Desa CGB50P, CGB35P installation manual Venting Heater

Page 8

INSTALLING HEATER

Continued

8

VENTING HEATER

Note: Venting/chimney materials are not supplied with heater.

WARNING

A qualified service person must install the venting system for this heater. If venting system is not properly installed and maintained, the vent safety shut-off system will pre- vent the heater from running. Follow all local codes.

WARNING

This heater has a vent safety shut-off system. This system shuts off the heater gas supply if you do not vent heater properly or the venting system is blocked. Do not operate heater if not properly vented. Do not tamper with the vent safety shut-off system. Carbon monoxide poison- ing and death may result.

WARNING

When venting this heater, follow the safety information listed below.

Never vent heater to another room or inside a building. Only vent heater to the outdoors.

Do not vent heater exhaust to a chimney or flue serving another solid-fuel-burning or gas appliance.

We recommend you use flues classified as prefabricated or masonry all-fuel chimney or type-B vent. See Vent Types, page 10.

If using old vent, check vent for soot, creosote, and loose particles. If vent is damaged, repair or replace it before using heater.

Extend the vertical section of vent pipe at least three feet above roof penetration.

Extend the vertical section of vent pipe at least two feet above the highest point of any roof within ten feet.

The horizontal run of vent pipe should rise at least 1/4 inch for each foot of run.

Support the vent pipe at least every five feet along its length. Do not use combustible materials to support vent pipe.

Never extend vent pipe horizontally through outside wall and terminate. You must connect a vertical run of vent pipe to the horizontal run. The vertical run must be at least 25% longer than the horizontal run.

Install vent or chimney cap that is approved for use with vented gas room heaters.

Do not use vent pipe smaller in diameter than that of the heater draft hood outlet.

Do not use dampers in the vent pipes.

Vertical height of vent must be greater than five feet above vent connection at draft hood.

100352

Image 8
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualFor Your Safety Contents Safety Information Carbon monoxide poisoning may lead to deathSafety Information Product Identification Check GAS Type Local Codes Unpacking Product FeaturesInstallation Items Locating Heater Heater ClearancesVenting Heater Venting Heater Do not vent heater in any of the following ways see FigureVenting Heater Proper Size Vent Connecting to GAS Supply External Regulator with Vent Pointing DownGas Connection Pressure Testing Gas Supply Piping System Checking GAS ConnectionsInstalling Glass Panel Removing Lower Front Access PanelInserting Glass Panels Fresh AIR for Combustion and Ventilation Determining FRESH-AIR Flow for Heater Location Draft Hood Spillage TestVentilation Air from Outdoors Example 2 Locating Heater in Confined Closed Area Lighting Instructions For Your Safety Read Before LightingOperating Heater Viewing Pilot Manual Lighting Procedure To Turn OFF GAS to ApplianceShutting Off Heater Shutting Off Burner Only pilot stays litBurner Flame Pattern Inspecting Pilot and Burner FlamePilot Flame Pattern Correct Burner Flame Pattern Cleaning and Maintenance Trouble Shooting Observed Possible Problem Cause RemedyObserved Possible Remedy Problem Cause TROUBLE- ShootingStat bulb satisfied Gas leak. See Warning Statement at topService Procedures Removing Control Valve and Burner TubeRemoving Burner Changing Burner Orifice Orifice Location 35,000 BTU/Hr Burner ShownTechnical Service Service Hints35,000 BTU/Hr ModelParts Not Under Warranty Ordering Replacement Parts CentralsParts Under Warranty Accessories Valve GA5010Illustrated Parts List QTY Cabinet Assembly 100352 Warranty Information International