Conair MPW, MPA manual Disabling or Enabling Output Monitors, Select the OM Enable/Disable menu

Page 53

All output monitors on the microKool chiller can be enabled or disabled permanently through the OM Enable/Disable Menu in Test Mode.

You need to use this feature if you have replaced the mother- board, or if dip switches 7 and 8 have been changed erro- neously. This will enable any required output monitors that were disabled and give fuse failures.

1

 

Enable Test Mode.

 

 

Press any key to display the first test menus.

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISABLING OR

ENABLING

OUTPUT

MONITORS

3

Select the OM Enable/Disable menu.

Press and hold the Setpoint key for 3 seconds to index to each test menu until the controller indicates “oS1” in the actual display and the status of the selected output in the Select display.

4

5

Press the Setpoint or key to change the status. Each press of the key changes the output status from ON to OFF or OFF to ON.

Press the Setpoint to select the next output.

Repeat Step 4 to change the status of the output, or press any key to continue indexing through the outputs.

6

Save changes and exit the output menu.

Press and hold the Select key for 3 seconds to save the changes and exit.

UGH004/0999

microKool Portable Chillers

MAINTENANCE 5-11

Image 53
Contents Page Date Manual Number UGH004/0999 Serial numbers Model numbers Introduction Table of ContentsTroubleshooting Introduction Your Responsibility AS a User Purpose User GuideHOW Guide is Organized Read this SO no ONE Gets Hurt Page Description Typical Applications What is the MicrokoolCHILLER? HOW IT Works Water Cooled HOW IT Works AIR Cooled High Efficiency Compressors FeaturesPsi Pressure Specifications MPW Water CooledMPA-5 Specifications MPA AIR CooledFreeze Protection Requirements Freezing Points of Aqueous Ethylene Glycol SolutionsInstallation MicroKool Portable Chillers come fully assembled UnpackingBoxes Install plumbing for process and cooling lines Preparing for InstallationMake sure the installation area provides Install pipe to the rear of the chiller Connecting Process Water Supply LinesRemove the shipping pipe plug from the female Coat the pipe threads with thread sealantOpen the unit’s electrical enclosure Connecting Main Power SupplyApply power to the unit Testing the InstallationTurn on the condenser water supply MPW Units and check for leaks. If any leaks appear, stopEntering Setpoint Deviation Parameters Dip switch Configuration Initial SetupOpen the electrical enclosure Change Dip Switch 1 to Changing Temperature UnitsOpen the electrical enclosure Set dip switch 3 to on Disconnect and lock out main power to the unitSelect a new passcode using Setpoint adjustment buttonsFollow Steps 1 through 5 Press the RUN button to save the passcodeOpen the electrical Select a new control point using the Display button Selecting Temperature Control PointPress the RUN button to save the control point Set dip switch 5 toInsert the two power leads from the device Installing Auto Start FeatureTo disable Auto Start Set dip switch 4 to the on positionWhen Auto Start is enabled Activating SPI Communication Apply power to the chiller Enter the passcode, if necessaryConnect the host machine to the chiller Enter the node addressOperation Setpoint display PC-1 Control FeaturesPumpdown On/Off PC-2 Control FeaturesTo raise and swivel the control panel Positioning Control PanelTo lower the control panel To detach the PC-2 control panelPress Setpoint to select the parameter you want to change Entering a PasscodeEnter the passcode Starting the ChillerStopping the Chiller Using Pumpdown FeatureTo shut down the unit Press Stop Press Button to turn on PumpdownPerforming AN Auto Tune Insufficient setpoint/process deviation Page Maintenance Preventative Maintenance Schedule Quarterly every 3 months Inspect power cords, wires and electrical connectionsCleaning Condensers Cleaning EvaporatorsTo fill the reservoir Refilling the TankLocate the fill port at Back of the chiller If the charge is low, recharge the system Checking Refrigerant ChargePerforming System Tests Set dip switches 3Press To shut down the chiller Then open the electrical enclosureKEY/DISPLAY Test Connect all inputs to the system Input TestPress any key to display the first test menus Select the Input Test menuSelect the Output Test menu Output TestConnect all outputs to the system Save changes and exit the output menu Select the OM Enable/Disable menuDisabling or Enabling Output Monitors Release the Setpoint key Calibrating Temperature SensorsPress the up key to begin calibrating Exit Calibration ModeWait until the control displays don or bad Press SelectExit the Operating Hours Log Logging Operating HoursIndex through test menus to the operating log Troubleshooting FEW Words Before BeginningVerify that you have manuals for other equip Messages shown on the control panel. TheseCause of a Problem HOW to IdentifyMotor? Supplied to the pumpIs the required water flow Greater than the pump’sLoose? Is the thermocoupleLevel Switch fuse Has the indicated device Ply wire leads becomeHas one of the main sup Disconnected?Compressor Refrigerant pressure is either too low or too high Shut Down AlarmsAll models Air-cooled unitsInstalled correctly? Is the freezestat settingFreeze Stat Input is open Is there sufficient fluid Flow through he evaporaCable? Is something wrong withSystem Alarms Chiller Will not Power UP If fuses continue to fail Checking Replacing FusesOn the front panel counterclockwise to open Replace the fuse. The fuses are located on the motherLocate the pump overload module attached Resetting OverloadsCheck the overload Replacing the Motherboard Remove and discard the old contactor Reverse this procedure to install the new conReplacing Compressor Contactor Checking Unloader Valve Replacing the Freezestat From outside the United States, call WE’RE Here to HelpAppendix A-2 SPI Command Pairs SPI Commands Supported by Conair MicrokoolStatus, Process SPI Status WordsStatus, Machine Appendix B-4 PARTS/DIAGRAMS PD-2 PD-3 PD-4 PD-5