Greenheck Fan ERV-582, ERV-581, ERV-522 Optional Accessories, Frost Control Application/Operation

Page 14
0.8 0.6
1.0 0.4
0 0.2
1 MIN T2
1 MIN T1
0.8 0.6
1.0 0.4
0 0.2
A1 B1 15

Optional Accessories

Frost Control Application/Operation

Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery wheel. Frost control is an optional feature that will prevent/control wheel frosting. Three options are available:

1.Timed Exhaust frost control

2.Electric preheat frost control

3.Modulating wheel frost control

All of these options are provided with a thermostat (with probe) mounted in the outdoor air intake compartment and a pressure sensor to monitor pressure drop across the wheel.

Frost Threshold Temperatures

Indoor RH @ 70°F

Frost Threshold Temp

 

 

20%

-10º F

 

 

30%

-5º F

 

 

40%

0º F

 

 

The typical temperature setting corresponds to the indoor air relative humidity as shown in the Frost Threshold Temperatures table and represents when frost can occur. An increase in pressure drop would indicate that frost is occurring. Both the pressure sensor and the outdoor air temperature sensor must trigger in order to initiate frost control. The two sensors together insure that frost control is only initiated during a real frost condition. Field wiring of a light (or other alarm) between 6 & C in the control center will notify personnel when unit is in frost control mode (refer to Remote Panel Wiring schematics section for wiring details). The following explains the three options in more detail.

Timed exhaust frost control includes a timer in addition to the thermostat and wheel pressure sensor. When timed exhaust frost control is initiated, the timer will turn the supply blower on and off to allow the warm exhaust air to defrost the energy recovery wheel. Default factory settings are 5 minutes off and 30 minutes on. Use the following test procedure for troubleshooting.

Testing (refer to Timer Faceplate drawing below)

After testing, set the Timer Scale as follows:

T1 = 10 minutes, T2 = 1 hour

Set the Timer Settings as follows:

T1 = 0.5, T2 = 0.5

The timer is now set for 5 minutes off and 30 minutes on. Remember to remove the jumper.

Electric preheat frost control includes an electric heater (at outdoor air intake) and an airflow pressure switch (located at the preheater) in addition to the thermostat and pressure sensor on wheel. (Refer to Electric Heater Application/Operation for electric preheater location). When electric preheat frost control is initiated, the electric preheater will turn on and warm the air entering the energy wheel to avoid frosting. Use the following test procedure for troubleshooting.

Testing:

Turn the thermostat as high as it will go and jumper the wheel pressure sensor. The heater should turn on.

If it doesn’t, either put the outdoor air side doors on or temporarily jumper the airflow pressure switch in the preheater control center to avoid nuisance tripping of the pressure switch. Also check the airflow switch pressure tap located at the supply discharge blower to ensure the tubing is connected and the tap is not blocked. Remember to remove the jumpers.

Modulating wheel frost control includes a variable frequency drive in addition to the thermostat and pressure sensor. When modulating wheel frost control is initiated, the variable frequency drive will reduce the speed of the wheel. Reducing the speed of the energy wheel reduces its effectiveness, which keeps the exhaust air condition from reaching saturation, thus, eliminating condensation and frosting. If the outdoor air temperature is greater than the frost threshold temperature OR the pressure differential

is less than the set point, the wheel will run at full speed. If the outdoor air temperature is less than the frost threshold temperature AND the pressure differential is greater than the set point, the wheel will run at reduced speed until the pressure differential falls below the set point. The temperature and pressure differential set points are set at the factory,

Jumper the wheel pressure switch in the unit control center. Set the Timer Scale for T1 and T2 to 1 minute. Set the Timer Settings for

T1 and T2 to 1.0. Set the dip switch to the down position. (normal position)

Dip

Switch

T2

Timer

Scale

T1

but are field-adjustable (refer to VFD section for more information). The variable frequency drive will be fully programmed at the factory.

• Turn the temperature

16

18

A2

sensor up as high as

possible. The supply blower should cycle on for one minute, then turn off for one minute.

