American Standard TRACER CH532 manual LED meaning and function

Page 26

LonTalk® option

LED meaning and function

Green Status LED

LED status

Meaning/Function

LED is OFF continuously.

• Normal condition

 

• Broken hardware

 

• No power

LED is ON.

• Broken hardware

·

• During the activation of the service pin

 

• The node is Applicationless

LED blinks 1second then always OFF

• When receiving a WINK command from the network (1)

LED blinks ½ second ON then always OFF

• Normal operation (usually after a reset)

LED flashes once every second

• The node card is not configured

 

• The node card is in continuous reset

(1)By sending a request, you can request the controller’s green status LED to blink (“wink”), a notification that the controller received the signal and is communicating.

Red Service LED

LED status

Meaning/Function

LED is ON for 20 seconds when power is applied to the controller

• The controller is in a reset phase

LED is OFF continuously

• The controller is operating normally

 

• Broken hardware

LED is ON during 2 seconds then always OFF

• When power is applied to the controller

 

• After a reset

LED is ON continuously

• The controller is not working properly

 

• Broken hardware

 

• Problems of connection with the CH532 module

Object details

Figure 10

Chiller Controller 8040

Mandatory network variables

nv1

nviChillerEnable

nv3

snvt_switch

 

 

nv2

nviCoolSetpt

nv4

snvt_temp_p

 

 

 

 

 

nvoOnOff snvt_switch

nvoActiveSetpt snvt_temp_p

Optional network variables

nv7

nviMode

nv11

nvoLvgCHWTTemp

Snvt_hvac_mode

snvt_temp_p

 

 

nv8

nviHeatSetpt

nv12

nvoEntCHWTTemp

snvt_temp_p

snvt_temp_p

 

 

 

 

nv13

nvoEntCndWTemp

 

 

 

 

snvt_temp_p

 

 

 

 

 

nv15

nvoAlarmDescr

 

 

snvt_str_asc

 

 

 

 

 

nv16

nvoChillerStat

 

 

snvt_chlr_status

 

 

 

 

 

 

 

Note: BAS intergrators requiring .xif file need to contact their local sales representative.

Other optional network variables are not supported.

26

CG-SV01B-E4

Image 26
Contents Tracer CH532 Chiller controller User guide General information About this manualContents Tracer CH532 Presentation Hardware architecture Tracer CH532 inputs and outputsTracer CH532 General description DescriptionNO11, NO13 Inputs and output summary listTracer CH532 Medium Y3 0..10V + ConvonoffCustomer Inputs and output summary list Starting/stopping the unit Accessing the menus MenusDisplay menu Data display Stp Local 07.0CCustomer settings menu Settings Customer Inputs and Outputs Operating modeMode Cooling Comp seq Auto Ckt1 Enable Status output NO10Remote Mode Chiller control Mode Local RemoteClock Setting menu Clock Weekly Program Hourly zone DisableWeekly program Start Mon Stop FriUnit configuration menu Configuration Pump Pump protection input Invert Inverter Compressors timersHP Control Control dead bandsPT100 Sensors and transducersPress probe 20mA Min Press 0bar Max Press 30.0bar 10V 0..1V 0..20mADefault parameters? Set the default parameters CW High Limit 15.0C Low ambient temperature limitationCompressor alarm Operating limits cooling Low Amb Cooling Low Amb LimitAlarms history AlarmsAlarms display and Resetting Unit status Description Status, warnings and alarm messagesMessage History events record No MessageLonTalk option DescriptionGreen Status LED LED status Meaning/Function Red Service LED LED status Meaning/FunctionLED meaning and function HVACHEAT=1, HVACCOOL=3 Attenuation dB/1000 feet at 20C maximum Cable characteristicsCharacteristic impedance ohms CG-SV01B-E4 CG-SV01B-E4 CG-SV01B-E4 Safety recommendations