SHUT DOWN ALARMS
The chiller has detected a problem that could lead to equipment damage or personal injury if it is not corrected.
◆The Alarm LED lights and the STOP/RUN LED flashes red.
◆The chiller automatically shuts down.
◆The control displays a red LED or alarm code indicating the source of the problem.
Alarm | Possible cause Solution |
Pump
The pump motor overload has tripped. The contact is open.
Is the correct voltage | Supply voltage should match |
supplied to the pump | the rating on the pump name |
motor? | plate. If voltage is correct, |
| check wiring connections. |
Is the required water flow | ❒ Review pump sizing |
greater than the pump’s | for the application. |
capacity? | ❒ Decrease the water flow |
| from the process. |
WARNING:
Only qualified electri- cal service personnel should examine and correct problems that require opening the unit's electrical enclosure or checking electrical current to diagnose the cause of a problem.
Is the motor overload faulty or set incorrectly?
Is the pump working properly?
Disconnect the power and open the electrical enclosure. Verify that the overload is set to trip at the proper amperage, which should not exceed the FLA. Manually trip and reset the overload. If the problem contin- ues, replace the overload. See
RESETTING AND REPLACING OVERLOADS.
Replace the pump if supply voltage, wiring and overload settings are correct, but the pump continues to draw exces- sive current.
Hi SAF
The actual tempera- ture of water supplied to the process is 100° F, or has exceeded 75° F for more than 30 minutes.
Is the refrigerant charge low?
Is the unloader valve stuck open?
Did the compressor fail?
See CHECKING REFRIGERANT
CHARGE. If the charge is low, contact a certified refrigeration technician to recharge.
See CHECKING THE UNLOADER
VALVE. If the valve is stuck open,
contact a certified refrigeration technician to repair.
Check compressor electrical connections. Replace the com- pressor, if it has failed.
TROUBLESHOOTING | microKool Portable Chillers | UGH004/0999 |