Unit configuration menu: “Configuration”
2. Compressors timers
To access one of the parameters
displayed, press |
| and change |
value using | or | . Confirm the |
value by pressing |
| |
ACC 1st Start |
| 2 min |
ACC |
| 5 min |
Min |
| 060 s |
Min |
| 015 s |
ACC 1st Start: Short cycle compressor at first start (0 to 60 min - factory setting: 2min)
ACC
Min
Min
3. HP Control
To access one of the parameters
displayed, press |
| and change |
value using | or | . Confirm the |
value pressing |
|
|
Fan control |
| 1Speed |
Fan Ctrl Stp |
| 15.0 b |
Dead band Fan |
| 06.0 b |
Fan Control: Fan type:
1 speed: 1 Speed fan
2 speed: 2 Speed fan
Invert: Inverter
Fan Ctrl StP: Fan control setpoint
(10 to 30 bar - factory setting: 15 bar)
Dead band Fan: Fans regulation dead band (2 to 8 bar - factory setting: 5 bar)
4. Control dead bands
To access one of the parameters
displayed, press and change
value using or . Confirm the value by pressing
Dead band Cmp | 03.0°C |
Antifreeze02.0°C
Heater03.0°C
Dead band Cmp: Compressors regulation dead band around water temperature (0.4 to 8.0°C - factory setting: 3.0°C)
AntiFreeze: Cold water temperature limit
Heater: Evaporator heater setpoint according to ambient air temperature (0 to 10°C - factory setting: 3°C)
5. Winter Freeze Protection
CW High Limit | 15°C |
Pmp Cycle OFF | 10 min |
WinFreezeProtPmp | Yes |
Ctrl Pump Required |
|
|
|
Chilled water high limit: (15 to 25°C: factory setting 15°C)
Water pump cycle OFF: (5 to 15 min: factory setting 10min)
Winter Freeeze protection with pump:
No ➨ Heater or Ethylene
Glycol Required
Yes ➨ Ctrl Pump Required
19 |