American Standard TRACER CH532 manual Operating mode, Mode Cooling Comp seq Auto Ckt1 Enable

Page 13

Customer settings menu: “Settings”

4. Operating mode

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Mode

 

Cooling

Comp seq

 

Auto

Ckt1

 

Enable

Comp seq: Compressor sequencing

1-2: fix order

 

Single circuit

Dual circuit

 

 

Start order

A1,B1

A1, A2, B1, B2

 

Stop order

B1, A1

B2, B1, A2, A1

2-1: fix order

 

 

 

Single circuit

Dual circuit

 

 

Start order

B1,A1

A2, A1, B2, B1

 

Stop order

A1, B1

B1, B2, A1, A2

Rotation

 

 

 

Single circuit

Dual circuit

 

 

Start order

A1,B1

A1, A2, B1, B2

 

Stop order

A1,B1

A1, A2, B1, B2

Auto (default factory setting)

 

 

Ckt2

Enable

Mode: Operating mode Cooling: Cold water production (default factory setting)

Heating: Hot water production (Reversible chillers only)

Extern: (external control)

Note: When switching from cooling to heating mode or from heating to cooling mode, unit will stop for 15 s before restarting.

To allow chiller waterflow rate adjustment disable circuit 1 and 2,

The Auto sequence intend to have equivalent numbers of starts and stops and an equivalent number of compressor working hours. The compressor start order will prioritize the compressors which have the least number of working hours. Ckt1/2: Circuit 1/2 operation

Enable: circuit operational

Disable: circuit non- operational

Note: It is possible to disable both circuit 1 and 2. Water pump will be kept in operation

5. Customer Inputs and Outputs

Ana. Input External setpoint reset Y = Enabled

N = Disabled

Pump Timer: Time between unit stop (by keyboard or external contact) and stop of the pump

(1 to 10 min - factory setting = 1 min)

6. Customer outputs configuration

Alarm Out:

MR only

State Out:

Unit state

Pump Timer:

01 min

 

 

then start the unit.

To access one of the parameters

displayed, press and change

value using or . Confirm the value by pressing

Analog Input

0..10V

Ana. Input

Disable

 

 

Analog Input: Signal type 0..10V (factory setting)

0..1V 0..20mA 4..20mA

Note: the total amplitude corresponds to reset delta of +20°C between 0%(0V,OA or 4 mA) and 100% (10V,1V, or 20 mA)

Default I/O: (NO9 / NO11)

This output will be used to give an information about the circuit status: A configuration parameter will allow to choose between the following three indications concerning this circuit:

ALL: All alarms (manual and automatic reset)

ALL But LA: All alarms but without Low Ambient alarm MR only: Manual reset alarms only (factory setting)

Status output: (NO10)

Add Heat: indicate an additionnal heat demand Unit State Send data telling that at least one compressor is ON (factory setting)

CG-SVU01B-E4

13

Image 13
Contents Tracer CH532 Chiller controller User guide About this manual General informationContents Tracer CH532 Presentation Tracer CH532 inputs and outputs Hardware architectureDescription Tracer CH532 General descriptionTracer CH532 Medium Inputs and output summary listNO11, NO13 Y3 0..10V + ConvonoffCustomer Inputs and output summary list Starting/stopping the unit Menus Accessing the menusStp Local 07.0C Display menu Data displayCustomer settings menu Settings Mode Cooling Comp seq Auto Ckt1 Enable Operating modeCustomer Inputs and Outputs Status output NO10Chiller control Mode Local Remote Remote ModeClock Setting menu Clock Weekly program Program Hourly zone DisableWeekly Start Mon Stop FriUnit configuration menu Configuration Pump Pump protection input HP Control Compressors timersInvert Inverter Control dead bandsPress probe 20mA Min Press 0bar Max Press 30.0bar Sensors and transducersPT100 10V 0..1V 0..20mACompressor alarm CW High Limit 15.0C Low ambient temperature limitationDefault parameters? Set the default parameters Operating limits cooling Low Amb Cooling Low Amb LimitAlarms display and Resetting AlarmsAlarms history Message Status, warnings and alarm messagesUnit status Description No Message History events recordDescription LonTalk optionLED meaning and function Red Service LED LED status Meaning/FunctionGreen Status LED LED status Meaning/Function HVACHEAT=1, HVACCOOL=3 Characteristic impedance ohms Cable characteristicsAttenuation dB/1000 feet at 20C maximum CG-SV01B-E4 CG-SV01B-E4 CG-SV01B-E4 Safety recommendations