Display menu: “Data display”
From the menu screen, select “Data Display” then press
Pressing or will allow navigation from screen 1 to 8 as shown hereafter:
The menu is looped making it possible to scroll from the first item in the menu to the last item.
Lvg Wat Temp | 08.0°C |
Ret Wat Temp | 12.0°C |
Amb Temp | 28.0°C |
Active StP | 07.0°C |
|
|
1.Water and air temperatures Lvg Wat Temp = Leaving water temperature
Ret Wat Temp = Entering water temperature
Amb Temp = Ambient air temperature
Active StP = Active water setpoint
HP ckt1 | 00.0 bar |
HP ckt2 | 00.0 bar |
LP ckt1 | 00.0 bar |
LP ckt2 | 00.0 bar |
|
|
2. Refrigerant pressures
HP ckt1 = Condensing Pressure circuit 1
HP ckt2 = Condensing Pressure circuit 2 (dual circuit units only) LP ckt1 = Evaporating Pressure circuit 1
LP ckt2 = Evaporating Pressure circuit 2 (dual circuit units only)
3. Refrigerant saturated temperatures
Sat Temp CDS1 | 00.0°C |
Sat Temp CDS2 | 00.0°C |
Sat Temp EVP1 | 00.0°C |
Sat Temp EVP2 | 00.0°C |
|
|
Sat Temp CDS1 = Condensing temperature circuit 1
Sat Temp CDS2 = Condensing temperature circuit 2 (dual circuit units only)
Sat Temp EVP1 = Evaporating temperature circuit 1
Sat Temp EVP2 = Evaporating temperature circuit 2 (dual circuit units only)
Legend for screens 4,5 and 6: Cmp A1 = Compressor A/circuit 1 Cmp B1/C1 = Compressor B and C/circuit 1
Cmp A2 = Compressor A/circuit 2 (dual circuit units only)
Cmp B2/C2 = Compressor B and C/circuit 2 (dual circuit units only)
Cmp A1 | Off |
Cmp B1 C1 | Off |
Cmp A2 | Off |
Cmp B2 C2 | Off |
|
|
4.Compressors status Possible Status:
Off = Compressor stopped On = Compressor running Rec.On = Compressor will start after
Rec.Off = Compressor will stop after
Cmp A1 | 000000 Hrs |
Cmp B1 C1 | 000000 Hrs |
Cmp A2 | 000000 Hrs |
Cmp B2 C2 | 000000 Hrs |
|
|
5.Compressors running time Hrs indicates the number of full hours compressor has been working since its first start.
6. Number of compressors starts
Cmp A1 | 000000 Starts |
Cmp B1 C1 | 000000 Starts |
Cmp A2 | 000000 Starts |
Cmp B2 C2 | 000000 Starts |
|
|
Starts indicates the number of compressor starts since first
7. Operating mode
Mode |
| Cooling |
Stp | Local | 07.0°C |
Ckt1 |
| Enable |
Ckt2 |
| Enable |
|
|
|
Mode = Running mode
-Cooling = Cold water production
-Heating = Hot water production
(Reversible chillers only)
Stp Local 07.0°C
-Stp = Current setpoint
-Local = Source of Setpoint Local = Cooling or heating setpoint defined locally Extern = Auxiliary setpoint or operating mode by external contact
Auto = setpoint by the automatic reset or the daily/weekly program Remote = Setpoint by supervisor
Ckt1/Ckt 2 = Operational circuits
-Enable = Circuit is operational
-Disable = Circuit is not operational
8.Compressors failures counters
Nb of CMP faults |
| |
Cpt | A1:0 | Cpt A 2:0 |
Cpt | B1:0 | Cpt B 2:0 |
Cpt | C1:0 | Cpt C 2:0 |
|
|
|
This menu indicates the number of compressors failure regardless of the history.
11 |