KitchenAid Microwave Oven Venting Design Specifications, Rectangular to Round Transition, Ef G

Page 11

VENTING DESIGN SPECIFICATIONS

This section is intended for architectural designer and builder/contractor reference only.

NOTES:

Vent materials needed for installation are not provided with microwave hood.

We do not recommend using a flexible metal vent.

To avoid possible product damage, be sure to vent air outside, unless using recirculation installation. Do not vent exhaust air into concealed spaces, such as spaces within walls or ceilings, attics, crawl spaces or garages.

For optimal venting installation, we recommend:

using roof or wall caps that have back draft dampers

using a rigid metal vent

using the most direct route by minimizing the length of the vent and number of elbows to provide efficient performance

using uniformly sized vents

using duct tape to seal all joints in the vent system

using caulking compound to seal exterior wall or roof opening around cap

not installing 2 elbows together, for optimal hood performance

If venting through the wall, be sure that there is proper clearance within the wall for the damper to open fully.

If venting through the roof, and rectangular to round transition is used, be sure there is at least 3" (7.6 cm) of clearance between the top of the microwave oven and the transition piece. See “Rectangular to Round Transition” illustration.

Rectangular to Round Transition

NOTE: The minimum 3" (7.6 cm) clearance must exist between the top of the microwave oven and the rectangular to round transition piece so that the damper can open freely and fully.

A

B

C

D

 

 

E

3" (7.6 cm)

F

A. Roof cap

B. 6" (15.2 cm) min. diameter round vent C. Elbow (for wall venting only)

D. Wall cap

E. 3¹⁄₄" x 10" to 6" (8.3 x 25.4 cm to 15.2 cm) rectangular to round transition piece

F. Vent extension piece, at least 3" (7.6 cm) high

Recommended Standard Fittings

The following length equivalents are for use when figuring vent length. See the examples in “Recommended Vent Length.”

ABC

Roof venting

Roof cap

Wall venting

Wall cap

D EF G

A. Rectangular to round transition piece: 3¹⁄₄" x 10" to 6" = 5 ft (8.3 x 25.4 cm to 15.2 cm = 1.5 m)

B. Roof cap: 3¹⁄₄" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)

C. 90° elbow: 3¹ " x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)

D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)

E. Wall cap: 3¹⁄₄" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)

F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)

G. 90° flat elbow: 3¹⁄₄" x 10" = 10 ft (8.3 x 25.4 cm = 3 m)

11

Image 11
Contents Microwave Hood Combination Safety Microwave Hood Combination Installation InstructionsLocation Requirements Installation RequirementsTools and Parts Required Product DimensionsInstallation Dimensions Electrical RequirementsRotate Blower Motor Installation InstructionsWall Venting Installation Only Remove Mounting PlateCD E Roof Venting Installation OnlyLocate Wall Studs Possible Wall Stud ConfigurationsMark Rear Wall Installation for No Wall Studs at Corner Holes Figures 1Installation for Wall Stud at One Corner Hole Figure Installation for Wall Studs at Both Corner Holes FigureWall Stud at One Corner Hole Figure Attach Mounting Plate to WallPrepare Upper Cabinet No Wall Studs at Corner Holes Figures 1C D Install Damper AssemblyInstall the Microwave Oven For Roof Venting Installation OnlyComplete Installation Recommended Standard Fittings Venting Design SpecificationsFor optimal venting installation, we recommend Rectangular to Round TransitionAssistance Replacement PartsAccessories Outillage et pièces Exigences DinstallationSécurité DE L’ENSEMBLE Four À MICRO­ONDES/HOTTE Dimensions à respecter lors de linstallation Exigences demplacementDimensions du produit Réorientation du moteur du ventilateur Instructions DinstallationSpécifications électriques Dépose de la plaque de montageFixer la plaque de support du clapet avec la vis Identifier la position du/des poteaux du colombage mural Configurations possibles du colombage muralTracé sur le mur arrière Un trou d’angle face à un poteau du colombage mural Figure Perçage de trous dans le mur arrièreFixation de la plaque de montage sur le mur Préparation du placard mural Installation du four à micro-ondes Installation du module du clapet anti­refluxAchever linstallation Raccord de transition rectangulaire/rond Raccords standard recommandésSPÉCIFICATIONS/CONCEPTION DU Circuit Dévacuation Conduit de dia 15,2 cm = longueur totale 73 pi 22,2 m AccessoiresLongueur recommandée du circuit dévacuation Pièces de rechange