Master Bilt TAF-48 ERC2, TAF-27 ERC2 Press and hold set for 5 seconds. The display will show CLoC

Page 9

To initiate a Manual Defrost, press and hold the MAN DEF key for 3 seconds.

There are two levels of programming in the ERC 2. The first level of security will enable the user to set two parameters: Time-of-day (CLoC) and Set point temperature (SEt). The other level allows access to the other parameters.

Three buttons are used for the programming: SET, UP and DOWN

Fig. 4 – Display Lay-out

To change time-of-day and set point temperature (First Level) follows these steps:

Step 1

 

Press and hold set for 5 seconds. The display will show CLoC

 

 

 

Step 2

 

Press SET again to change the time-of-day

 

 

 

Step 3

 

Press UP or DOWN until the correct time-of-day is displayed

 

or

 

Step 4

 

Press SET to accept the new time

 

 

 

Step 5

 

Press DOWN to go to the next parameter – Set point

 

 

Temperature - (cut out)

 

 

 

Step 6

 

Press SET to change the set point temperature

 

 

 

Step 7

 

Press UP or DOWN to go to the desired set point. The range is

 

or

– 40 to 60°F or –40 to 16°C

Step 8

 

Press SET to accept the change

 

 

 

Step 9

 

Press DOWN to exit the first level of programming

 

 

 

Note 1: During programming, if no button is pushed during 30 seconds, the control will go back to the normal operating mode. This is valid for both programming levels.

Note 2: When changing the time, press and hold the MAN DEF button for 3 seconds to change the AM/PM mode.

Note 3: Master-Bilt’s Set point Temperature (Set) is set at a recommended –10°F at the factory for low temperature(LT) and +35oF for medium temperature(MT) application.

Note 4: If demand defrost (ddEF) is used, the minimum number of defrost is 1 per 24 hours.

9

Image 9
Contents Master-Bilt Products Installation & Operations ManualPage Table of Contents Store Conditions IntroductionGround Required For Safe Operation Installation Instructions PRE-INSTALLATION Instructions Inspection for Shipping Damage MechanicalElectrical ERC 2 Electronic Refrigeration Control Low Temperature Freezers TAF ModelsPress and hold set for 5 seconds. The display will show CLoC Elec Con ALHi Error Codes Display Control StatusTemperature Resistance Ohms Sensor Probe Temperature and ResistanceFinal Check List Sensor ProbeService Instructions Trouble Shooting Guide MASTER-BILT Part Numbers Owner Responsibility Sale and Disposal