American Standard TRACER CH532 manual Clock Setting menu Clock

Page 15

Clock Setting menu: “Clock”

From the menu screen, select

Clock” then press . Following screen will appear:

User password

0000

Enter default password:”0000” (factory set)

Press and cursor will move to first field of password. Pressing

or will increment the value from 0 to 9999. Keeping pressure on

or will move the numbers fast.

Press to confirm password.

Pressing or will allow navigation from screen 1 to 3 as shown hereafter:

1. Clock setting

To access one of the 4 parameters displayed, press and change value

using or . Confirm the value

by pressing Mon: Weekday

Clock

Mon

Hour00:00

Date00/00/00

Mon: Monday (factory setting)

Tue: Tuesday

Wed: Wednesday

Thu: Thursday

Fri: Friday

Sat: Saturday

Sun: Sunday

Hour: Time (hours/minutes)

Date: Date setting (day/month/year)

2. ON/OFF program type

When enabled, this program will control the unit operation (On/Off). This program will allow the user to:

-Make a choice between the daily and/or the weekly operation

-Define the operational days and hours

-Define the operating setpoints for each mode (cooling and heating)

The operating mode selected by the operator or by the external control will be taken into account. Example:

Time

 

Monday

Tuesday

Wednesday

Thursday

Friday

Saturday

00:00

 

 

 

 

 

 

 

02:00

 

 

 

 

 

 

 

04:00

 

 

 

 

 

 

 

06:00

 

 

 

 

 

 

 

08:00

 

Operation enable

Example

 

 

 

10:00

 

 

 

 

 

12:00

ƒ

from Monday to Friday

 

 

 

 

14:00

ƒ

from 8:00 to 18:00

 

 

 

 

 

 

 

 

 

 

 

 

16:00

 

 

 

 

 

 

 

18:00

 

 

 

 

 

 

 

20:00

 

 

 

 

 

 

 

22:00

 

 

 

 

 

 

 

To access one of the parameters

displayed, press and change

value using or . Confirm the value by pressing

 

Program

 

On/Off Unit

Weekly

N

Daily

N

 

 

Weekly: Weekly program

Y: Enabled

N: Disabled (factory setting)

Daily: Daily program

Y: Enabled

N: Disabled (factory setting)

CG-SV01B-E4

15

Image 15
Contents Tracer CH532 Chiller controller User guide About this manual General informationContents Tracer CH532 Presentation Tracer CH532 inputs and outputs Hardware architectureDescription Tracer CH532 General descriptionY3 0..10V + Convonoff Inputs and output summary listTracer CH532 Medium NO11, NO13Customer Inputs and output summary list Starting/stopping the unit Menus Accessing the menusStp Local 07.0C Display menu Data displayCustomer settings menu Settings Status output NO10 Operating modeMode Cooling Comp seq Auto Ckt1 Enable Customer Inputs and OutputsChiller control Mode Local Remote Remote ModeClock Setting menu Clock Start Mon Stop Fri Program Hourly zone DisableWeekly program WeeklyUnit configuration menu Configuration Pump Pump protection input Control dead bands Compressors timersHP Control Invert Inverter10V 0..1V 0..20mA Sensors and transducersPress probe 20mA Min Press 0bar Max Press 30.0bar PT100Operating limits cooling Low Amb Cooling Low Amb Limit CW High Limit 15.0C Low ambient temperature limitationCompressor alarm Default parameters? Set the default parametersAlarms Alarms display and ResettingAlarms history Status, warnings and alarm messages MessageUnit status Description No Message History events recordDescription LonTalk optionRed Service LED LED status Meaning/Function LED meaning and functionGreen Status LED LED status Meaning/Function HVACHEAT=1, HVACCOOL=3 Cable characteristics Characteristic impedance ohmsAttenuation dB/1000 feet at 20C maximum CG-SV01B-E4 CG-SV01B-E4 CG-SV01B-E4 Safety recommendations