14Model ERV Energy Recovery Unit

Image 14
Contents General Safety Information Models ERV-251 ERV-361 ERV-521 ERV-581 ERV-522 ERV-582Unpacking Inspection and Maintenance during StorageReceiving HandlingInstallation Table of ContentsSupplemental Installation Operation and Maintenance Manuals Basic OperationLifting Recommended Roof OpeningRoof Curb Mounting Curb Outside Dimensions and WeightsCurb Outside Dimensions Ductwork ConnectionsRail Mounting / Layout Arrangement a Service ClearancesERV-251, ERV-361, ERV-521, ERV-581 ERV-522, ERV-582 Arrangement B, C or DField Control Wiring Length/Gauge Electrical InformationUnit Accessories Access Panel Description and Location ERV-251, ERV-361, ERV-521, ERV-581 ERV-522Outdoor Air Dimensional Data ERV-522 Unit Size Exterior Dimensions Arrangement C Arrangement DFrost Control Application/Operation Optional AccessoriesFrost Threshold Temperatures Indoor RH @ 70F Modulating the Wheel Testing Temperature Sensor with OverrideEconomizer Application/Operation Enthalpy Sensor with OverrideDrive Operation Variable Frequency Drives for Energy Recovery BlowersFactory Set Points Economizer Signal Source Variable Frequency Drives for Energy Recovery WheelResetting the drive to factory defaults 10 VDCTypical Wiring Diagram TransformerDirty Filter Sensor Service OutletRotation Sensor CO2 SensorDay Timer or On/Off Switch Remote Control Panel and Wiring SchematicsIndicator Lights powered by the ER Unit Hand/Off/Auto SwitchPressure Sensors analog or digital Temperature Sensors 1K Ohm RTDSensors Mounted by Factory Amp Current Sensors analog or digitalStart-Up Pre Start-Up Checklist check as items areStart-Up Checklist General Start-Up InformationEconomizer Application / Operation section Optional Accessories ChecklistOptional Accessories section Variable Frequency Drives sectionUnit Start-Up Drive Belt Energy Recovery WheelVibration Air SealsFan Belts Routine MaintenanceMaintenance Procedures Lubrication Fan MotorsEnergy Recovery Wheel Maintenance External Filter MaintenanceDoor Seal Maintenance Internal Filter MaintenanceWheel segment removed Accessing the Energy Recovery Wheel in Models ERV-522Removing the Energy Recovery Wheel in ERV-251 Energy Recovery Wheel Bearing Cleaning the Energy Recovery WheelEnergy Recovery Wheel Belt Parts List Inside layout of ERV-361 Inside layout of ERV-522Basic Unit Other AccessoriesSequence of Operation Summer OperationTroubleshooting Airflow Troubleshooting Unit Symptom Possible Cause Corrective ActionTroubleshooting Unit Maintenance Log Warranty

ERV-361, ERV-251, ERV-521, ERV-582, ERV-522 specifications

Greenheck Fan has established itself as a leader in the design and manufacturing of high-performance ventilation systems, including its innovative energy recovery ventilators (ERVs). Among their popular models are the ERV-581, ERV-522, ERV-582, ERV-521, and ERV-251, each designed to enhance indoor air quality while optimizing energy efficiency.

The ERV-581 offers comprehensive ventilation solutions for commercial buildings, equipped with advanced heat recovery technology. This model features a robust, compact design, allowing for easy installation in limited spaces. Its efficient energy recovery capabilities transfer heat and moisture between incoming and outgoing airstreams, leading to significant reductions in heating and cooling costs. The ERV-581 also includes a user-friendly control panel for simplified operation.

Next in line, the ERV-522 is engineered for larger spaces, balancing higher airflow rates with enhanced energy recovery performance. This model is particularly beneficial for schools and office buildings, where maintaining fresh air quality is paramount. The ERV-522 employs a two-stage filtration system, ensuring that airborne pollutants are effectively captured before being circulated back into the environment. Its resilient construction further ensures longevity and durability in demanding applications.

The ERV-582 enhances the lineup with its dual-function capability, serving both as an energy recovery ventilator and a dehumidification system. This flexibility makes it an ideal choice for climates with high humidity levels, where moisture control is essential. The ERV-582 incorporates Greenheck’s patented technology for optimal performance under varying temperature and humidity conditions, making it a versatile solution for diverse environments.

The ERV-521 stands out with its eco-friendly design, featuring recyclable components that align with sustainable building practices. This model is particularly favored in LEED-certified projects, where energy efficiency and minimal environmental impact are essential. The ERV-521 also includes an intelligent control system that adjusts airflow rates based on occupancy levels, ensuring optimal energy usage.

Finally, the ERV-251 is a compact, energy-efficient model suited for residential installations. It is designed to fit seamlessly into homes, providing essential ventilation while reducing energy consumption. The user-friendly interface allows homeowners to monitor and adjust settings easily, making the ERV-251 a popular choice for those looking to improve indoor air quality without compromising on comfort.

Together, these Greenheck ERV models exemplify cutting-edge technologies and engineering, paving the way for healthier indoor environments while promoting energy conservation. Each unit is tailored to meet specific application needs, making them invaluable assets for any ventilation strategy.