Emerson XDCF user manual Liebert XD prefabricated piping assembly

Page 19

 

Piping Connections and Piping Access Points

Figure 13 Liebert XD prefabricated piping assembly

 

Return Main

 

Supply Main

Service Valve, typical

 

(all ports)

Threaded Cap (Typical)

5.Thread the return couplers together, the larger of the two couplers (Liebert XD Flex Pipe and return main).

6.Use one of the adjustable wrenches to hold the fixed side of the female coupler on the Liebert XDCF stationary. With the other adjustable wrench, tighten the collar onto the coupler. Tighten these only until the force required to tighten abruptly increases. See Figure 14.

NOTICE

Do not overtighten the couplers. Overtightening of couplers will damage the couplers.

Figure 14 Detail view of Liebert XD Flex Pipe and prefabricated piping port

Tighten collar with wrench.

DO NOT OVERTIGHTEN!

Supply Side Torque Range for

1/2" coupler is 22.1 to 25.8 lb/ft (30-35Nm)

Return Side Torque Range for

1" coupler is 59 to 62.7 lb/ft (80-85Nm)

Service Valve Note:

Make sure the valve

is closed before attaching flex pipe to the system.

Hold threaded coupler here with a wrench to keep the pipe stationary while tightening collar with another wrench.

Flex Pipe

7.Repeat Steps 5 and 6 for the smaller coupler (supply line).

8.Once the supply and return connections are completed, open the return service valve, then open the supply service valve.

With the equipment running, cool air is discharged from the back of the Liebert XDCF.

15

Image 19
Contents Liebert Xdcf Fluorinated Greenhouse Gas Requirements-European Union Important Safety GuidelinesTable of Contents Figures Liebert Xdcf component locations Example XD-CF10-BP-0 XD CFGeneral Product Information ReferencesParts Included With Liebert Xdcf Room PreparationEquipment Inspection Product/System DescriptionUnit Handling Recyclable Packaging Unpacking the Liebert Xdcf134a Mechanical ConsiderationsInstallation Installation ConsiderationsPreparing the Lower Module for Attachment Mounting Lower Liebert Xdcf ModuleLocator hole for lower unit stud Attaching Lower Liebert Xdcf ModuleLiebert XD Flex Pipe support panel attachment Attaching Liebert XD Flex Pipe Support PanelPreparing the Upper Module for Attachment Attaching Upper Liebert Xdcf ModuleAttaching Liebert XD Flex Pipe retainers Attaching Upper Liebert Xdcf ModuleHeader System Piping Connections and Piping Access PointsEuropean Union Fluorinated Greenhouse Gas Requirements Connection Methods and PointsRecommended Piping Size Connecting Liebert XD Flex Pipes to Liebert Xdcf ModulesTools Required Liebert XD prefabricated piping assembly Tools Required Return Supply Line InsulationChecklist for Proper Installation Fluorinated Greenhouse Gas Requirements MaintenanceLiebert Xdcf specifications SpecificationsSpecifications Specifications Page Ne t