Carrier 17, 19EX installation instructions Frame 4 Marine Waterboxes, Pumpout Unit

Page 19

FRAME 4 MARINE WATERBOXES

COOLER WATERBOX

Pass

In

Out

Arr.

Code

 

 

 

1

8

5

A

5

8

B

 

 

7

9

C

2

4

6

D

 

16

17

G

3

7

6

E

4

9

F

 

CONDENSER WATERBOX

Pass

In

Out

Arr.

Code

 

 

 

1

11

2

P

2

11

Q

 

 

10

12

R

2

1

3

S

 

13

15

Y

3

10

3

T

1

12

U

 

 

 

 

 

NOTES:

1.The vents for these waterboxes are 1 in. FPT at the top of each box. The drains are 1 in. FPT, at the bottom.

2.Victaulic connections are standard.

3.Flanged connections are optional.

Fig. 13 Ð Nozzle Arrangements (cont)

Fig. 14 Ð Pumpout Unit

INSTALL WATER TO OIL COOLER ON FA COMPRE- SORS Ð On FA compressors, water must be piped to the oil cooler heat exchanger (located under the suction pipe to the compressor). The water supply may be either city water or chilled water. Pipe city water to an open sight drain. Chilled water enters via the cooling entering water intake (Fig. 15).

City water must be clean and noncorrosive. Water side erosion or corrosion of the oil cooler coil may lead to extensive machine damage not covered by the standard warranty.

If water from the machine chilled water circuit is used for oil cooling, it should enter the oil cooler from the entering water line of the machine cooler. Water leaving the oil cooler should connect to the leaving water line of the machine cooler at a point downstream from the chilled water sensor, so that oil cooler leaving water temperature does not affect the sen- sor readings.

Locate the oil cooler leaving water connection at some distance from any water temperature indicators. On single- pass machines, water leaving the oil cooler should be con- nected into the suction side of the chilled water pump so that adequate pressure drop is assured for oil cooling.

The nominal conditions for oil cooler water ¯ow are:

Flow rate . . . . . . . . . . . . . . . . . . . . . . . 30 gpm (1.9 L/s) Leaving temperature . . . . . . . . 85 to 100 F (29 to 38 C) Pressure drop at oil cooler . . . . . . . 7.25 psid (50 kPad) Max differential pressure across closed

solenoid valve . . . . . . . . . . . . . . 150 psid (1034 kPad)

The oil cooler connections are 11¤4 in. FPT.

19

Image 19
Contents Installation Instructions Contents Model Number Identication 19EX Typical 19EX InstallationTypical 17EX Installation 19EX Front View 17EX Front ViewTypical Top View 19EX Shown Ft-lb Item no TorqueNozzle Type Condenser LENGTH² Width Height Tube PullComponent DIAMETER²² LENGTH²² Diameter Length HeatDry Operating²² Refrigerant Condenser Total Weight Condenser ChargeRefrigerant Charge Dry Operating²² Refrigerant WaterCondenser Additional Cooler WeightsAdditional Condenser Weights Auxiliary Connection SizesTotal 17EX Drive Component Weights Total 19EX Motor Weights 60 HzTotal 19EX Motor Weights 50 Hz Compressor WeightsÐ 17EX Motors Ð Total Weight, Kg SI Ð 17EX Motors Ð Total Weight, Lbs EnglishNIH Waterbox Cover Weights Marine Waterbox Cover WeightsPsi KPa Ft-in 31-33 DimensionsCooler Sizes 31-33 Cooler SizesMachine Vibration Isolation Connect Piping Pass Out Arr NOZZLE-IN-HEAD WaterboxesFrame 3 and 5 Marine Waterboxes Cooler WaterboxPumpout Unit Frame 4 Marine WaterboxesWater Piping, Oil Cooler to Chilled Water Circuit Typical Valves Relief Valve Locations and DataPH-HZ Individual Component RatingsGeneral Page General 19EX Shown Oil Pump Wiring02525 877211¤8 Foam Tubing 15¤8 Insulation Requirements19EX Chillers Plan View Front ViewInstallation START-UP Request Checklist Testing YES/NO Date to be Completed