INITIAL SETUP
NOTE: Dip switch 7 must be ON and dip switch 8 must be OFF for the chiller to work. Do not change the factory setting of these two dip switches.
WARNING: Electric shock hazard
This equipment is powered by high voltage. Always disconnect and lock out the main power source before opening the unit or the electrical enclosure to modify factory settings. Failure to disconnect and lock out the main power source can result in severe personal injury.
The
You can modify the parameters for high and low process tem- perature deviation warnings from the control panel. See
SETTING SETPOINT DEVIATION PARAMETERS.
Dip switches on the motherboard inside the
❒Select the units of measure for tem- perature displays.
❒Enable password protection.
❒ Enable the Auto Tune.
❒Enable the Auto Start feature.
❒Enable the Test Mode.
❒ Select the source point of tempera- ture control.
8 7 6 5 4 3 2 1
Dip switch Configuration
No. | OFF | ON | |
1 |
| Display units in °F | Display units °C |
2 |
| Auto Tune disabled | Auto Tune enabled |
3 |
| Passcode protect | Password reset/modify |
|
|
|
|
4 | * | Auto Start disabled | Auto Start enabled |
5 | * | Control point protect | Control point source select |
6 |
| Test Mode disabled | Test mode enabled |
7 | † | Controller type selection | Controller type selection |
8 | † | Controller type selection | Controller type selection |
|
|
|
|
* Available only on
†Switch 7 must be ON, and switch 8 must be OFF. Do not change the settings of these two switches.
To change the dip switch settings, see the appropriate topic on the following pages.
INSTALLATION | microKool Portable Chillers | UGH004/0999 |