Understanding HART Calibration

Understanding HART Calibration

An analog transmitter has one stage of electrical conversion from a measured physical parameter to a

4-20 mA current loop output. A HART transmitter has the three stages shown in Figure 3.

Depending on how the transmitter is used in your application, you may need to test and adjust the Input stage, the Output stage, or both. For example, if your application requires the Primary Variable (PV) to be correct when read by a host computer, you must calibrate the Input stage.

If your application requires that the 4-20 mA current output value accurately reflect what the Input stage is measuring, you must calibrate both the Input and Output stages.

Transmitters in multidrop systems, in which more than one is wired in parallel, do not use their Output stages at all. Their analog outputs are all held at an idling level of 4 mA no matter what the Input stage is measuring.

744 HART Mode Menus for Adjustment

In 744 HART mode, adjusting the Input stage is called Sensor Trim. Adjusting the Output stage is called Output Trim. Both adjustments are made from the Service menu.

For pressure transmitters, there is another adjustment, called Pressure Zero Trim. This adjustment is the same as trimming the lower sensor point at zero. All three operations are run from the 744 HART mode Service menu.

13

Image 21
Contents 744 Page Table of Contents 744 Hart Mode Users GuideList of Tables 744 List of Figures 744 Introduction Documenting Process Calibrator Hart ModeHow to Contact Fluke Connecting to a Hart Transmitter ∙ Poll address if not Documenting Process Calibrator Hart Mode Supported vs. Generic Transmitters Supported vs. Generic Transmitters Setup Operations Communication OperationsViewing Process Variables Hart Mode Menu Tree Sensor Hart Output Hart Information Interaction between Analog Mode and Hart Mode Service OperationsAbort Softkey Understanding Hart Calibration Hart Mode Menus for AdjustmentBlock Diagram of a Hart Transmitter Calibrating a Supported Hart Transmitter Loop Test Sensor Trim Output TrimPress Continue Cloning a Transmitter 744 Index Device identification