Carrier 30XA080-500 30XA Minimum and Maximum Cooler Flow Rates, Minimum Maximum Nominal

Page 54

Table 3 — 30XA Minimum and Maximum Cooler Flow Rates

 

 

 

ITEM

 

MINIMUM

 

MAXIMUM

 

NOMINAL

 

 

 

Cooler Leaving Water Temperature*

40 F (4.4 C)

 

60 F (15 C)

 

 

 

Cooler Entering Water Temperature†

45 F (7.2 C)

 

70 F (21.1 C)

 

 

30XA

 

 

Cooler

Number of

Minimum Flow Rate

Maximum Flow Rate

Nominal Flow Rate

UNIT SIZE

 

 

Passes

(gpm)

 

(L/s)

(gpm)

 

(L/s)

(gpm)

 

(L/s)

 

 

 

Standard

2

95

 

6.0

379

 

23.9

 

 

 

080

 

 

Plus one pass

3

43

 

2.7

192

 

12.1

180.4

 

11.4

 

 

 

Minus one pass

1

196

 

12.4

782

 

49.3

 

 

 

 

 

 

Standard

2

101

 

6.4

403

 

25.4

 

 

 

090

 

 

Plus one pass

3

43

 

2.7

200

 

12.6

201.9

 

12.7

 

 

 

Minus one pass

1

229

 

14.4

917

 

57.9

 

 

 

 

 

 

Standard

2

101

 

6.4

403

 

25.4

 

 

 

100

 

 

Plus one pass

3

43

 

2.7

200

 

12.6

225.5

 

14.2

 

 

 

Minus one pass

1

229

 

14.4

917

 

57.9

 

 

 

 

 

 

Standard

2

125

 

7.9

501

 

31.6

 

 

 

110

 

 

Plus one pass

3

61

 

3.8

244

 

15.4

244.9

 

15.5

 

 

 

Minus one pass

1

254

 

16.0

1014

 

64.0

 

 

 

 

 

 

Standard

2

125

 

7.9

501

 

31.6

 

 

 

120

 

 

Plus one pass

3

73

 

4.6

293

 

18.5

264.8

 

16.7

 

 

 

Minus one pass

1

281

 

17.7

1124

 

70.9

 

 

 

 

 

 

Standard

2

134

 

8.5

538

 

33.9

 

 

 

140

 

 

Plus one pass

3

73

 

4.6

293

 

18.5

317.8

 

20.1

 

 

 

Minus one pass

1

324

 

20.4

1296

 

81.8

 

 

 

 

 

 

Standard

2

165

 

10.4

660

 

41.6

 

 

 

160

 

 

Plus one pass

3

98

 

6.2

391

 

24.7

365.1

 

23.0

 

 

 

Minus one pass

1

354

 

22.3

1418

 

89.5

 

 

 

 

 

 

Standard

2

202

 

12.7

807

 

50.9

 

 

 

180

 

 

Plus one pass

3

73

 

4.6

391

 

24.7

409.6

 

25.8

 

 

 

Minus one pass

1

416

 

26.2

1662

 

104.9

 

 

 

 

 

 

Standard

2

223

 

14.1

892

 

56.3

 

 

 

200

 

 

Plus one pass

3

98

 

6.2

391

 

24.7

463.9

 

29.3

 

 

 

Minus one pass

1

458

 

28.9

1833

 

115.6

 

 

 

 

 

 

Standard

2

235

 

14.8

941

 

59.4

 

 

 

220

 

 

Plus one pass

3

122

 

7.7

489

 

30.9

505.9

 

31.9

 

 

 

Minus one pass

1

501

 

31.6

2004

 

126.4

 

 

 

 

 

 

Standard

2

266

 

16.8

1063

 

67.1

 

 

 

240

 

 

Plus one pass

3

147

 

9.3

587

 

37.0

545.8

 

34.4

 

 

 

Minus one pass

1

538

 

33.9

2151

 

135.7

 

 

 

 

 

 

Standard

2

257

 

16.2

1027

 

64.8

 

 

 

260

 

 

Plus one pass

3

141

 

8.9

562

 

35.5

600.3

 

37.9

 

 

 

Minus one pass

1

584

 

36.8

2334

 

147.3

 

 

 

 

 

 

Standard

2

293

 

18.5

1173

 

74.0

 

 

 

280

 

 

Plus one pass

3

141

 

8.9

562

 

35.5

642.2

 

40.5

 

 

 

Minus one pass

1

620

 

39.1

2481

 

156.5

 

 

 

 

 

 

Standard

2

327

 

20.6

1308

 

82.5

 

 

 

300

 

 

Plus one pass

3

174

 

11.0

697

 

44.0

687.5

 

43.4

 

 

 

Minus one pass

1

687

 

43.3

2750

 

173.5

 

 

 

 

 

 

Standard

2

361

 

22.8

1442

 

91.0

 

 

 

325

 

 

Plus one pass

3

211

 

13.3

843

 

53.2

733.4

 

