Step 4 — Fill the Chilled Water Loop.

IMPORTANT: Before starting unit, be sure all of the air has been purged from the system.

SYSTEM

DILUTED

POT FEEDER AND TRANSFER PUMP

WARNING

In low ambient (below 32 F [0° C]) and/or low leaving fluid temperature applications (below 40 F [4.4° C]), a suit- able antifreeze solution of the proper concentration for the specific operating conditions must be used as the fluid cir- culated through the cooler to prevent freezing and damage to the system. Failure to operate the system with an anti- freeze solution of the proper concentration will void the warranty should damage result from freezing.

The chilled water pump (if equipped) is rated for 150 psig (1034 kPa) duty. The maximum cooler fluidside pressure is 300 psig (2068 kPa). Check the pressure rating for all of the

CLEANING

AGENT

 

 

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPORARY

 

 

30XA UNIT

 

 

PUMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPORARY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a30-4411

 

 

TO DRAIN

 

BYPASS

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 31 — Typical Set Up for Cleaning Process

SYSTEM

chilled water devices installed. Do not exceed the lowest pres-

DILUTED

POT FEEDER AND TRANSFER PUMP

sure rated device.

WATER SYSTEM CLEANING — Proper water system cleaning is of vital importance. Excessive particulates in the water system can cause excessive pump seal wear, reduce or stop flow, and cause damage of other components.

1. Install a temporary bypass around the chiller to avoid

circulating dirty water and particulates into the pump

SIDE STREAM FILTER

CLEANING

AGENT

 

x

TEMPORARY

30XA UNIT

PUMP

 

x

package and chiller during the flush. Use a temporary

circulating pump during the cleaning process. Also, be

sure that there is capability to fully drain the system after

cleaning. See Fig. 31.

2. Be sure to use a cleaning agent that is compatible with

all system materials. Be especially careful if the system

contains any galvanized or aluminum components. Both

detergent-dispersant and alkaline-dispersant cleaning

agents are available.

3. It is recommended to fill the system through a water me-

ter. This provides a reference point for the future for loop

volume readings, and it also establishes the correct quan-

tity of cleaner needed in order to reach the required

concentration.

4. Use a feeder/transfer pump to mix the solution and fill the

system. Circulate the cleaning system for the length of

time recommended by the cleaning agent manufacturer.

a.

After cleaning, drain the cleaning fluid and flush the

 

system with fresh water.

b.

A slight amount of cleaning residue in the system can

 

help keep the desired, slightly alkaline, water pH of 8

 

to 9. Avoid a pH greater than 10, since this will

 

adversely affect pump seal components.

c.

A side stream filter is recommended (see Fig. 32 dur-

 

ing the cleaning process). Filter side flow rate should

 

be enough to filter the entire water volume every 3 to

 

4 hours. Change filters as often as necessary during

 

the cleaning process.

d.

Remove temporary bypass when cleaning is complete.

A suction guide with an internal strainer is standard on all 30XA units with factory-installed hydronic packages. This strainer allows removal of particulates from the chilled water loop. Using the combination valve and the field-installed isolation valve at the inlet, the strainer can be isolated from the chilled water loop to be cleaned.

 

 

TEMPORARY

 

 

a30-4412

 

BYPASS

TO DRAIN

 

Fig. 32 — Cleaning Using a Side Stream Filter

The Carrier ComfortLink™ controls provided have a built- in feature to remind building owners or operators to clean the strainer at a pre-set time interval. Properly installed, cleaned and maintained systems will rarely need the strainer cleaned after the initial fill. This time interval is user-configurable.

Ideally, the chilled water loop will be cleaned before the unit is connected. If the run-in screen is left in the suction guide/ strainer, it is recommended that the Service Maintenance be set to alert the operator within 24 hours of start-up to be sure that the run-in screen in the suction guide/strainer is removed after 24 hours of operation.

NOTE: The suction guide/strainer must be removed after the first 24 hours of operation.

To set the time for the parameter, go to Time ClockMCFGW.FIL in the handheld Navigator™ display. To set the time for the parameter with the Touch Pilot™ dis- play, go to Main MenuServiceMAINTCFGwfilter_c. Values for this item are input in days.

WATER TREATMENT — Fill the fluid loop with water (or brine) and a corrosion-resistant inhibitor suitable for the water of the area. Consult the local water treatment specialist for characteristics of system water and a recommended inhibitor for the cooler fluid loop.

Untreated or improperly treated water may result in corro- sion, scaling, erosion, or algae. The services of a qualified wa- ter treatment specialist should be obtained to develop and mon- itor a treatment program.

CAUTION

Water must be within design flow limits, clean, and treated to ensure proper chiller performance and reduce the poten- tial of tube damage due to corrosion, scaling, erosion, and algae. Carrier assumes no responsibility for chiller damage resulting from untreated or improperly treated water.

