Hardware architecture
TRACER CH532 offers customer the possibility to use inputs or outputs in order to:
-use an external water setpoint reset using an analog input (refer to figure 3)
-use an auxiliary setpoint
-connect a remote on/off of the unit or a circuit
-reset faults
-connect a remote Cooling/Heating switch
-return a circuit fault
Note: External water setpoint Based on a external signal input, it will be possible to offset the active setpoint from 0°C to 20°C. This function can be used in conjunction with the automatic setpoint reset function.
Figure 3
setpoint |
| 5 | 4 |
1 |
| ||
|
| ||
Water |
|
| |
|
|
| |
| 2 | Ambient | 3 |
| temperature |
1.Leaving water temperature setpoint
2.Minimum value
3.Maximum value
4.Reset = 20°C
5.Active setpoint
Table 3: Customer Inputs and output summary list
|
| TRACER CH532 Medium | TRACER CH532 Large |
|
| Single circuit units | Dual circuit units |
AI | External water setpoint reset (option) | B8: | |
DI | Auxiliary setpoint On/Off | ID8: 24Vac | |
DI | Circuit 1 On/Off (or Unit On/Off |
|
|
| for single circuit units) | ID13H: 230Vac | |
DI | Circuit 2 On/Off | - | ID16H: 230Vac |
DI | Faults external reset | ID6: 24Vac | |
DI | Cooling/Heating mode switch | ID7: 24Vac | |
DO | Circuit 1 fault | NO9: | |
DO | Circuit 2 fault | - | NO11: |
DO | Unit status or additional |
|
|
| heating demand | NO10: |
Legend:
AI: Analog Input
DI: Digital Input
DO: Digital Output
8 |