46.3

 

 

 

Minus one pass

1

724

 

45.7

2897

 

182.8

 

 

 

 

 

 

Standard

2

379

 

23.9

1516

 

95.6

 

 

 

350

 

 

Plus one pass

3

244

 

15.4

978

 

61.7

775.4

 

48.9

 

 

 

Minus one pass

1

767

 

48.4

3068

 

193.6

 

 

 

 

 

 

Standard

1

501

 

31.6

2004

 

126.4

 

 

 

400

 

 

Plus one pass

 

 

917.6

 

57.9

 

 

 

Minus one pass

 

 

 

 

 

 

 

 

Standard

1

501

 

 

2004

 

 

 

 

 

450

 

 

Plus one pass

 

 

1019.3

 

64.3

 

 

 

Minus one pass

 

 

 

 

 

 

 

 

Standard

1

501

 

 

2004

 

 

 

 

 

500

 

 

Plus one pass

 

 

1092.8

 

68.9

 

 

 

Minus one pass

 

 

 

 

 

*For applications requiring cooler leaving water temperature operation at less than 40 F (4.4 C), the units require the use of antifreeze and application may require one of the special order brine option. Contact your local Carrier representative for more information.

For applications requiring cooler entering water temperature operation at less than 45 F (7.2 C), contact your local Carrier representative for unit selection using the Carrier electronic catalog.

NOTE: Nominal flow rates required at ARI (Air Conditioning and Refrigeration Institute) conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering water temperature, 95 F (35 C) ambient. Fouling factor 0.00010 ft2-hr-F/Btu (0.000018 m2-K/kW).

54

Image 54
Contents Installation Instructions Place, Mount, and Rig the Unit AquaForce Chiller Model Number Designation A30-440130XA080 Air-Cooled Liquid Chiller Dimensions Right END View A30-4403100 4404090 110A30-4405 30XA090-120 Air-Cooled Liquid Chiller with Pump Dimensions Front View 160 140115.88 115.64Back View A30-440730XA140,160 Air-Cooled Liquid Chiller with Pump Dimensions 2300 30XA180,200 Air-Cooled Liquid Chiller Dimensions A30-4174 220 46.17 171.42 240 46.23 170.83 A30-4409614 532 208 132 1500 4260 4798 4799 5221 8363 300 260280 A30-4177614 532 208 132 1900 5011 5747 5760 6184 9555 A30-4178325 350614 532 208 132 1900 6205 6941 6954 7378 10750 A30-4181 4182 A30Left END View Front View A30 450 500A30-4183 A30-418 A30-41 Back View Unit Mounting Weights Units with Mchx Condenser Coils 30XA140,160 30XA080 30XA220-30030XA090-120 30XA325-350 30XA400-50030XA090-120 30XA140,160 A30-4421Dual Pump Units English Unit Mounting Weights Units with Al/Cu Condenser Coils Cooler Side ED CBA K L M N O P Compressor Side FG HIJ 1273 2898 1160 972 2089 1271 662 1273 3106 1248 972 2089 1271 959 Unit Mounting Weights Units with Cu/CU Condenser Coils 30XA080 30XA090-1201394 3139 1280 1093 2330 1392 10,627 Do not use a forklift truck to move the units A30-4420 A30-4421Physical Data, 30XA080-500 English Unit 30XAPhysical Data, 30XA080-500 SI Refrigerant Charge kg Ckt A/Ckt B/Ckt C MchxUnit Rigging Label Detail 30XA080-200 A30-4427A30-4428 Unit Rigging Label Detail 30XA400-500 30XA Typical Piping and Wiring Units with Hydronic Package Cooler Option Dimensions A30-4413A30-4417 A30-4418A30-4138 A30-4414 A30-4415 PT Hydronic Pump PackageA30-4002 Thermal Flow Sensor A30-343230XA Minimum and Maximum Cooler Flow Rates Minimum Maximum NominalDetail a 30XA080-12030XA140-500 A30-3997A30-4411 A30-441230XA Pump Impeller Sizes090-160 FTV-5 Rpm Impeller Dia30XA120 30XA090,10030XA110 30XA140A30-4439 A30-4436A30-4437 A30-44403450 RPM Page Make Electrical Connections NON-FUSED Disconnect Unit Voltage Number No Hydronic Package Unit Voltage Number Unit Voltage Number No Hydronic Package 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 Unit Voltage Number Unit Voltage Number No Hydronic Package 230-60 207 253 592.4 800 869.3 700 607.0 883.9 115 30XA140-500 Electrical Data, Dual Point High Ambient Option 460-60 414 506 10/6 115 575-60 518 633 380-60 342 418 230-60 207 253 383.8/256.9 600/350 660.8/436.2 450/300 115 Power and Control Connections Compressor and Fan Electrical Data Unit Cond Size FansCCN Communication Bus Wiring Pump Electrical DataA30-4001 A30-3999 A30-4000Refrigerant Charge Page Copyright 2009 Carrier Corporation