TESTING THE THERMISTORS
There are two thermistors that are used in controlling the temperature of the water in the heat exchanger system. The T- in that sam- ples the temperature of the water going into the heat exchanger and the
Thermistors are devices that change their resistance value with changes in temperature. By running a constant voltage through the thermistor, one can read the change of voltage caused by the change of resistance thus determining the temperature of the thermis- tor. There are test points on the control board (see above) that can be read with a
To test the temperature at the T-in Thermistor
There is a BLACK test point along the top edge of the control board on the right side of center. This is where the NEGATIVE (Common/Black) probe of a
the voltage on the chart below and find the corresponding temperature.
To test the temperature at the T-Mid Thermistor
Using the same BLACK test point with the NEGATIVE probe of the
Gas Pack Thermister Conversion
| 4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DC | 2.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Voltage | 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 1.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 50(10) | .6) | .1) | .7) | .2) | .8) | .3) | .9) | .4) | 140(60) | .6) | .1) | .7) | .2) | .8) | .3) | .9) |
| 60(15 | 70(21 | 80(26 | 90(32 | 100(37 | 110(43 | 120(48 | 130(54 | 150(65 | 160(71 | 170(76 | 180(82 | 190(87 | 200(93 | 210(98 | ||
|
|
|
|
|
|
|
| Temperature °F (°C) |
|
|
|
|
|
|
10