GE GN94DNSRSA Remote Controller Installation, Location, Configurations, Mounting the Controller

Page 22

Installation Instructions

REMOTE CONTROLLER INSTALLATION

LOCATION

• The controller should be out of reach of small children.

• Avoid locations where the controller may become hot (near the oven or radiant heater).

Avoid locations in direct sunlight. The digital display may be difficult to read in direct sunlight.

Avoid locations where the remote controller could be splashed with liquids.

Do not install in locations where it can be adjusted by the public.

CONFIGURATIONS

A maximum of 4 remote controllers can be installed for a water heater or bank of water heaters. Controllers can only be wired in parallel. Controllers cannot be wired in series.

REMOTE CONTROLLER INSTALLATION (cont.)

MOUNTING THE CONTROLLER

1Determine a suitable location for the controller.

2Mount a single gang outlet box in the wall where the remote control is indicated.

3Run the cable between the controller and the water heater or the controller and the other controller.

4Remove the face plate from the remote controller, using a screwdriver.

5Connect the cable to the remote controller.

6Mount the controller to the wall in the single gang outlet box installed in step 2.

7Disconnect the power from the water heater.

8Remove the cover of the water heater.

9Remove the plastic cover from the PCB and electrical connections.

Outline of Remote

If 4 AGTRC1’s are installed, press the Priority and On/Off buttons on the fourth controller until a beep sounds.

securing screw

wiring hole

securing screw

1-21/32"

3-5/16"

Wire Controllers in Parallel

CABLE LENGTHS AND SIZE

The cable for the remote controller should be a nonpolarized two-core cable with a minimum gauge of 22 AWG. The maximum cable length from each controller to the water heater depends on the total number of wired controllers connected to the water heater.

NUMBER OF WIRED

MAXIMUM CABLE LENGTH FOR EACH

CONTROLLERS

CONTROLLER TO WATER HEATER

 

 

1

328 ft. (100 m)

 

 

2

164 ft. (50 m)

 

 

3 or 4

65 ft. (20 m)

 

 

22

WARNING: DO NOT ATTEMPT TO CONNECT THE REMOTE CONTROLLERS WITH THE POWER ON.

10Thread the cable through the access hole

at the base of the unit and connect the wires to the controller terminals on the bottom right-hand side of the PCB.

11Secure the controller cable using the clamp provided.

Image 22
Contents For Your Safety Before BeginninginstallationSafety Precautions Models GN75DNSRSA, GN94DNSRSA, GP94DNSRSAInstallation Instructions Safety PrecautionsParts Provided Tools YOU will NeedGN75/GN94/GP94DNSRSA DimensionsDescription Planning for Venting INTAKE/EXHAUST GuidelinesFlue Terminal Clearances Flue Terminal Clearances Ansi Z21.10.3 CSAAdditional Clearances Vent Terminal Horizontal Termination with Flue Installation Condensate DrainCondensate Drain Planning for Plumbing Shown with optional pipe coverCorrosive Atmospheres Clearances for Water HeaterMounting the Water Heater Mounting the Water Heater Mounting the WaterheaterGAS Piping GAS PipingConnecting the Water Heater to the GAS Supply Pressure Relief Valve Water PipingWater Piping Internal BUILT-IN Freezer ProtectionConnecting the Water Heater to the Water Supply Supplemental Freeze ProtectionRecommended Piping for Basic Installation KEYFreeze Protection For External Piping Electrical Connection Information Electrical RequirementsCondensate Venting InstructionsVenting Instructions Maximum Vent LengthVent Products Flue Installation Concentric VentingProduct Parts High Altitude Installations GuidelinesLocation Remote Controller InstallationConfigurations Mounting the ControllerCleaning the Inlet Filter Cleaning the Inlet FilterInstallation Checklist Pressure Drop Curve Technical DataOutlet Flow Data Ladder Diagram Page