2.7Converting to another type of gas

For conversion of the appliance from natural gas to another type of gas, or visa versa, it is necessary to exchange the pilot injector and the main injector. The conversion may only be executed by a qualfied competent person.

Procedure:

1.Shut the heater down. Close the main inlet gas valve and switch off the electricity supply at the main switch;

2.Remove the burner assembly;

3.Replace the injectors with the cor- rect injectors from the conversion set. (see table below).

Remark:

-When conversion of the appliance from natural gas to another type of gas, fix the screw on the gas block of the burner pressure control as far as the stop.

-When conversion of the appliance from another type of gas to natural gas, then the right burner pressure should be adjust.

2.8Maintenance

To ensure safe and efficient operation of the water heater it is recommended that it is cleaned and serviced at least once a year by a qualified competent person.

2.8.1Magenesium anode

The life cycle of the anode is determined by the quality and the quantity of the water flowing through the water heater. It is therefore recommended that the anode be inspected and replaced if necessary at least once a year.

1. Close the stop cock in the cold water supply pipe;

2. Open the nearest hot water tap in order to allow the pressure to drop from the water heater and the pipes;

3. Slacken the anode with a fitting wrench;

4. Check the anode and replace it if it has been reduced in diameter by 60% or more at any point on its lenght;

5. Check for water leaks.

If is necessary to replace the anode it should be replaced by one of the same type. The type of anode required can be detemined on the basis of the type of the appliance and the serial number.

 

unit

 

BTI 85

 

 

BTI 100

 

 

 

G20

G30

G31

G20

G30

G31

 

 

 

 

 

 

 

 

Supply pressure

mbar

20

30

37

20

30

37

Burner pressure

mbar

11.5

30

37

10.0

30

37

Diameter main injector

mm

3.90

2.30

2.30

4.50

2.35

2.35

Diameter pilot injector

mm

0.56/

0.23

0.23

0.56/

0.23

0.23

 

 

0.41

 

 

0.41

 

 

19

Image 19
Contents BTI 100 G BTI 85 GPage Contents General Description of the appliance GeneralPage Gas control valve Technical safety equipmentControl panel Ignition failure Combustion products discharge safety deviceOperation of the storage water heater Normal operationBTI DimensionsDimensions Technical informationAOS Data Butane G30 30 mbar Technical dataUnit BTI Data Naturel GAS G20 20 mbarIonisation current Electrical connectionFor non-domestic applications Installation instructionsInstallation For domestic applicationsVented systems See figur Water circulation systemUnvented system See figur Electrical connection Gas connectionFlue system Draught diverterShut down CommissioningFilling the water heater Putting into operationReplacing the cover see figure Setting the gas pressureRemoving and replacing the control panel front cover Removing the cover see figureMounting the inner door Temperature regulationUnit BTI MaintenanceConverting to another type of gas Magenesium anodeGas smell Inlet combinationCondensation 3 Use CommisioningFailure Possible Cause Corrective Action Fault overviewRange of guarantee Guarantee in generalGuarantee of the tank Conditions for installation and useClaims Appendix 1 Connection diagram BTI models Page Page 0308 253 R0