Conair MPW, MPA manual Entering Setpoint Deviation Parameters

Page 23

You can establish a normal operating range around the process temperature setpoint using the high and low deviation parame- ters. If the process temperature exceeds the high deviation limit, or falls below the low deviation limit for longer than 15 minutes, the chiller will alert you to the unacceptable tempera- ture variation with an alarm light.

These temperature deviation limits will adjust automatically relative to the process temperature setpoint.

The factory default setting is the process temperature setpoint

±10° F (6° C). This parameter is adjustable to establish a nar- rower or wider acceptable temperature range for normal oper- ation. You cannot set the Low Deviation below the factory-set Low Safety temperature. The High Deviation cannot be set to exceed the factory-set High Safety temperature.

FACTORY DEFAULT SETTINGS

Model

MPW

MPA

Process Setpoint

50° F (10° C)

50° F (10° C)

High Safety

75° F (24° C)

75° F (24° C)

Low Safety

10° F (-12° C)

10° F (-12° C)

 

 

 

To change the temperature deviation settings:

1 Press the Setpoint Select button to select the deviation parameter you want to change.

2 Use the and setpoint buttons to enter the deviation temperature. The setting is stored in memory even when the power is turned off. The recom- mended setting is ± 2-10° F.

NOTE: If you enabled passcode protection, you must enter the passcode to change this parameter. See ENABLING AND

DISABLING PASSCODE PROTECTION.

Too enter the passcode:

Hold down the Setpoint Select button for 5 seconds. When the control displays “ 1 PaS”, use the setpoint adjustment buttons to enter the passcode. Press the Setpoint Select button again. If the correct passcode was entered the controller will display ACC PAS for 3 seconds. If the passcode was incorrect, the controller will display rEJ PAS (rejected passcode).

Access to system parameters remain until power is cycled or the RUN or STOP button is pressed.

ENTERING

SETPOINT

DEVIATION

PARAMETERS

UGH004/0999

microKool Portable Chillers

INSTALLATION 3-7

Image 23
Contents Page Date Manual Number UGH004/0999 Serial numbers Model numbers Introduction Table of ContentsTroubleshooting Introduction Your Responsibility AS a User Purpose User GuideHOW Guide is Organized Read this SO no ONE Gets Hurt Page Description Typical Applications What is the MicrokoolCHILLER? HOW IT Works Water Cooled HOW IT Works AIR Cooled High Efficiency Compressors FeaturesPsi Pressure Specifications MPW Water CooledMPA-5 Specifications MPA AIR CooledFreeze Protection Requirements Freezing Points of Aqueous Ethylene Glycol SolutionsInstallation MicroKool Portable Chillers come fully assembled UnpackingBoxes Install plumbing for process and cooling lines Preparing for InstallationMake sure the installation area provides Coat the pipe threads with thread sealant Connecting Process Water Supply LinesInstall pipe to the rear of the chiller Remove the shipping pipe plug from the femaleOpen the unit’s electrical enclosure Connecting Main Power SupplyUnits and check for leaks. If any leaks appear, stop Testing the InstallationApply power to the unit Turn on the condenser water supply MPWEntering Setpoint Deviation Parameters Dip switch Configuration Initial SetupOpen the electrical enclosure Change Dip Switch 1 to Changing Temperature UnitsSetpoint adjustment buttons Disconnect and lock out main power to the unitOpen the electrical enclosure Set dip switch 3 to on Select a new passcode usingFollow Steps 1 through 5 Press the RUN button to save the passcodeOpen the electrical Select a new control point using the Display button Selecting Temperature Control PointPress the RUN button to save the control point Set dip switch 5 toInsert the two power leads from the device Installing Auto Start FeatureTo disable Auto Start Set dip switch 4 to the on positionWhen Auto Start is enabled Enter the node address Apply power to the chiller Enter the passcode, if necessaryActivating SPI Communication Connect the host machine to the chillerOperation Setpoint display PC-1 Control FeaturesPumpdown On/Off PC-2 Control FeaturesTo detach the PC-2 control panel Positioning Control PanelTo raise and swivel the control panel To lower the control panelPress Setpoint to select the parameter you want to change Entering a PasscodeEnter the passcode Starting the ChillerPress Button to turn on Pumpdown Using Pumpdown FeatureStopping the Chiller To shut down the unit Press StopPerforming AN Auto Tune Insufficient setpoint/process deviation Page Maintenance Preventative Maintenance Schedule Quarterly every 3 months Inspect power cords, wires and electrical connectionsCleaning Condensers Cleaning EvaporatorsTo fill the reservoir Refilling the TankLocate the fill port at Back of the chiller If the charge is low, recharge the system Checking Refrigerant ChargeThen open the electrical enclosure Set dip switches 3Performing System Tests Press To shut down the chillerKEY/DISPLAY Test Select the Input Test menu Input TestConnect all inputs to the system Press any key to display the first test menusSelect the Output Test menu Output TestConnect all outputs to the system Save changes and exit the output menu Select the OM Enable/Disable menuDisabling or Enabling Output Monitors Release the Setpoint key Calibrating Temperature SensorsPress Select Exit Calibration ModePress the up key to begin calibrating Wait until the control displays don or badExit the Operating Hours Log Logging Operating HoursIndex through test menus to the operating log Troubleshooting Messages shown on the control panel. These Before BeginningFEW Words Verify that you have manuals for other equipCause of a Problem HOW to IdentifyGreater than the pump’s Supplied to the pumpMotor? Is the required water flowLoose? Is the thermocoupleDisconnected? Ply wire leads becomeLevel Switch fuse Has the indicated device Has one of the main supCompressor Air-cooled units Shut Down AlarmsRefrigerant pressure is either too low or too high All modelsFlow through he evapora Is the freezestat settingInstalled correctly? Freeze Stat Input is open Is there sufficient fluidCable? Is something wrong withSystem Alarms Chiller Will not Power UP Replace the fuse. The fuses are located on the mother Checking Replacing FusesIf fuses continue to fail On the front panel counterclockwise to openLocate the pump overload module attached Resetting OverloadsCheck the overload Replacing the Motherboard Remove and discard the old contactor Reverse this procedure to install the new conReplacing Compressor Contactor Checking Unloader Valve Replacing the Freezestat From outside the United States, call WE’RE Here to HelpAppendix A-2 SPI Command Pairs SPI Commands Supported by Conair MicrokoolStatus, Process SPI Status WordsStatus, Machine Appendix B-4 PARTS/DIAGRAMS PD-2 PD-3 PD-4 PD-5