To initiate a Manual Defrost, press and hold the MAN DEF key for 3 seconds.
There are two levels of programming in the ERC 2. The first level of security will enable the user to set two parameters:
Three buttons are used for the programming: SET, UP and DOWN
Fig. 4 – Display Lay-out
To change
Step 1 |
| Press and hold set for 5 seconds. The display will show CLoC |
|
|
|
Step 2 |
| Press SET again to change the |
|
|
|
Step 3 |
| Press UP or DOWN until the correct |
| or |
|
Step 4 |
| Press SET to accept the new time |
|
|
|
Step 5 |
| Press DOWN to go to the next parameter – Set point |
|
| Temperature - (cut out) |
|
|
|
Step 6 |
| Press SET to change the set point temperature |
|
|
|
Step 7 |
| Press UP or DOWN to go to the desired set point. The range is |
| or | – 40 to 60°F or |
Step 8 |
| Press SET to accept the change |
|
|
|
Step 9 |
| Press DOWN to exit the first level of programming |
|
|
|
Note 1: During programming, if no button is pushed during 30 seconds, the control will go back to the normal operating mode. This is valid for both programming levels.
Note 2: When changing the time, press and hold the MAN DEF button for 3 seconds to change the AM/PM mode.
Note 3:
Note 4: If demand defrost (ddEF) is used, the minimum number of defrost is 1 per 24 hours.
9