Omega Engineering M-4066 manual Server Item Names

Page 48

Server Item Names

Server Items are made available when the "Server" Topic is defined. These items give information about the Server and the current operational status of the Server.

PortType (R) - communication medium: "COM", "LPT", etc.

PortNo (R) - port number.

PollTries (R) - No. of missed polls before a device is considered offline.

NumberDevices (R/W) - number of devices in the system

OfflinePolltime (R/W) - how often to poll for off-line devices Milliseconds

NoDevicesOffline (R) - how many devices currently offline

Online (R) - indicates if communicating with any devices (0 or 1)

Ready (R) - 0 indicates that OMWT-SOFT-OPC is not receiving

(initializing or do a restart function); 1-OMWT-SOFT-OPC is ready to receive.

CntNode – the number of nodes OMWT-SOFT-OPC is maintaining. For TCP/IP Receiver, this is the number of connections to receivers. Use this number to access the Noden items.

Noden.online (R) – indicates if the node is online or offline (0 – offline; 1 – online). n is the node number starting at 1.

Noden.address (R) – address of the nodeFor TCP/IP Receiver, the address is the IP address. n is the node number starting at 1.

Noden.description (R) – the description string for the node. n is the node number starting at 1.

NetErrors.Last - the last error that occurred (string); see below.

NetErrors.LastNo - the last error that occurred (enumerated); see below.

NetErrors.LastDevice - the topic name of the device that had the error

NetErrors.Count - number of errors that have occurred since Server started

NetErrors.Com - number of CRC errors

NetErrors.NoHostAdapter - number of errors from not detecting the

Adapter

DeviceCount.DIGITAL (R) - number of digital devices

DeviceCount.TEMP(R) - number of temperature devices

DeviceCount.HUMIDITY (R) - number of humidity devices

DeviceCount.DIGCOUNTER (R) – number of digital counter devices

DeviceCount.AI (R)- number of Analog Input devices

DeviceCount.CNTTEMP – number of Counter Temperature

DeviceCount.FASTCNTTEMP – number of Fast Counter Temperature

DeviceCount.ALARMTEMP – number of Alarm Temperature

DeviceCount.IDR – number of Access/Control Readers

DeviceCount.DIRECTCNT – number of Directional Counters

44 N OMWT-SOFT-OPC Server Tags

OMWT-SOFT-OPC Server

Image 48
Contents OWMT-SOFT-OPC OMEGAnet Online Service Internet e-mail Info@omega.com Contents OMWT-SOFT-OPC Server Data Logging Overview Quick StartOverview OMWT-SOFT-OPC Server OMWT-SOFT-OPC Server and Wireless Wireless SetupDescription Edit Device Receivers Device ListOMWT-RECIP OMWT-REPEATPolling Identification FilteringWhat is OPC? Data Logging DiagnosticsSetup OMWT-SOFT-OPC Main WindowMain Window Change PortAdd/Delete IP Connection View IP Connection Status Outputs New and EditTrain ReConfigure Net Search and Add DevicesDevices Errors QuitHelp OMWT-SOFT-OPC Server .INI File Format OMWT-SOFT-OPC.iniServer Logging IP AddressesTemperature Setup Humidity Digcounter and Directional Counter DirectcntCnttemp Fastcnttemp FASTCNTTEMP1Alarmtemp Analog Input OMWT-AIN5V, OMWT-AIN10V, OMWT-AIN20MA, OMWT-VIB, OmwtMOT Access/Control Reader Repeater Dual Discrete OutputWireless Analog Output OUTPUTANALOG1OMWT-SOFT-OPC INI Backup OMWT-SOFT-OPC Server Tags Device NamesOMWT-SOFT-OPC Server Tags Temperature Device Tag NamesDigital I/O DIGITALn Temperature/Humidity HUMIDITYn OMWT-IRCNT, OWT-DIRCNT Cnttemp CNTTEMPn Fastcnttemp FASTCNTTEMPn Alarmtemp ALARMTEMPn AnalogInput AIn Access/Control Reader IDRn OMWT-SOFT-OPC Server Tags Repeater REPEATERn Dual Discrete Output OUTPUTDISCn Wireless Analog Output OutputAnalogn Server Item Names OMWT-SOFT-OPC Server OMWT-SOFT-OPC Server Tags N OMWT-SOFT-OPC Server Tags Features OMWT-SOFT-OPC Server Data LoggingFile Management File Format Data Log File Format Error Log Setting up to use OMWT-RECIP Receivers OMWT-RECIP ReceiversOverview of OMWT-RECIP Receivers OMWT-RECIP Receiver Notes Error Messages Communication ErrorsRuntime Errors Communication Error CRC16 or Time OutOMWT-SOFT-OPC Server Internal Error Why Use Corrections CorrectionsCorrection IDs Pre-defined ThermistorHow to use Corrections Correction.INI filePredefined Corrections NtcnormalresWARRANTY/DISCLAIMER OMEGA…Of Course