●Quarterly (every 3 months)
❒Inspect power cords, wires and electrical connections.
Check for loose or frayed wires, burned contacts, and signs of overheated wires. Check exterior power cords to the main power source and from the electrical box to the pump and heating elements. Check the ground wire and thermocouple connections. Replace any wire that appears damaged or has worn or cracked insulation.
●Annually (every 12 months)
❒Test and calibrate the unit’s control systems. The chiller’s Test Mode checks the operation
of displays, control buttons, inputs and outputs. You can also calibrate the supply and return thermocouples.
See PERFORMING SYSTEM TESTS in this section.
❒Clean all surfaces that come in contact with water. Minerals and other water contaminants cause heat- transfer surface fouling and decrease performance, especially in the
EVAPORATORS AND CONDENSERS in this section.
WARNING: Improper servicing may result in equipment damage or per- sonal injury.
This equipment should be installed, adjusted, and serviced by qualified technical personnel who are familiar with the construction, opera- tion and potential hazards of this type of equip- ment.
All wiring, disconnects and fuses should be installed by qualified electrical technicians in accordance with electrical codes in your region.
Only certified refrigerant technicians should recharge the refrigerant used in this system.
Always disconnect and lock out the incoming main power source before opening the electri- cal enclosure or performing
PREVENTATIVE
MAINTENANCE
SCHEDULE