SERVICE PROCEDURE RG-VIII

Resettable Thermal Switch

Testing and Replacement

RESETTABLE THERMAL SWITCH CONTINUITY TESTING

Step 1. Remove outer jacket door.

Step 2. Disconnect wire leads from resettable thermal switch.

Step 3. Using a multimeter capable of measuring continuity (Ohms), place one probe of meter on one of the brass connection tabs of the resettable thermal switch, and the remaining probe on the other connection tab.

Step 4. If continuity is indicated, the switch is closed, allowing millivolt current to pass.

Step 5. If continuity is not indicated, the switch is open, possibly due to an over heating condition. The switch is designed to open at predetermined temperatures depending on model. An open switch can be reset by depressing the red colored button located at the center of the switch. The overheating condition must be determined prior to putting the heater back in service.

PROBABLE CAUSE FOR RESETTABLE THERMAL SWITCH ACTIVATION

 

PROBABLE CAUSE

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

1.

Verify adequate combustion air supply is

 

 

 

 

available.

Insufficient combustion air

2.

Clear jacket slot openings of any dirt, dust,

 

restrictions or other obstructions.

 

 

 

 

 

 

 

3. inspect flame arrestor plate and clean with

 

 

 

 

stiff brush and/or vacuum to remove scale

 

 

 

 

deposits and debris.

1. Weak switch or switch

1. Replace resettable thermal switch

out of calibration.

2.

Verify switch color code and approximate

 

 

 

2. Incorrect switch.

 

temperature.

 

 

Flammable vapor incident

1. Replace water heater.

 

 

 

 

 

 

 

Resettable thermal switch

color code reference.

Approximate switch

Color Code activation temperature (open)

Blue

240°

Yellow

270°

Red

290°

34

34

Image 34
Contents Service Manual Bradford White Introduction White Rodgers/Robertshaw Gas Valve Troubleshooting Chart Honeywell Gas Control Troubleshooting Chart Honeywell Gas Control Troubleshooting Chart Defender Installation of Inner Door With Gasket Combustion chamber Closed Circuit Thermocouple Testing White Rodgers Control Closed Circuit Thermocouple Testing Robertshaw ControlThermocouple Replacement White Rodgers/Robertshaw Gas Valve Open Circuit Thermopile Testing Honeywell Gas Control PILOT/ELECTRODE Assembly Inspection Cleaning and Replacement Piezo IGNITER, Electrode Testing and Replacement DefenderGas Valve Testing and Replacement White Rodgers/Robertshaw Line PressureMagnet Assembly Testing White Rodgers Control Thermocouple TestingMagnet Assembly Testing Robertshaw Control ECO Energy Cut Off Testing Combination THERMOSTAT/GAS Valve ReplacementWrench Boss Position thermocouple, pilot tube and Piezo wire Honeywell Gas Control Testing, Disassembly, and Replacement Thermopile Testing Temperature Sensor Testing DefenderDetermine Water Temperature Inside Tank Sensor Resistance at Various TemperaturesGAS Control DISASSEMBLY/REASSEMBLY Temperature sensor Wire routing clip Disconnect Use caution not to bend or damage valve body pins Pull in this direction Temperature sensor Insertion stick GAS Control Replacement Defender Combustion chamber Main Burner Inspection, Adjustment Cleaning and Replacement Cast Iron Burner AdjustmentPosition thermocouple/thermopile Pilot tube and Piezo wire Burner Cleaning Resettable Thermal Switch Continuity Testing Resettable Thermal Switch Replacement Over Tighten ScrewsScreenLok Flame Arrestor Cleaning Feedline NutDIP Tube Inspection and Replacement Anode Inspection and Replacement Generic Parts List Parts@bradfordwhite.com Techserv@bradfordwhite.com