Piping Connections and Piping Access Points

Figure 15 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe

Return Service Valve Make sure valve is open after system leak check

Supply Service Valve

Make sure valve is open after system leak check

Return

Main

Supply Main

Return Flex pipe

Supply Flex Pipe

5.6Disconnecting a Liebert XDCF With Liebert XD Flex Pipe From a Liebert XD System

NOTE

Before uninstalling a Liebert XDCF with Liebert XD Flex Pipe from the prefabricated piping mains: Close the supply service valve, wait approximately two minutes, then close the return service valve.

Read all instructions before beginning.

Tools Required

Two adjustable wrenches, maximum adjustment size of 2-1/2 inches

Phillips head #2 screwdriver

1.Close the service valve in the supply line to the Liebert XDCF (smaller coupler).

2.Close the service valve in the return line to the Liebert XDCF (larger coupler).

3.Locate and have at the ready the caps and plugs for both ends of the supply and return couplers.

4.Loosen the female supply coupler from the male supply coupler (smaller coupler). This requires two adjustable wrenches. Refer to Figure 14.

5.The Liebert XDCF side of the female coupler must be held stationary while the collar on the coupler is being loosened. Refer to Figure 14.

6.Disconnect the coupler.

16

Image 20
Contents Liebert Xdcf Important Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Figures Liebert Xdcf component locations XD CF Example XD-CF10-BP-0References Parts Included With Liebert XdcfRoom Preparation General Product InformationUnit Handling Product/System DescriptionEquipment Inspection Unpacking the Liebert Xdcf Recyclable PackagingMechanical Considerations 134aInstallation Considerations InstallationMounting Lower Liebert Xdcf Module Preparing the Lower Module for AttachmentAttaching Lower Liebert Xdcf Module Locator hole for lower unit studAttaching Liebert XD Flex Pipe Support Panel Liebert XD Flex Pipe support panel attachmentAttaching Upper Liebert Xdcf Module Preparing the Upper Module for AttachmentAttaching Upper Liebert Xdcf Module Attaching Liebert XD Flex Pipe retainersPiping Connections and Piping Access Points European Union Fluorinated Greenhouse Gas RequirementsConnection Methods and Points Header SystemTools Required Connecting Liebert XD Flex Pipes to Liebert Xdcf ModulesRecommended Piping Size Liebert XD prefabricated piping assembly Tools Required Insulation Return Supply LineChecklist for Proper Installation Maintenance Fluorinated Greenhouse Gas RequirementsSpecifications Liebert Xdcf specificationsSpecifications Specifications Page Ne t