Customer settings menu: “Settings”

From the menu screen, select

Settings” then press . Following screen will appear:

User password

0000

Enter password:”0000” (factory-set)

Press and cursor will move to first field of password. Pressing

or will change the value from 0

to 9999. Keeping pressure on or

will move the numbers fast.

Press to confirm password.

Pressing will allow navigation from screen 1 to 5 as shown hereafter:

1. Setpoints

Cooling Stp

07.0°C

Heating Stp

45.0°C

Aux Wat Stp

10.0°C

Aux Wat

Disable

 

 

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Cooling StP

 

07.0°C

Heating StP

 

45.0°C

Aux Wat StP

 

10.0°C

Aux Wat

 

Disable

Cooling Stp = Cold water setpoint (-12 to 20°C - factory setting: 7°C) Heating Stp = Hot water setpoint

(20 to 60°C - factory setting: 45°C) Aux Wat Stp = Auxiliary setpoint (-12 to 60°C - factory setting: 10°C) Aux Wat = Auxiliary setpoint from external source:

Enable = Auxiliary setpoint validated Disable = Auxiliary setpoint non- validated

. Automatic cooling and heating mode setpoints reset

TRACER CH532 offers the possibility to offset cold and/or hot water setpoints according to ambient air temperature.

The automatic setpoint reset program will allow you to change the water temperature setpoint (cooling and heating mode) with the ambient temperature. This function can be used in conjunction with the external setpoint reset function.

Figure 4

5

4

1

 

Ambient

2 temperature 3

1.Leaving water temperature setpoint

2.Starting point

3.Ending point

4.Reset delta

5.Active set point

Below the reset starting point, the water temperature setpoint will be the normal setting. Between the starting and ending point the setpoint will vary proportionally with the ambient temperature. After the ending point, the setpoint will stay at its maximum or minimum value.

2.1Cooling mode setpoint reset To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Cold water reset

N

Start Point

 

20.0°C

End Point

 

30.0°C

Reset Delta

 

10.0°C

Cold Water Reset: Ambient temperature based cold water setpoint offset

Y = Enabled

N = Disabled (factory setting) Start Point: Starting point (-15 to 50°C - factory setting: 20°C)

End Point: Ending point (-15 to 60°C

- factory setting: 30°C)

Reset Delta: Reset amplitude (-15 to

15°C - factory setting: 10°C)

3.Heating mode setpoint reset (Reversible chillers only)

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Hot water reset

N

Start Point

 

20.0°C

End Point

 

30.0°C

Reset Delta

 

10.0°C

Hot Water Reset: Ambient temperature based hot water setpoint offset

Y = Enabled

N = Disabled (Factory setting) Start Point: Starting point

(-15 to 50°C - factory setting: 20°C)

End Point: Ending point

(-15 to 60°C - factory setting: 30°C)

Reset Delta: Reset amplitude

(-15 to 15°C - factory setting: 10°C)

12

CG-SVU01B-E4

Image 12
Contents Tracer CH532 Chiller controller User guide General information About this manualContents Tracer CH532 Presentation Hardware architecture Tracer CH532 inputs and outputsTracer CH532 General description DescriptionInputs and output summary list Tracer CH532 MediumNO11, NO13 Y3 0..10V + ConvonoffCustomer Inputs and output summary list Starting/stopping the unit Accessing the menus MenusDisplay menu Data display Stp Local 07.0CCustomer settings menu Settings Operating mode Mode Cooling Comp seq Auto Ckt1 EnableCustomer Inputs and Outputs Status output NO10Remote Mode Chiller control Mode Local RemoteClock Setting menu Clock Program Hourly zone Disable Weekly programWeekly Start Mon Stop FriUnit configuration menu Configuration Pump Pump protection input Compressors timers HP ControlInvert Inverter Control dead bandsSensors and transducers Press probe 20mA Min Press 0bar Max Press 30.0barPT100 10V 0..1V 0..20mACW High Limit 15.0C Low ambient temperature limitation Compressor alarmDefault parameters? Set the default parameters Operating limits cooling Low Amb Cooling Low Amb LimitAlarms Alarms display and ResettingAlarms history Status, warnings and alarm messages MessageUnit status Description History events record No MessageLonTalk option DescriptionRed Service LED LED status Meaning/Function LED meaning and functionGreen Status LED LED status Meaning/Function HVACHEAT=1, HVACCOOL=3 Cable characteristics Characteristic impedance ohmsAttenuation dB/1000 feet at 20C maximum CG-SV01B-E4 CG-SV01B-E4 CG-SV01B-E4 Safety recommendations