Bradford-White Corp THROUGH-THE-WALL GAS WATER HEATER Ground Clearance Installations

Page 23

TABLE 9

2” (5.1 cm) PVC VENT CONNECTOR LENGTHS FROM INSIDE WALL FOR

LOW GROUND CLEARANCE INSTALLATIONS

Terminating

# of

Maximum

Minimum

 

Elbows

Length

Length

(2) 90° Elbows with Vent Terminal

0

35 ft (10.7

2 ft (.6 m)

 

 

m)

 

(2) 90° Elbows with Vent Terminal

1

30 ft (9.2 m)

2 ft (.6 m)

(2) 90° Elbows with Vent Terminal

2

25 ft (7.6 m)

2 ft (.6 m)

(2) 90° Elbows with Vent Terminal

3

20 ft (6.1 m)

3 ft (.9 m)

(2) 90° Elbows with Vent Terminal

4

15 ft (4.6 m)

4 ft (1.2 m)

TABLE 10

3” (7.6 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL FOR LOW

GROUND CLEARANCE INSTALLATIONS

Terminating (Reduce 3” to 2”)

#of

Maximum

Minimum

(Reduce 7.6 cm to 5.1 cm)

Elbows

Length

Length

(2) 90° Elbows with Vent Terminal

0

90 ft (27.5 m)

10 ft (3.1 m)

(2) 90° Elbows with Vent Terminal

1

85 ft (25.9 m)

10 ft (3.1 m)

(2) 90° Elbows with Vent Terminal

2

80 ft (24.4 m)

10 ft (3.1 m)

(2) 90° Elbows with Vent Terminal

3

75 ft (22.9m)

10 ft (3.1 m)

(2) 90° Elbows with Vent Terminal

4

70 ft (21.4 m)

10 ft (3.1 m)

(2) 90° Elbows with Vent Terminal

5

65 ft (19.8 m)

12 ft (3.7 m)

HIGH ALTITUDE INSTAL LATIONS FOR ELEVATIONS OVER 2,000 FEET (610 m) ABOVE SEA LEVEL

The capacity of the induced draft blower declines with increasing altitude due to a reduction in the air density. In order to assure safe and reliable performance of the water heater, the following guidelines must be followed. Refer to the venting tables below for maximum distances for the altitudes in your location.

TABLE 11 - HIGH ALTITUDE VENT CONNECTOR MODIFICATIONS

Altitude above sea

Maximum venting

Maximum venting

level

length reduction

length reduction from

 

from tables 7 & 9

tables 8 & 10

0 - 2,000 ft

No reduction in vent

No reduction in vent

(0 - 610 m)

length required

length required

over 2,000 - 5,000 ft

Reduce maximum vent

No reduction in vent

(over 610 - 1524 m)

length by 20 ft (6.1 m)

length required

over 5,000 - 8,000 ft

Use only 3” (7.6 cm)

No reduction in vent

(over 1524 - 2439 m)

PVC (Tables 8 & 10)

length required

over 8,000 - 10,000 ft

Use only 3” (7.6 cm)

Reduce maximum vent

(over 2439 - 2540 m)

PVC (Tables 8 & 10)

length by 20 ft (6.1 m)

23

Image 23
Contents TTW Installation and Operating Congratulations Table of Contents General Information Locating The Water Heater InstallationIf YOU Smell GAS Installation Locating The Water Heater Minimum Clearances Venting Exceptions For Installations in CanadaVenting System Condensation Model Service PartVenting Part Vent Connector Lengths Length Terminal Through the Roof Venting Vertical Venting Through the Wall VentingThrough the Wall Venting with LOW Ground Clearance Venting Part LOW Ground Clearance Installations Vent Connector Lengths for 3 7.6 cm Diameter PVC Terminating # of 90 Elbows Maximum Minimum Through the Wall Venting Through the Roof Venting Vertical Venting Through the Wall Venting with LOW Ground Clearance High Altitude Vent Connector Modifications Cm Vent Connector Lengths from Inside Wall for LOWGround Clearance Installations Confined Spaces Combustion Air SupplyDo not Operate Appliance Until Leakage is Corrected Unconfined SpacesWater Connections Specially Engineered InstallationsCertain IT is Filled with Water Page Installation Water Connections Gas Connections Match or Open Flame for TestingElectrical Connections Electrical Connections Figure Electrical Connections Figure General Operation Lighting and shutdown instructions Burner Flame Check Thermostat AdjustmentMaintenance Maintenance Page Time That Parts and the Water Heater are Warranted Parts List Drawing Part Name and Description Page Vent Pipe Preparation and Joining