done by a qualified ma- chine shop that has experience in this operation. Contact your local Carrier representative for a recommended machine shop.

CAUTION

After trimming, the impeller MUST be balanced. Failure to balance trimmed impellers can result in excessive vibra- tion, noise, and premature bearing failure.

Impeller trimming has the added benefit of maximum bhp (brake horsepower) savings, which can recover the cost incurred by performing the impeller trimming.

FREEZE PROTECTION — The 30XA units are provided with a flow switch to protect against freezing situations that occur from no water flow. While the flow switch is helpful in preventing freezing during no-flow situations, it does not protect the chiller in case of power failure during sub-freezing ambient temperatures, or in other cases where water tempera- ture falls below the freezing mark. Appropriate concentrations of inhibited propylene or ethylene glycol or other suitable inhibited antifreeze solution should be considered for chiller protection where ambient temperatures are expected to fall below 32 F (0° C). Consult local water treatment specialist on characteristics of the system water and add a recommended inhibitor to the chilled water. The Carrier warranty does not cover damage due to freezing.

If the pump will be subjected to freezing temperatures, steps must be taken to prevent freeze damage. If the pump will not be used during this time, it is recommended to drain the pump and hydronic package and these components are backflushed with inhibited glycol. Otherwise, a glycol-water solution should be considered as the heat transfer fluid. Drains are locat- ed on the pump(s) and suction guide/strainer for units with hy- dronic kits. Units without hydronic kits have a drain plug mounted on the bottom of the cooler head at each end of the cooler.

NOTE: Do not use automobile anti-freeze, or any other fluid that is not approved for heat exchanger duty. Only use

appropriately inhibited glycols, concentrated to provide ade- quate protection for the temperature considered.

Use an electric tape heater for the external piping, if unit will be exposed to freezing temperatures.

Ensure that power is available to the chiller at all times, even during the off-season, so that the pump and cooler heaters have power. Also make sure that the piping tape heaters have power.

On units with pump packages, a heater is supplied with the hydronic package that will protect this section from freezing in outdoor-air temperatures down to –20 F (–29 C), except in the case of a power failure. The Carrier warranty does not cover damage due to freezing.

All units are equipped with cooler heaters. Units are protect- ed from freezing down to 0° F (–18 C) through the cooler heat- ers and control algorithms. If the unit controls the chilled water pump and valves, allowing flow through the cooler, the unit is protected from freezing down to –20 F (–29 C). The Carrier warranty does not cover damage due to freezing.

PREPARATION FOR WINTER SHUTDOWN — If the unit is not operational during the winter months, at the end of cooling season complete the following steps.

CAUTION

Failure to remove power before draining heater equipped coolers and hydronic packages can result in heater tape and insulation damage.

1.If the unit has optional heater tapes on the cooler and the cooler will not be drained, do not shut off power discon- nect during off-season shutdown. If the unit has optional heater tapes on the cooler and the cooler is drained, open the circuit breaker for the heater, CB-13 or shut off power during off-season shutdown.

2.Draining the fluid from the system is highly recommend- ed. If the unit is equipped with a hydronic package, there are additional drains in the pump housing and strainer that must be opened to allow for all for all of the water to drain.

3.Isolate the cooler from the rest of the system with water shutoff valves.

4.Replace the drain plug and completely fill the cooler with a mixture of water and a suitable corrosion-inhibited anti- freeze solution such as propylene glycol. The concentra- tion should be adequate to provide freeze protection to 15° F (8.3° C) below the expected low ambient tempera- ture conditions. Antifreeze can be added through the vent on top of the cooler. If the unit has a hydronic pump pack- age, the pump must be treated in the same manner.

5.Leave the cooler filled with the antifreeze solution for the winter, or drain if desired. Be sure to deenergize heaters (if installed) as explained in Step 1 to prevent damage. Use an approved method of disposal when removing anti- freeze solution.

At the beginning of the next cooling season, be sure that there is refrigerant pressure on each circuit before refilling cooler, add recommended inhibitor, and reset the CB-HT (cir- cuit breaker heater) (if opened) or restore power.

