CHILLER
WILL NOT
POWER UP
If you apply power to the chiller and the control panel does not light, you have a problem with the main power circuit or the unit’s microprocessor board.
WARNING: Electrical Shock Hazard Disconnect and lockout the main power supply before proceeding.
Symptom | Possible cause Solution |
Applying power does not turn on the chiller or light the control panel.
Is power reaching the chiller?
❒Verify that the main power supply and any customer- installed electrical discon- nect or emergency stop devices are in the ON posi- tion.
❒Verify correct electrical con- nections between the unit and the control, and between the unit and the power supply. Replace any damaged wires or cables.
Has the unit blown a fuse?
Is the correct voltage reaching the chiller?
Check Fuse 1 on the mother- board and any fuses or breakers associated with customer- installed disconnect devices. Replace or reset as required. Identify the cause of the ground fault and correct it. See CHECK-
ING AND REPLACING FUSES.
Check the electrical require- ments on the unit nameplate. Verify correct main supply voltage to the unit and the sec- ondary voltage supply from the transformer to unit compo- nents. Replace the transformer, if necessary.
| The control panel is | Is the unit in Test Mode? | If the Test Mode LED is lit, | |
| lit, but the chiller |
| you must disable Test Mode on | |
| will not operate |
| the motherboard before resum- | |
| when RUN is |
| ing operation. See PERFORMING | |
| pressed. |
| SYSTEM TESTS in the | |
|
|
| MAINTENANCE section. | |
|
|
|
|
|
|
|
|
|
|
TROUBLESHOOTING | microKool Portable Chillers | UGH004/0999 |