Desa CGB35P, CGB50P Determining FRESH-AIR Flow for Heater Location, Draft Hood Spillage Test

Page 17

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Example 1: Locating Heater in Unconfined (Open) Area

NOTICE

An unconfined area has a minimum air volume of 50 cubic feet for each 1000 BTU/Hr input rating of all appliances in the area (cubic feet equals length x width x height of area). Include adjoining rooms only if there are no doors between the rooms or if you add ventila- tion grills between the rooms (see Ventilating Confined Area, page 19).

In an open area, the air that leaks around doors and windows may provide enough fresh air for combustion and ventilation.

Draft Hood Spillage Test

Follow the steps below to see if enough fresh air is available.

1.Close all windows and doors.

2.If you have a fireplace, start a fire. Build fire until flames are burning strongly.

3.Turn on all exhaust fans. These include exhaust fans for kitchen, bathroom, water heaters (gas or electric), etc.

4.Turn on all vented gas appliances. These include any room heaters, water heaters, clothes dryer, etc.

5.Wait ten minutes for drafts to regulate.

6.Check for draft-hood spillage at each vented gas appliance. Do this by holding a lit match two inches from the draft opening (see Figure 13). If match flame pulls toward the draft hood, there is no spillage. If match flame blows away from the draft hood, there is spillage. This is a hazardous condition. See Draft Hood Spillage, page 18.

Vent Pipe

Draft Hood

Match

Typical

Water

Heater

Vent Pipe

Heater

Match

Draft Hood

Opening

Figure 13 - Checking for Draft Spillage

No Draft Hood Spillage: This shows there is enough fresh air in area for appliances. Turn off all exhaust fans and appliances if desired.

Continued

17

100352

Image 17
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualFor Your Safety Contents Carbon monoxide poisoning may lead to death Safety InformationSafety Information Product Identification Check GAS Type Local Codes Unpacking Product FeaturesInstallation Items Heater Clearances Locating HeaterVenting Heater Do not vent heater in any of the following ways see Figure Venting HeaterVenting Heater Proper Size Vent External Regulator with Vent Pointing Down Connecting to GAS SupplyGas Connection Checking GAS Connections Pressure Testing Gas Supply Piping SystemRemoving Lower Front Access Panel Installing Glass PanelInserting Glass Panels Fresh AIR for Combustion and Ventilation Draft Hood Spillage Test Determining FRESH-AIR Flow for Heater LocationVentilation Air from Outdoors Example 2 Locating Heater in Confined Closed Area Lighting Instructions For Your Safety Read Before LightingOperating Heater Viewing Pilot To Turn OFF GAS to Appliance Manual Lighting ProcedureShutting Off Heater Shutting Off Burner Only pilot stays litBurner Flame Pattern Inspecting Pilot and Burner FlamePilot Flame Pattern Correct Burner Flame Pattern Cleaning and Maintenance Observed Possible Problem Cause Remedy Trouble ShootingTROUBLE- Shooting Observed Possible Remedy Problem CauseStat bulb satisfied Statement at top Gas leak. See WarningRemoving Control Valve and Burner Tube Service ProceduresRemoving Burner Orifice Location 35,000 BTU/Hr Burner Shown Changing Burner OrificeService Hints Technical Service35,000 BTU/Hr ModelParts Not Under Warranty Ordering Replacement Parts CentralsParts Under Warranty Valve GA5010 AccessoriesIllustrated Parts List QTY Cabinet Assembly 100352 International Warranty Information