Bradford-White Corp MI30T*F service manual Honeywell Gas Control Troubleshooting Chart

Page 6

Honeywell Gas Control Troubleshooting Chart

Flammable Vapor Ignition Resistant Water Heaters

Observe green LED indicator on Gas Control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.

Green LED Indicator

LED Status

Control Status

Probable Cause

 

 

 

 

 

Service

Procedure

Five flashes and

three second

pause

Six flashes and

three second

pause

Seven flashes and

three second

pause

Eight flashes and

three second

pause

Thermostat/well sensor fault.

Water leak detected by accessory module.

Gas Control electronic fault detected.

Standing pilot remains on while set point knob is in “OFF” position.

1.Damage to the temperature sensor.

2.Temperature sensor resistance out of range.

Excessive amount of water in drain pan/water dam.

1.Control need to be reset.

2.Control is wet or physically damaged.

Pilot valve stuck in open position.

1.See service procedure RG-VI

1.Check T&P valve

2.Check all water fittings.

3.Pressurize and leak test tank.

1.Reset Gas Control

2.Replace Gas Control.

Replace Gas Control.

6

66

Image 6
Contents Service Manual Bradford White Introduction White Rodgers/Robertshaw Gas Valve Troubleshooting Chart Honeywell Gas Control Troubleshooting Chart Honeywell Gas Control Troubleshooting Chart Defender Installation of Inner Door With Gasket Combustion chamber Closed Circuit Thermocouple Testing White Rodgers Control Closed Circuit Thermocouple Testing Robertshaw ControlThermocouple Replacement White Rodgers/Robertshaw Gas Valve Open Circuit Thermopile Testing Honeywell Gas Control PILOT/ELECTRODE Assembly Inspection Cleaning and Replacement Piezo IGNITER, Electrode Testing and Replacement DefenderGas Valve Testing and Replacement White Rodgers/Robertshaw Line PressureThermocouple Testing Magnet Assembly Testing White Rodgers ControlMagnet Assembly Testing Robertshaw Control ECO Energy Cut Off Testing Combination THERMOSTAT/GAS Valve ReplacementWrench Boss Position thermocouple, pilot tube and Piezo wire Honeywell Gas Control Testing, Disassembly, and Replacement Thermopile Testing Temperature Sensor Testing DefenderDetermine Water Temperature Inside Tank Sensor Resistance at Various TemperaturesGAS Control DISASSEMBLY/REASSEMBLY Temperature sensor Wire routing clip Disconnect Use caution not to bend or damage valve body pins Pull in this direction Temperature sensor Insertion stick GAS Control Replacement Defender Combustion chamber Main Burner Inspection, Adjustment Cleaning and Replacement Cast Iron Burner AdjustmentPosition thermocouple/thermopile Pilot tube and Piezo wire Burner Cleaning Resettable Thermal Switch Continuity Testing Resettable Thermal Switch Replacement Over Tighten ScrewsScreenLok Flame Arrestor Cleaning Feedline NutDIP Tube Inspection and Replacement Anode Inspection and Replacement Generic Parts List Parts@bradfordwhite.com Techserv@bradfordwhite.com