Fluke Complete Guide to the 744 Manual for HART Mode Users

Page 22

744

HART Mode Users Guide

744 Calibrator

Sensor trim

 

 

Loop test

Pressure zero trim

PV

PVAO

Output trim

 

 

Physical

 

 

Input

 

variable

 

Computation

HART transmitter

Output

4-20mA loop

pe02f.eps

Figure 3. Block Diagram of a HART Transmitter

14

Image 22
Contents 744 Page Table of Contents Hart Mode Users Guide 744List of Tables 744 List of Figures 744 Documenting Process Calibrator Hart Mode IntroductionHow to Contact Fluke Connecting to a Hart Transmitter ∙ Poll address if not Documenting Process Calibrator Hart Mode Supported vs. Generic Transmitters Supported vs. Generic Transmitters Communication Operations Setup OperationsViewing Process Variables Hart Mode Menu Tree Sensor Hart Output Hart Information Service Operations Interaction between Analog Mode and Hart ModeAbort Softkey Hart Mode Menus for Adjustment Understanding Hart CalibrationBlock Diagram of a Hart Transmitter Calibrating a Supported Hart Transmitter Loop Test Output Trim Sensor TrimPress Continue Cloning a Transmitter 744 Index Device identification