56

Image 56
Contents Installation Instructions Place, Mount, and Rig the Unit AquaForce Chiller Model Number Designation A30-440130XA080 Air-Cooled Liquid Chiller Dimensions Right END View A30-44034404 090100 110A30-4405 30XA090-120 Air-Cooled Liquid Chiller with Pump Dimensions Front View 140 115.88160 115.64Back View A30-440730XA140,160 Air-Cooled Liquid Chiller with Pump Dimensions 2300 30XA180,200 Air-Cooled Liquid Chiller Dimensions A30-4174 220 46.17 171.42 240 46.23 170.83 A30-4409614 532 208 132 1500 4260 4798 4799 5221 8363 260 280300 A30-4177614 532 208 132 1900 5011 5747 5760 6184 9555 A30-4178325 350614 532 208 132 1900 6205 6941 6954 7378 10750 A30-4181 4182 A30Left END View Front View A30 A30-4183 450500 A30-418 A30-41 Back View Unit Mounting Weights Units with Mchx Condenser Coils 30XA080 30XA220-300 30XA090-120 30XA325-35030XA140,160 30XA400-50030XA090-120 30XA140,160 A30-4421Dual Pump Units English Unit Mounting Weights Units with Al/Cu Condenser Coils Cooler Side ED CBA K L M N O P Compressor Side FG HIJ 1273 2898 1160 972 2089 1271 662 1273 3106 1248 972 2089 1271 959 Unit Mounting Weights Units with Cu/CU Condenser Coils 30XA080 30XA090-1201394 3139 1280 1093 2330 1392 10,627 Do not use a forklift truck to move the units A30-4420 A30-4421Physical Data, 30XA080-500 English Unit 30XAPhysical Data, 30XA080-500 SI Refrigerant Charge kg Ckt A/Ckt B/Ckt C MchxUnit Rigging Label Detail 30XA080-200 A30-4427A30-4428 Unit Rigging Label Detail 30XA400-500 30XA Typical Piping and Wiring Units with Hydronic Package Cooler Option Dimensions A30-4413A30-4417 A30-4418A30-4138 A30-4414A30-4415 PT Hydronic Pump PackageA30-4002 Thermal Flow Sensor A30-343230XA Minimum and Maximum Cooler Flow Rates Minimum Maximum Nominal30XA080-120 30XA140-500Detail a A30-3997A30-4411 A30-4412Pump Impeller Sizes 090-160 FTV-530XA Rpm Impeller Dia30XA090,100 30XA11030XA120 30XA140A30-4436 A30-4437A30-4439 A30-44403450 RPM Page Make Electrical Connections NON-FUSED Disconnect Unit Voltage Number No Hydronic Package Unit Voltage Number Unit Voltage Number No Hydronic Package 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 Unit Voltage Number Unit Voltage Number No Hydronic Package 230-60 207 253 592.4 800 869.3 700 607.0 883.9 115 30XA140-500 Electrical Data, Dual Point High Ambient Option 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 230-60 207 253 383.8/256.9 600/350 660.8/436.2 450/300 115 Power and Control Connections Compressor and Fan Electrical Data Unit Cond Size FansA30-4001 CCN Communication Bus WiringPump Electrical Data A30-3999 A30-4000Refrigerant Charge Page Copyright 2009 Carrier Corporation
Related manuals
Manual 8 pages 25.4 Kb

30XA080-500 specifications

The Carrier 30XA080-500 is a sophisticated air-cooled chiller designed for large commercial and industrial applications, renowned for its energy efficiency and reliability. This model is part of Carrier's extensive range of chillers, providing an optimal solution for space cooling needs while supporting sustainability goals.

One of the main features of the 30XA080-500 is its advanced scroll compressor technology. This design not only enhances the chiller's efficiency but also ensures quieter operation. The compressors operate with a high efficiency at partial loads, making the 30XA080-500 ideal for buildings with varying cooling demands. The unit also incorporates multiple compressors, allowing for enhanced reliability through redundancy; if one compressor fails, others can maintain performance.

The 30XA080-500 is equipped with high-performance evaporators and condensers which facilitate superior heat exchange. The unit features a fin-and-tube heat exchanger design, optimized for maximum surface area and minimal air resistance, thus enhancing overall performance. Moreover, the chiller is built with microchannel technology, which significantly reduces the refrigerant charge while improving efficiency through better heat transfer.

In terms of controls, the Carrier 30XA080-500 utilizes advanced VFD (Variable Frequency Drive) technology. This allows the system to adjust motor speed to match building loads, further increasing efficiency and reducing energy consumption. The intuitive control options enable users to monitor performance and make adjustments easily, helping optimize system operations in real time.

Another highlight of the 30XA080-500 is its environmentally conscious refrigerant, R-410A, which is known for its low Global Warming Potential (GWP). This makes the unit compliant with current and future environmental regulations, ensuring that users can operate within legal limits while reducing their carbon footprint.

The durability of the 30XA080-500 is enhanced by a rugged construction designed to withstand various weather conditions, making it suitable for outdoor installation. Insulated panels and protective coatings guard against corrosion, extending the lifespan of components and reducing maintenance costs.

In conclusion, the Carrier 30XA080-500 is a high-efficiency chiller that offers advanced technology, reliable performance, and environmental consciousness, making it an excellent choice for modern commercial buildings seeking to balance cooling needs with sustainability and energy savings. Its combination of innovative features positions it as a leader in the chiller market.