Fluke 744 manual Hart Output Hart Information

Page 19

Documenting Process Calibrator HART Mode

Communication Operations

HART Output

HART Information

From the Active Device screen press the Setup and HART Output softkeys to access the read/write HART Output screen. Here you can change the Poll Address (0 = single transmitter, any other address = multidrop), and control burst mode.

From the Active Device screen press the Setup and HART Information softkeys to access the read-only HART Information screen. This screen shows more complete information about the transmitter model, hardware and software revision numbers, and how many preambles it sends.

pe12s.bmp

pe13s.bmp

11

Image 19
Contents 744 Page Table of Contents 744 Hart Mode Users GuideList of Tables 744 List of Figures 744 Introduction Documenting Process Calibrator Hart ModeHow to Contact Fluke Connecting to a Hart Transmitter ∙ Poll address if not Documenting Process Calibrator Hart Mode Supported vs. Generic Transmitters Supported vs. Generic Transmitters Communication Operations Setup OperationsViewing Process Variables Hart Mode Menu Tree Sensor Hart Output Hart Information Service Operations Interaction between Analog Mode and Hart ModeAbort Softkey Understanding Hart Calibration Hart Mode Menus for AdjustmentBlock Diagram of a Hart Transmitter Calibrating a Supported Hart Transmitter Loop Test Sensor Trim Output TrimPress Continue Cloning a Transmitter 744 Index Device identification