Conair MPW, MPA manual Preparing for Installation, Make sure the installation area provides

Page 19

The microKool chiller is easy to install, if you plan the loca- tion and prepare the area properly.

1 Position the chiller as close to the process machine as possible.

Chiller

Process machine

Alternate

locations

PREPARING FOR INSTALLATION

2

Make sure the installation area provides:

A three-phase power source supplying the correct current for your chiller model. Check the serial tag on the side of the electrical enclosure for the required voltage, phase, frequency, full load amps, disconnect fuse size and minimum wire connection size. Field wiring should be completed by qualified personnel to the planned location for the chiller. All electrical wiring should comply with your region’s electrical codes.

A clean, well-ventilated environment.

The room temperature should not exceed 110° F (43° C) with 95% non-condensing humidity and should not fall below 55° F (12° C).

Minimum clearance for safe operation and mainte- nance. Nothing should be placed on top of the unit while the unit is operating. All models require a minimum clear- ance of 5 ft. around the perimeter for servicing. Models equipped with fans also require unrestricted outlet air flow.

A source of water for cooling on water-cooled units. City, tower or chiller water may be used, as long as the supply pressure is at least 25 psi and not more than 85 psi.

3

Install plumbing for process and cooling lines.

See the specification tables for the correct line and fitting sizes. Larger line sizes are acceptable as long as they are reduced at the chiller connections. Smaller line sizes are not recommended.

UGH004/0999

microKool Portable Chillers

INSTALLATION 3-3

Image 19
Contents Page Date Manual Number UGH004/0999 Serial numbers Model numbers Introduction Table of ContentsTroubleshooting Introduction HOW Guide is Organized Purpose User GuideYour Responsibility AS a User Read this SO no ONE Gets Hurt Page Description CHILLER? What is the MicrokoolTypical Applications HOW IT Works Water Cooled HOW IT Works AIR Cooled High Efficiency Compressors FeaturesPsi Pressure Specifications MPW Water CooledMPA-5 Specifications MPA AIR CooledFreeze Protection Requirements Freezing Points of Aqueous Ethylene Glycol SolutionsInstallation Boxes UnpackingMicroKool Portable Chillers come fully assembled Make sure the installation area provides Preparing for InstallationInstall plumbing for process and cooling lines Coat the pipe threads with thread sealant Connecting Process Water Supply LinesInstall pipe to the rear of the chiller Remove the shipping pipe plug from the femaleOpen the unit’s electrical enclosure Connecting Main Power SupplyUnits and check for leaks. If any leaks appear, stop Testing the InstallationApply power to the unit Turn on the condenser water supply MPWEntering Setpoint Deviation Parameters Dip switch Configuration Initial SetupOpen the electrical enclosure Change Dip Switch 1 to Changing Temperature UnitsSetpoint adjustment buttons Disconnect and lock out main power to the unitOpen the electrical enclosure Set dip switch 3 to on Select a new passcode usingOpen the electrical Press the RUN button to save the passcodeFollow Steps 1 through 5 Select a new control point using the Display button Selecting Temperature Control PointPress the RUN button to save the control point Set dip switch 5 toInsert the two power leads from the device Installing Auto Start FeatureWhen Auto Start is enabled Set dip switch 4 to the on positionTo disable Auto Start Enter the node address Apply power to the chiller Enter the passcode, if necessaryActivating SPI Communication Connect the host machine to the chillerOperation Setpoint display PC-1 Control FeaturesPumpdown On/Off PC-2 Control FeaturesTo detach the PC-2 control panel Positioning Control PanelTo raise and swivel the control panel To lower the control panelPress Setpoint to select the parameter you want to change Entering a PasscodeEnter the passcode Starting the ChillerPress Button to turn on Pumpdown Using Pumpdown FeatureStopping the Chiller To shut down the unit Press StopPerforming AN Auto Tune Insufficient setpoint/process deviation Page Maintenance Preventative Maintenance Schedule Quarterly every 3 months Inspect power cords, wires and electrical connectionsCleaning Condensers Cleaning EvaporatorsLocate the fill port at Back of the chiller Refilling the TankTo fill the reservoir If the charge is low, recharge the system Checking Refrigerant ChargeThen open the electrical enclosure Set dip switches 3Performing System Tests Press To shut down the chillerKEY/DISPLAY Test Select the Input Test menu Input TestConnect all inputs to the system Press any key to display the first test menusConnect all outputs to the system Output TestSelect the Output Test menu Disabling or Enabling Output Monitors Select the OM Enable/Disable menuSave changes and exit the output menu Release the Setpoint key Calibrating Temperature SensorsPress Select Exit Calibration ModePress the up key to begin calibrating Wait until the control displays don or badIndex through test menus to the operating log Logging Operating HoursExit the Operating Hours Log Troubleshooting Messages shown on the control panel. These Before BeginningFEW Words Verify that you have manuals for other equipCause of a Problem HOW to IdentifyGreater than the pump’s Supplied to the pumpMotor? Is the required water flowLoose? Is the thermocoupleDisconnected? Ply wire leads becomeLevel Switch fuse Has the indicated device Has one of the main supCompressor Air-cooled units Shut Down AlarmsRefrigerant pressure is either too low or too high All modelsFlow through he evapora Is the freezestat settingInstalled correctly? Freeze Stat Input is open Is there sufficient fluidCable? Is something wrong withSystem Alarms Chiller Will not Power UP Replace the fuse. The fuses are located on the mother Checking Replacing FusesIf fuses continue to fail On the front panel counterclockwise to openCheck the overload Resetting OverloadsLocate the pump overload module attached Replacing the Motherboard Replacing Compressor Contactor Reverse this procedure to install the new conRemove and discard the old contactor Checking Unloader Valve Replacing the Freezestat From outside the United States, call WE’RE Here to HelpAppendix A-2 SPI Command Pairs SPI Commands Supported by Conair MicrokoolStatus, Process SPI Status WordsStatus, Machine Appendix B-4 PARTS/DIAGRAMS PD-2 PD-3 PD-4 PD-5