61

Image 61
Contents Installation Instructions Place, Mount, and Rig the Unit A30-4401 AquaForce Chiller Model Number Designation30XA080 Air-Cooled Liquid Chiller Dimensions A30-4403 Right END View090 4404100 110A30-4405 30XA090-120 Air-Cooled Liquid Chiller with Pump Dimensions Front View 115.88 140160 115.64A30-4407 Back View30XA140,160 Air-Cooled Liquid Chiller with Pump Dimensions 2300 30XA180,200 Air-Cooled Liquid Chiller Dimensions A30-4174 A30-4409 220 46.17 171.42 240 46.23 170.83614 532 208 132 1500 4260 4798 4799 5221 8363 280 260300 A30-4177A30-4178 614 532 208 132 1900 5011 5747 5760 6184 9555350 325614 532 208 132 1900 6205 6941 6954 7378 10750 A30-4181 A30 4182Left END View Front View A30 500 450A30-4183 A30-418 A30-41 Back View Unit Mounting Weights Units with Mchx Condenser Coils 30XA090-120 30XA325-350 30XA080 30XA220-30030XA140,160 30XA400-500A30-4421 30XA090-120 30XA140,160Dual Pump Units English Unit Mounting Weights Units with Al/Cu Condenser Coils Cooler Side ED CBA K L M N O P Compressor Side FG HIJ 1273 2898 1160 972 2089 1271 662 1273 3106 1248 972 2089 1271 959 Unit Mounting Weights Units with Cu/CU Condenser Coils 30XA090-120 30XA0801394 3139 1280 1093 2330 1392 10,627 A30-4420 A30-4421 Do not use a forklift truck to move the unitsUnit 30XA Physical Data, 30XA080-500 EnglishRefrigerant Charge kg Ckt A/Ckt B/Ckt C Mchx Physical Data, 30XA080-500 SIA30-4427 Unit Rigging Label Detail 30XA080-200A30-4428 Unit Rigging Label Detail 30XA400-500 30XA Typical Piping and Wiring Units with Hydronic Package A30-4413 Cooler Option DimensionsA30-4418 A30-4417A30-4414 A30-4138PT Hydronic Pump Package A30-4415A30-4002 A30-3432 Thermal Flow SensorMinimum Maximum Nominal 30XA Minimum and Maximum Cooler Flow Rates30XA140-500 30XA080-120Detail a A30-3997A30-4412 A30-4411090-160 FTV-5 Pump Impeller Sizes30XA Rpm Impeller Dia30XA110 30XA090,10030XA120 30XA140A30-4437 A30-4436A30-4439 A30-44403450 RPM Page Make Electrical Connections NON-FUSED Disconnect Unit Voltage Number No Hydronic Package Unit Voltage Number Unit Voltage Number No Hydronic Package 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 Unit Voltage Number Unit Voltage Number No Hydronic Package 230-60 207 253 592.4 800 869.3 700 607.0 883.9 115 30XA140-500 Electrical Data, Dual Point High Ambient Option 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 230-60 207 253 383.8/256.9 600/350 660.8/436.2 450/300 115 Power and Control Connections Unit Cond Size Fans Compressor and Fan Electrical DataPump Electrical Data CCN Communication Bus WiringA30-4001 A30-4000 A30-3999Refrigerant Charge Page Copyright 2009 Carrier Corporation
Related manuals
Manual 8 pages 25.4 Kb

30XA080-500 specifications

The Carrier 30XA080-500 is a sophisticated air-cooled chiller designed for large commercial and industrial applications, renowned for its energy efficiency and reliability. This model is part of Carrier's extensive range of chillers, providing an optimal solution for space cooling needs while supporting sustainability goals.

One of the main features of the 30XA080-500 is its advanced scroll compressor technology. This design not only enhances the chiller's efficiency but also ensures quieter operation. The compressors operate with a high efficiency at partial loads, making the 30XA080-500 ideal for buildings with varying cooling demands. The unit also incorporates multiple compressors, allowing for enhanced reliability through redundancy; if one compressor fails, others can maintain performance.

The 30XA080-500 is equipped with high-performance evaporators and condensers which facilitate superior heat exchange. The unit features a fin-and-tube heat exchanger design, optimized for maximum surface area and minimal air resistance, thus enhancing overall performance. Moreover, the chiller is built with microchannel technology, which significantly reduces the refrigerant charge while improving efficiency through better heat transfer.

In terms of controls, the Carrier 30XA080-500 utilizes advanced VFD (Variable Frequency Drive) technology. This allows the system to adjust motor speed to match building loads, further increasing efficiency and reducing energy consumption. The intuitive control options enable users to monitor performance and make adjustments easily, helping optimize system operations in real time.

Another highlight of the 30XA080-500 is its environmentally conscious refrigerant, R-410A, which is known for its low Global Warming Potential (GWP). This makes the unit compliant with current and future environmental regulations, ensuring that users can operate within legal limits while reducing their carbon footprint.

The durability of the 30XA080-500 is enhanced by a rugged construction designed to withstand various weather conditions, making it suitable for outdoor installation. Insulated panels and protective coatings guard against corrosion, extending the lifespan of components and reducing maintenance costs.

In conclusion, the Carrier 30XA080-500 is a high-efficiency chiller that offers advanced technology, reliable performance, and environmental consciousness, making it an excellent choice for modern commercial buildings seeking to balance cooling needs with sustainability and energy savings. Its combination of innovative features positions it as a leader in the chiller market.