Bradford-White Corp MI30T*F service manual Honeywell Gas Control Troubleshooting Chart

Page 5

Honeywell Gas Control Troubleshooting Chart

Flammable Vapor Ignition Resistant Water Heaters

Observe green LED indicator on Gas Control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.

Green LED Indicator

LED Status

Control Status

 

 

 

Probable Cause

Service

Procedure

None (LED not on

or flashing

One flash and three second pause

LED on

continuously

(Solid)

Two flashes and

three second

pause

Gas Control is operating normally. Pilot flame may not be present. Check for pilot flame through sight glass and light if necessary.

If set point knob is in “PILOT” position then pilot flame is detected. Turn set point knob to desired setting.

Set point knob has been recently turned to the “OFF” position. Wait until LED goes out before attempting to relight

Weak pilot signal detected. System will reset when pilot flame is sufficient.

1. Gas Control is functioning normally.

2. Gas Control is not powered. Light pilot.

3. Thermopile failure.

Gas Control is powered and waiting for the set point knob to be turned to a water temperature setting.

Set point knob was turned to “OFF” position.

1. Thermopile failure

2. Unstable pilot

3. Pilot tube block or restricted.

4. Resettable thermal switch has opened

If the pilot will not stay lit replace pilot assembly. If problem persists replace Gas Control.

Normal operation. Adjust thermostat to desired temperature setting.

LED will go out and the control will function normally when the pilot is lit.

1.See service procedure RG-II

2.See service procedure RG-III

3.See service procedure RG-III

4.See service procedure RG-VIII

Three flashes and

Insufficient water heating. System

three second

will reset.

pause

 

Four flashes and

Excessive tank temperature.

three second

System must be reset.

pause

 

1.Temperature sensor out of calibration

1.Temperature sensor out of calibration

2.Faulty Gas Control

1.See service procedure RG-VI

1.See service procedure RG-VI

2.See service procedure RG-VI

5

5

Image 5
Contents Service Manual Bradford White Introduction White Rodgers/Robertshaw Gas Valve Troubleshooting Chart Honeywell Gas Control Troubleshooting Chart Honeywell Gas Control Troubleshooting Chart Defender Installation of Inner Door With Gasket Combustion chamber Closed Circuit Thermocouple Testing Robertshaw Control Closed Circuit Thermocouple Testing White Rodgers ControlThermocouple Replacement White Rodgers/Robertshaw Gas Valve Open Circuit Thermopile Testing Honeywell Gas Control PILOT/ELECTRODE Assembly Inspection Cleaning and Replacement Defender Piezo IGNITER, Electrode Testing and ReplacementLine Pressure Gas Valve Testing and Replacement White Rodgers/RobertshawMagnet Assembly Testing Robertshaw Control Thermocouple TestingMagnet Assembly Testing White Rodgers Control Combination THERMOSTAT/GAS Valve Replacement ECO Energy Cut Off TestingWrench Boss Position thermocouple, pilot tube and Piezo wire Honeywell Gas Control Testing, Disassembly, and Replacement Thermopile Testing Defender Temperature Sensor TestingSensor Resistance at Various Temperatures Determine Water Temperature Inside TankGAS Control DISASSEMBLY/REASSEMBLY Temperature sensor Wire routing clip Disconnect Use caution not to bend or damage valve body pins Pull in this direction Temperature sensor Insertion stick GAS Control Replacement Defender Combustion chamber Cast Iron Burner Adjustment Main Burner Inspection, Adjustment Cleaning and ReplacementPosition thermocouple/thermopile Pilot tube and Piezo wire Burner Cleaning Resettable Thermal Switch Continuity Testing Over Tighten Screws Resettable Thermal Switch ReplacementFeedline Nut ScreenLok Flame Arrestor CleaningDIP Tube Inspection and Replacement Anode Inspection and Replacement Generic Parts List Parts@bradfordwhite.com Techserv@bradfordwhite.com