F. Water Supply and Drain Connections

WARNING

1.Water supply and drain connections must be installed in accordance with applicable national, state, and local regulations.

2.Normal operating water temperature should be within 45°F to 95°F (7°C to 35°C). Operation of the icemaker, for extended periods, outside of this normal temperature range may affect icemaker performance.

3.To prevent damage to equipment, do not operate the icemaker when the water supply is off, or if the pressure is below 10 PSIG. Do not run the icemaker until the proper water pressure is reached.

A plumbing permit and services of a licensed plumber may be required in some areas.

External filters, strainers, or softeners may be required depending on water quality. Contact your local Perlick distributor for recommendations.

Water supply inlet is 1/2" female pipe thread (FPT).

A water supply line shut-off valve and drain valve should be installed. A minimum of 3/8" OD copper tubing is recommended for the water supply line.

Water supply pressure should be a minimum of 10 PSIG and a maximum of 113 PSIG. If the pressure exceeds 113 PSIG, the use of a pressure reducing valve is required.

Drain outlet is 1/2" FPT.

Drain line should not be piped directly to the sewer system. An air gap of a minimum of 2 vertical inches (5 cm) should be between the end of the drain pipe from the icemaker and the floor drain.

For gravity drain installation, drain must have 1/4" fall per foot (2 cm per 1 m) on horizontal runs to get good flow. A vented tee connection is also required for proper flow.

For optional drain pump installation, refer to the instruction manual included with the pump.

Water Supply Line

Shut-Off Valve

Water Supply Line

Drain Valve

Water Supply Inlet 1/2" FPT

Piping to approved drain. Leave a 2inch (5-cm) vertical air gap between the end of the pipe and the drain.

2-inch (5-cm) air gap

Vented Tee Connection

Drain Outlet 1/2" FPT

DrainFloor

Fig. 23

21

Image 21
Contents Perlick Contents Serious injury Important Safety InformationIndicates important information about the use and care UnitSpecifications A. Construction Nameplate Rating Perlick ICE MakerH50IMS-R, H-50IMS-L Dimensions/ConnectionsH50IMW H50IMS-ADL, H50IMS-ADR H50IMW-AD Checks Before Installation II. Installation and Operating InstructionsLocation GeneralBuilt-In Installation Site A CornerBetween a Cabinet and a Wall or Tall Cabinet Parts H50IMW Overlay Panel Specification Overlay Panel SpecificationH50IMW-AD Overlay Panel Specification Fabrication of Overlay Panel Screws Top Panel Notch Hinge B Filler BushingGasket Hinge Attachment of Overlay Panel to Door Bushing Gasket Electrical Connection SetupWater Supply and Drain Connections Final Checklist Startup Cleaning and Sanitizing Instructions III. Cleaning and MaintenanceCleaning Solution Cleaning ProcedureTabs Sanitizing Procedure Sanitizing SolutionDischarge Tube Caps Spray Assembly Separator Slope Rail Stainless Steel Exterior MaintenanceStorage Bin and Scoop CondenserPreparing the Icemaker for Long Storage 