Table 14 Ð Individual Component Ratings
POWER SOURCE | ITEM | AVERAGE kW | DESIGN CENTER | SUPPLY | FLA | LRA | |
VOLTAGE |
| ||||||
|
|
|
|
| |||
| Seal Leakage | 0.23 | 115 | 4.78 | 21.7 | ||
1* | Pump | ||||||
|
|
|
|
| |||
(17EX Only) | Motor Space | 0.50 | 115 | 4.35 | 4.35 | ||
| Heater | ||||||
|
|
|
|
|
| ||
| Control Module | 0.40 | 115 | 3.50 | Ð | ||
| and Actuator | ||||||
1² |
|
|
|
| |||
Oil Sump Heater | 1.00 | 115 | 8.70 | Ð | |||
| |||||||
| |||||||
|
|
|
|
|
| ||
|
| 1.35 | 220 | 4.32 | 24.5 | ||
|
| 1.30 | 430 | 2.15 | 12.2 | ||
2² | Oil Pump | 1.37 | 563 | 2.13 | 25.0 | ||
|
| 1.49 | 230 | 4.83 | 28.0 | ||
|
| 1.49 | 393 | 2.59 | 12.2 | ||
1** | Hot Gas | 0.20 | 115 | 2.00 | 4.75 | ||
Bypass | |||||||
|
|
|
|
|
| ||
|
|
| 204 | 10.90 | 63.5 | ||
3** | Pumpout |
| 230 | 9.50 | 57.5 | ||
3.41 | 460 | 4.70 | 28.8 | ||||
(Optional) | Compressor | ||||||
| 575 | 3.80 | 23.0 | ||||
|
|
| |||||
|
|
| 400 | 4.70 | 28.8 |
LEGEND
FLA Ð Full Load Amps LRA Ð Locked Rotor Amps
*Available for 17EX machines only. ²Available for 17/19EX machines.
**Available as an option on 17/19EX machines.
NOTE: The oil pump is powered through a ®eld wiring terminal into the power panel. Power to the controls and oil heater via the power panel must be on circuits that can provide continuous service when the compressor starter is disconnected.