American Standard TRACER CH532 manual Alarms display and Resetting, Alarms history

Page 22

Alarms

1. Alarms display and Resetting

A fault on a unit will be shown through the user interface or through 2 digital outputs, one for each refrigerant circuit.

The alarms are divided into 3 categories:

-Warning. Shows that something is wrong on the unit but unit can be kept in operation. A message is displayed on the user interface screen. These messages are not recorded in the history list.

-Fault with automatic reset: when the cause of the fault disappears, the fault is cancelled and unit operation will return to normal. The messages displayed on the user interface screen disappear but are recorded in the history list of faults. The fault is relayed through the digital output if I/O parameter is set to show a circuit fault.

-Fault with manual reset: when the cause of the fault disappears, a manual reset is required to restart the unit. The messages displayed on the user interface screen disappear and are recorded in the history list of faults. The fault is relayed through the digital output if I/O parameter is set to show a circuit fault.

Should an alarm occur, will be lit in red.

Pressing once will display the alarm message (refer to table 4 for possible messages)

When alarm message is displayed

press to reset the default if necessary.

2. Alarms history

200 events can be recorded by TRACER CH532. Each record will give the fault description, the reset type, the order and the day and time of occurrence.

Maintaining for 5 seconds give will access to the last event recorded.

Then using allows the user to view the complete history. (refer to table 5 for possible messages)

22

CG-SV01B-E4

Image 22
Contents Tracer CH532 Chiller controller User guide General information About this manualContents Tracer CH532 Presentation Hardware architecture Tracer CH532 inputs and outputsTracer CH532 General description DescriptionNO11, NO13 Inputs and output summary listTracer CH532 Medium Y3 0..10V + ConvonoffCustomer Inputs and output summary list Starting/stopping the unit Accessing the menus MenusDisplay menu Data display Stp Local 07.0CCustomer settings menu Settings Customer Inputs and Outputs Operating modeMode Cooling Comp seq Auto Ckt1 Enable Status output NO10Remote Mode Chiller control Mode Local RemoteClock Setting menu Clock Weekly Program Hourly zone DisableWeekly program Start Mon Stop FriUnit configuration menu Configuration Pump Pump protection input Invert Inverter Compressors timersHP Control Control dead bandsPT100 Sensors and transducersPress probe 20mA Min Press 0bar Max Press 30.0bar 10V 0..1V 0..20mADefault parameters? Set the default parameters CW High Limit 15.0C Low ambient temperature limitationCompressor alarm Operating limits cooling Low Amb Cooling Low Amb LimitAlarms display and Resetting AlarmsAlarms history Message Status, warnings and alarm messagesUnit status Description History events record No MessageLonTalk option DescriptionLED meaning and function Red Service LED LED status Meaning/FunctionGreen Status LED LED status Meaning/Function HVACHEAT=1, HVACCOOL=3 Characteristic impedance ohms Cable characteristicsAttenuation dB/1000 feet at 20C maximum CG-SV01B-E4 CG-SV01B-E4 CG-SV01B-E4 Safety recommendations