Fluke 744 manual Calibrating a Supported Hart Transmitter

Page 23

Documenting Process Calibrator HART Mode

Calibrating a Supported HART Transmitter

Calibrating a Supported HART

Transmitter

An “as found” and “as left” transmitter calibration has an easier, more automated process for HART transmitters than for analog transmitters. The calibration procedure is the same as described in the 744 Users Manual, except for how you set up the calibration template, and how you adjust the transmitter.

Note

pe14s.bmp

If you are starting a calibration procedure from a loaded Task, connect to the HART transmitter first and establish communication before you press Task in analog mode.

The following procedure assumes that you are familiar with using a 740 Series Documenting Process Calibrator to calibrate analog transmitters, and are not running a loaded Task.

1.Make the appropriate measuring, sourcing, and HART interface connections between the calibrator and the transmitter, and press rto establish communication.

2.Press rto switch to analog mode.

3.You are presented with a set of choices for analog mode. Use the uand dkeys to select one of the measure/source choices. This is where you select measure mA (analog output), or measure PV, which does not involve the Output stage of the transmitter. See Figure 3.

4.Press e.

5.Press the As Found softkey.

6.Use the uand dkeys followed by eto select an instrument calibration procedure. You’ll see that the calibration template is preloaded with appropriate data. You can make changes to any item if you wish.

15

Image 23
Contents 744 Page Table of Contents 744 Hart Mode Users GuideList of Tables 744 List of Figures 744 Introduction Documenting Process Calibrator Hart ModeHow to Contact Fluke Connecting to a Hart Transmitter ∙ Poll address if not Documenting Process Calibrator Hart Mode Supported vs. Generic Transmitters Supported vs. Generic Transmitters Viewing Process Variables Setup OperationsCommunication Operations Hart Mode Menu Tree Sensor Hart Output Hart Information Abort Softkey Interaction between Analog Mode and Hart ModeService Operations Understanding Hart Calibration Hart Mode Menus for AdjustmentBlock Diagram of a Hart Transmitter Calibrating a Supported Hart Transmitter Loop Test Sensor Trim Output TrimPress Continue Cloning a Transmitter 744 Index Device identification