American Standard TRACER CH532 manual Customer Inputs and output summary list

Page 8

Hardware architecture

TRACER CH532 offers customer the possibility to use inputs or outputs in order to:

-use an external water setpoint reset using an analog input (refer to figure 3)

-use an auxiliary setpoint

-connect a remote on/off of the unit or a circuit

-reset faults

-connect a remote Cooling/Heating switch

-return a circuit fault

Note: External water setpoint Based on a external signal input, it will be possible to offset the active setpoint from 0°C to 20°C. This function can be used in conjunction with the automatic setpoint reset function.

Figure 3

setpoint

 

5

4

1

 

 

 

Water

 

 

 

 

 

 

2

Ambient

3

 

temperature

1.Leaving water temperature setpoint

2.Minimum value

3.Maximum value

4.Reset = 20°C

5.Active setpoint

Table 3: Customer Inputs and output summary list

 

 

TRACER CH532 Medium

TRACER CH532 Large

 

 

Single circuit units

Dual circuit units

AI

External water setpoint reset (option)

B8: 0..10V-0..20mA

DI

Auxiliary setpoint On/Off

ID8: 24Vac

DI

Circuit 1 On/Off (or Unit On/Off

 

 

 

for single circuit units)

ID13H: 230Vac

DI

Circuit 2 On/Off

-

ID16H: 230Vac

DI

Faults external reset

ID6: 24Vac

DI

Cooling/Heating mode switch

ID7: 24Vac

DO

Circuit 1 fault

NO9: NO-230Vac

DO

Circuit 2 fault

-

NO11: NO-230Vac

DO

Unit status or additional

 

 

 

heating demand

NO10: NO-230Vac

Legend:

AI: Analog Input

DI: Digital Input

DO: Digital Output

8

CG-SVU01B-E4

Image 8
Contents Tracer CH532 Chiller controller User guide General information About this manualContents Tracer CH532 Presentation Hardware architecture Tracer CH532 inputs and outputsTracer CH532 General description DescriptionInputs and output summary list Tracer CH532 MediumNO11, NO13 Y3 0..10V + ConvonoffCustomer Inputs and output summary list Starting/stopping the unit Accessing the menus MenusDisplay menu Data display Stp Local 07.0CCustomer settings menu Settings Operating mode Mode Cooling Comp seq Auto Ckt1 EnableCustomer Inputs and Outputs Status output NO10Remote Mode Chiller control Mode Local RemoteClock Setting menu Clock Program Hourly zone Disable Weekly programWeekly Start Mon Stop FriUnit configuration menu Configuration Pump Pump protection input Compressors timers HP ControlInvert Inverter Control dead bandsSensors and transducers Press probe 20mA Min Press 0bar Max Press 30.0barPT100 10V 0..1V 0..20mACW High Limit 15.0C Low ambient temperature limitation Compressor alarmDefault parameters? Set the default parameters Operating limits cooling Low Amb Cooling Low Amb LimitAlarms history AlarmsAlarms display and Resetting Unit status Description Status, warnings and alarm messagesMessage History events record No MessageLonTalk option DescriptionGreen Status LED LED status Meaning/Function Red Service LED LED status Meaning/FunctionLED meaning and function HVACHEAT=1, HVACCOOL=3 Attenuation dB/1000 feet at 20C maximum Cable characteristicsCharacteristic impedance ohms CG-SV01B-E4 CG-SV01B-E4 CG-SV01B-E4 Safety recommendations